Plan Review Details - Permit 09120061
Plan Review Stops For Permit 09120061
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-16 Cont ID  
Sent By jwitmer Date 2009-12-16 Time 12:58 Rev Time 1.50
Received By jwitmer Date 2009-12-16 Time 07:00 Sent To  
Notes
2009-12-16 13:01:32BUILDING PLAN REVIEW
 PERMIT: 09120061
 ADD: 222 LAKEVIEW SUITE# 550
 CONT: MIAMI SYSTEMS
 TEL: (561)394-5450
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 DEC. 16/ 2009
  
  
 1) G3 ARCHITECTURE DESIGN & PLANNING HAS NOT PROVIDED
 THE REQUIRED CERTIFICATE OF AUTHORIZATION REQUIRED BY
 THE ARCHITECTURAL BOARD AND STATE ADMINISTRATIVE CODE,
 481.219 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET.
  
 2) SHEET A0.1:
 2A) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDER THIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2B) PROJECT DATA: TYPE OF BUILDING DECLARED IS A TYPE
 I-B PLEASE SEE THIS BUILDING IS OVER 12 STORIES IN
 HEIGHT REQUIRING IT TO BE A TYPE I-A BUILDING , SEE
 TABLE 503.
  
 2C) PROJECT DATA INDICATES THE USE GROUP AS A A-2UNDER
 THE IBC, PLEASE SEE FLORIDA BUILDING CODE SECTION 303
 A-3 (GYMNASIUMS WITHOUT SPECTATOR SEATING).
  
 2D) PROJECT DATA INDICATES THE OCCUPANT LOAD OF 30 AND
 FACTOR OF 1/100, PLEASE REVIEW TABLE 1004.1.1 FOR
 EXERCISE ROOM WITH EQUIPMENT 50 GROSS AND LOCKER ROOMS
 50 GROSS, PLEASE MAKE CORRECTIONS.
  
 2E) PROJECT DATA, DOES NOT INDICATE IF THE HI-RISE IS
 SPRINKLED OR NOT?
  
  
 3) SHEET A2.0;
 3A) PLANS INDICATE ONLY ONE EXIT, PLEASE REVIEW TABLE
 1015.1 FOR A OCCUPANCIES WITH OCCUPANT LOADS GREATER
 THAN 49 TWO EXITS WILL BE REQUIRED.
  
 3B) THE DRINKING FOUNTAIN NITCH DOES NOT INDICATE THE
 WIDTH OF THE NITCH FIGURE 27. PLEASE ALSO PROVIDE THE
 CLEAR FLOOR SPACE FOR THE DRINKING FOUNTAIN ON SHEET
 A6.0. 11-4.15.5 CLEARANCES.
  
 3C) ROOM 014 AND DOOR# 14 APPEARS TO BE MISSING THE
 18??? MANEUVERING DISTANCE ON THE LATCH SIDE. 11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE FLOOR
 OR GROUND AREA WITHIN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 3D) PLEASE SEE IN BOTH RESTROOMS WITHIN THE ENTRY AND
 THE TURNING AROUND OBSTRUCTIONS FIGURE 7B WHEN X< 48
 INCHES.
  
 3E) PLANS FAIL TO PROVIDE A LAVATORY WITHIN THE
 ACCESSIBLE TOILET STALL. ACCESSIBLE STALLS BOTH
 RESTROOMS, PLEASE SEE 912.8 OF THE EXISTING BUILDING
 CODE, CHANGE OF OCCUPANCY AND THE REQUIREMENTS FOR
 ACCESSIBILITY SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE. 11-4.1.6(1)(B) EXISTING
 ELEMENTS, SPACES, OR COMMON AREAS ARE ALTERED, THEN
 EACH SUCH ALTERED ELEMENT, SPACE, FEATURE, OR AREA
 SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION
 11-4.1.1 TO SECTION 11-4.1.3, MINIMUM REQUIREMENTS FOR
 NEW CONSTRUCTION. IF THE APPLICABLE PROVISION FOR NEW
 CONSTRUCTION REQUIRES THAT AN ELEMENT, SPACE, OR COMMON
 AREA BE ON AN ACCESSIBLE ROUTE, THE ALTERED ELEMENT,
 SPACE.
  
