Plan Review Details - Permit 09120128
Plan Review Stops For Permit 09120128
Review Stop P PLUMBING
Rev No 2 Status P Date 2010-01-07 Cont ID  
Sent By kstevens Date 2010-01-07 Time 15:48 Rev Time 0.00
Received By kstevens Date 2010-01-07 Time 15:48 Sent To  
Notes
2010-01-07 15:48:50CONTRACTOR TO REFERENCE PLANS REFERENCED IN MASTER
 PERMIT.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-12-10 Cont ID  
Sent By kstevens Date 2009-12-10 Time 16:29 Rev Time 0.00
Received By kstevens Date 2009-12-10 Time 16:28 Sent To  
Notes
2009-12-10 16:45:41DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FLORIDA STATUTES
 FLORIDA ADMINISTRATIVE CODE
  
 1. SHTS L-6.O & L-6.1 THE PLANS SHALL BE SIGNED, SEALED
 & DATED PER SECTION 106.1 & FS 481.
  
 2. PLANS SHALL SHOW THE LOCATION OF THE WATER SOURCE,
 BACKFLOW PREVENTER (IF REQUIRED), CONTROLLER & RAIN
 SENSOR. SECTIONS 106.1.1, 608 & APPENDIX F PART II(J) &
 FS 373.62.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  