Plan Review Details - Permit 09120068
Plan Review Stops For Permit 09120068
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2010-02-16 Cont ID  
Sent By jgomez Date 2010-02-16 Time 11:21 Rev Time 0.00
Received By jgomez Date 2010-02-16 Time 11:21 Sent To  
Notes
2010-02-16 11:22:37ENERGY CALCULATIONS WITH ENGINEER'S SEAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jgomez Date 2010-02-03 Time 13:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-02-02 Cont ID  
Sent By jgomez Date 2010-02-02 Time 14:48 Rev Time 0.00
Received By jgomez Date 2010-02-02 Time 14:47 Sent To  
Notes
2010-02-02 14:49:31BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- A) PROVIDE REVISED ENERGY CALCULATIONS. NEED TO USE
 FORM 1100B-08.
 B) ENGINEER WHO PREPARED THE ENERGY CALCULATIONS NEED
 TO PROVIDE ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE.
 C) COMPLETE ALL THE INFORMATION ON SECOND PAGE OF
 ENERGY CALCULATIONS SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-16 Cont ID  
Sent By jgomez Date 2009-12-16 Time 15:05 Rev Time 0.00
Received By jgomez Date 2009-12-16 Time 15:05 Sent To  
Notes
2009-12-16 15:20:34RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE.
 ***NOTE: PLEASE MAKE SURE ALL THE INFORMATION IS
 PROVIDED AND FORM IS PROPERLY SIGNED AND DATED BY THE
 REQUIRED PARTIES.
  
 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF CLAY TILE. NOA 06-1213.03 SUBMITTED FOR THE
 MISSION CLAY TILE EXPIRED ON 05/20/09. NEED TO PROVIDE
 CURRENT NOA.
  
 B) ROOF TILE ADHESIVE. SEE CLAY TILE PRODUCT APPROVAL
 FOR LISTED ADHESIVES.
  
 C) FLAT ROOF NOA 07-0730.03. PROVIDE RAS 117
 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE
 OF NOA.
 C(1) SPECIFY WHICH APPROVED ASSEMBLY AND BASE SHEET
 FASTENING OPTION IS GOING TO BE USED FROM NOA
 SUBMITTED.
  
 3- OWES $4117.68 WHICH IS THE BALANCE FOR THE PERMIT
 FEE.
  
 4- SHEET A301. REVISE STUCCO SPECIFICATIONS ON SECTIONS
 THRU KITCHEN AND MASTER BATHROOM. TABLE R703.4 DOESN'T
 APPLY TO STUCCO. SEE TABLE R702.1(1) AND REVISE STUCCO
 THICKNESS AS REQUIRED.
 ALSO, SPECIFY TWO LAYERS OF WATER-RESISTANT BARRIER AS
 REQUIRED BY SEC. R703.6.3.
  
 5- PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 POLYCYNENE INSULATION TO BE USED TO VERIFY REQUIRED
 THICKNESS AND COORDINATE WITH THE ENERGY CALCULATIONS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-02-02 Cont ID  
Sent By btrobaug Date 2010-02-02 Time 15:08 Rev Time 0.00
Received By btrobaug Date 2010-02-02 Time 14:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-12-16 Cont ID  
Sent By btrobaug Date 2009-12-16 Time 17:01 Rev Time 0.00
Received By btrobaug Date 2009-12-15 Time 13:36 Sent To  
Notes
2009-12-16 14:11:40 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.
  
 THIS PLAN IS BEING PASSED TO FACILITATE THE START OF
 THIS PROJECT, THE PLANS HOWEVER ARE DEFICIENT, AND THE
 FOLLOWING ITEMS NEED CORRECTING:
  
 COMMENTS RELATING TO SHEET E-3
  
 1} THE SMOKE ALARMS ARE SHOWN ON CIRCUIT A-29 WHICH IS
 LABELED AS AHU-3 IN THE PANEL SCHEDULE. NOTE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED PER
 313.2.1 TO EXISTING ALARMS AS WELL. CIRCUIT B-26 IS
 LABELED SMOKE DETECTOR.
  
 2} CIRCUIT B-15 MUST BE A SMALL APPLIANCE CIRCUIT PER
 210.52(B)(1) "RECEPTACLE OUTLETS SERVED IN THE KITCHEN,
 PANTRY, BREAKFAST ROOM, DINING ROOM, OR SIMILAR AREA OF
 A DWELLING UNIT, THE TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY
 210.11(C)(1) SHALL SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS COVERED BY 210.52(A), ALL COUNTERTOP OUTLETS
 COVERED BY 210.52(C), AND RECEPTACLE OUTLETS FOR
 REFRIGERATION EQUIPMENT." THE CIRCUIT IS LISTED AS 20
 AMP IN THE PANEL SCHEDULE, BUT IS LABELED AS " GENERAL
 USE".TO AVOID CONFUSION IN THE FIELD CHANGE TO
 BREAKFAST ROOM OR SMALL APPLIANCE.ALSO ONE RECEPTACLE
 ON THAT CIRCUIT IS IN THE KITCHEN WHICH IS NOT A
 VIOLATION AS LONG AS IT IS SMALL APPLIANCE.
  
