Plan Review Details - Permit 09120074
Plan Review Stops For Permit 09120074
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-01-05 Cont ID  
Sent By mawillia Date 2010-01-05 Time 15:57 Rev Time 0.00
Received By mawillia Date 2010-01-05 Time 15:13 Sent To  
Notes
2010-01-05 15:34:13*****APPROVED*****
  
 THE COMMENT FROM THE PREVIOUS PLAN REVIEW HAS BEEN
 ADDRESSED. THE THREE SHEETS OF THE FIRE ALARM PLAN
 FIRE-STAMPED ACCORDINGLY; READY FOR PERMIT ISSUANCE.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-12-10 Cont ID  
Sent By mawillia Date 2009-12-10 Time 15:29 Rev Time 0.00
Received By mawillia Date 2009-12-10 Time 15:06 Sent To  
Notes
2009-12-10 15:26:51*****DENIED*****
  
 1. VERIFY THAT THE AMPERAGE FOR THE HORN STROBE DEVICES
 SHOWN IN THE FIRE ALRM PLAN CORRELATES WITH THAT IN THE
 FIRE ALARM RISER DIAGRAM WHICH IN TURN SHOULD BE
 REFLECTED IN THE BATTERY CALCULATIONS.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-29 Cont ID  
Sent By btrobaug Date 2009-12-29 Time 08:19 Rev Time 0.00
Received By btrobaug Date 2009-12-29 Time 08:18 Sent To FIRE
Notes
2009-12-29 08:19:52TO FIRE IN BOX./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-10 Cont ID  
Sent By mawillia Date 2009-12-10 Time 15:06 Rev Time 0.00
Received By mawillia Date 2009-12-07 Time 14:42 Sent To  
Notes
2009-12-07 14:43:16SENT TO FIRE BOX.