 3} THE TRASH COMPACTOR SHOWN ON SHEET A401 IS NOT
 CIRCUITED IN THE ISLAND AND IS NOT LISTED IN THE PANEL
 SCHEDULE OR THE LOAD CALCULATION. CORRELATE SAME.
  
 COMMENTS RELATING TO SHEET E-5:ELECTRICAL RISER
 DIAGRAM.
  
 3} THE #4 CU GROUND RAN WITH THE FEEDERS FROM THE METER
 TO THE FIRST MEANS OF DICONNECT (PANEL "A") CREATES A
 PARALLEL PATH TO GROUND WITH THE NEUTRAL AND MUST BE
 REMOVED. AN ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE
 TO BE RAN FROM THE FIRST MEANS OF DISCONNECT. 250.6.
 250.24 (A)(5)
  
 4} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. THIS IS
 BEING ASED FOR DUE TO RELOCATION OF THE SERVICE.
  
 5} AN INTERSYSTEM BONDING TERMINAL PER 250.94 WILL BE
 REQUIRED AT THE RELOCATED SERVICE.
  
 PLEASE RESUBMIT A REVISION SHOWING ACTUAL CONDITIONS
 PRIOR TO CALLING ROUGH ELECTRICAL INSPECTION. THE
 REVIEWED PLAN MUST BE ON THE JOB SITE AT TIME OF
 INSPECTION. ALLOW AT LEAST ONE WEEK (PER TRADE) FOR
 PLAN REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2010-02-08 Cont ID  
Sent By kstevens Date 2009-12-15 Time 10:50 Rev Time 0.00
Received By kstevens Date 2009-12-15 Time 10:49 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2009-12-02 Cont ID  
Sent By swurafti Date 2009-12-02 Time 16:03 Rev Time 0.00
Received By swurafti Date 2009-12-02 Time 16:03 Sent To  
Notes
2009-12-02 16:04:09HISTORIC APPROVED BY JPAPA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-01-26 Cont ID  
Sent By lmartine Date 2010-01-25 Time 13:42 Rev Time 0.00
Received By lmartine Date 2010-01-25 Time 13:42 Sent To  
Notes
2010-01-26 13:52:13R--7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-01-13 Cont ID  
Sent By shill Date 2010-01-13 Time 11:07 Rev Time 0.00
Received By shill Date 2009-12-03 Time 12:55 Sent To  
Notes
2009-12-03 12:57:49SENT TO R-7.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2010-02-02 Cont ID  
Sent By jgomez Date 2010-02-02 Time 16:36 Rev Time 0.00
Received By jgomez Date 2010-02-02 Time 14:54 Sent To  
Notes
2010-02-02 16:37:31NO FEES DUE. PALM BEACH COUNTY STAMPED PLANS ON
 1/25/10.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2009-12-16 Cont ID  
Sent By jgomez Date 2009-12-16 Time 15:05 Rev Time 0.00
Received By jgomez Date 2009-12-16 Time 15:05 Sent To  
Notes
2009-12-16 15:06:53NEED TO BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG
 RD) TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-02-02 Cont ID  
Sent By jgomez Date 2010-02-02 Time 14:40 Rev Time 0.00
Received By jgomez Date 2010-02-02 Time 14:40 Sent To  
Notes
2010-02-02 14:43:34MECHANICAL REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE UPDATED ENERGY CALCULATIONS. SEC. N1100.2.2.
 NEED TO PROVIDE FORM 1100B-08. ENGINEER WHO PREPARED
 CALCULATIONS TO PROVIDE ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTES.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-01-05 Cont ID  
Sent By jgomez Date 2010-01-05 Time 10:25 Rev Time 0.00
Received By jgomez Date 2010-01-05 Time 10:25 Sent To  
Notes
2010-01-05 10:47:38RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.2.2 OF THE 2007 FLORIDA RESIDENTIAL CODE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-12-16 Cont ID  
Sent By kstevens Date 2009-12-16 Time 16:16 Rev Time 0.00
Received By kstevens Date 2009-12-16 Time 16:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2010-02-01 Cont ID  
Sent By ajones Date 2010-02-01 Time 16:23 Rev Time 0.00
Received By ajones Date 2010-02-01 Time 16:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-01-08 Cont ID  
Sent By astelly Date 2010-01-08 Time 17:38 Rev Time 0.00
Received By astelly Date 2010-01-08 Time 17:38 Sent To I
Notes
2010-01-08 17:49:42AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
  
 PLEASE SUBMIT A SURVEY OF THE PROPERTY SHOWING THE
 EXISTING CURB CUT FOR THE PROPERTY.