 11-4.1.3(11) TOILET FACILITIES. IF TOILET ROOMS ARE
 PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY WITH SECTION 11-4.22. OTHER TOILET ROOMS
 PROVIDED FOR THE USE OF OCCUPANTS OF SPECIFIC SPACES
 (I.E., A PRIVATE TOILET ROOM FOR THE OCCUPANT OF A
 PRIVATE OFFICE) SHALL BE ADAPTABLE. IF BATHING ROOMS
 ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE BATHROOM
 SHALL COMPLY WITH SECTION 11-4.23. ACCESSIBLE TOILET
 ROOMS AND BATHING FACILITIES SHALL BE ON AN ACCESSIBLE
 ROUTE.
  
 4) PLANS ARE MISSING DOOR SCHEDULE INDICATING THE SIZE
 OF THE DOORS, 1008.1.1.
  
 5) SHEET A.6 FURNITURE PLAN, WITH THE LAY OUT OF THE
 FURNITURE PLAN IT IS APPARENT THAT WITH THE SINGLE EXIT
 COMMON PATH OF TRAVEL IS A ISSUE, SEE SECTION 1014.3
 (5)
 WHERE A TENANT SPACE IN GROUP A OCCUPANCY HAS AN
 OCCUPANT LOAD OF MORE THAN 50, THE LENGTH OF A COMMON
 PATH OF EGRESS TRAVEL SHALL NOT BE MORE THAN 20 FEET
 (6098 MM).
  
 6) SHEET A5 PLEASE PROVIDE THE SMOKE DEVELOPMENT AND
 FLAME SPREAD RATINGS PER SECTION 803.1 AND TABLE 803.5.
 FOR WALL FINISHES.
  
 7) NOTE PLANS DO NOT INDICATE ANY EXTERIOR WALL
 SECTIONS, INSULATION NOR THE HEIGHT OF GYPSUM ABOVE THE
 FINISH CEILING. PLEASE SEE COMMENT IF FOAM INSULATION
 IS TO BE USED AS THE EXTERIOR
 WALL INSULATION. MECHANICAL CODE 602.2.1.5.1-
 PLENUMS!!!
  
 602.2.1.5 FOAM PLASTIC INSULATION. FOAM PLASTIC
 INSULATION USED AS WALL OR CEILING FINISH IN PLENUMS
 SHALL EXHIBIT A FLAME SPREAD INDEX OF 75 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF 450 OR LESS WHEN TESTED IN
 ACCORDANCE WITH ASTM E 84 AND SHALL ALSO COMPLY WITH
 SECTION 602.2.1.5.1, 602.2.1.5.2 OR 602.2.1.5.3.
  
 602.2.1.5.1 SEPARATION REQUIRED. THE FOAM PLASTIC
 INSULATION SHALL BE SEPARATED FROM THE PLENUM BY A
 THERMAL BARRIER COMPLYING WITH SECTION 2603.4 OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 8) CHANGE IN OCCUPANCY: BEFORE A PERMIT TO CONSTRUCT,
 MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-15 Cont ID  
Sent By dpalmer Date 2009-12-15 Time 13:49 Rev Time 0.00
Received By dpalmer Date 2009-12-15 Time 13:49 Sent To  
Notes
2009-12-15 13:49:37 
 ** DENIED
  
  
  
 1) NOTE: THE ARCHITECTURAL TITLE BLOCK IS MISSING THE
 REQUIRED FIRM LICENSE NUMBER. THIS IS ALSO KNOWN AS THE
 CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE SEE FLORIDA
 STATUTES 481.219 WHICH REQUIRES THE FIRM LICENSE
 NUMBER. PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 WHICH REQUIRES THE NUMBER TO BE ON THE
 TITLE BLOCK.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY
 OTHER TRADE.
  
 2) NOTE: THE FOLLOWING MINIMUM CODES ARE REQUIRED TO BE
 ON PLANS. SOME OF CODES LISTED ARE INCORRECT.
 PLANS INDICATE 2004 FBC ON E3, HOWEVER AS OF MARCH 1ST
 2009 THE STATE ADOPTED THE 2007 FBC W/ 2009
 SUPPLEMENTS.
 PLANS ALSO INDICATE A 2005 NFPA-101 ON E-3. THERE WAS A
 2003 NFPA-101 AND AS OF DECEMBER 31ST, 2008 THE STATE
 ADOPTED THE 2006 NFPA-101.
 THE PLANS INDICATE THE 2005 NFPA-70 ( NEC), HOWEVER AS
 OF OCTOBER 1ST, 2009 THE STATE ADOPTED THE 2008 NFPA-70
 ( NEC).
 THE ADOPTION OF NFPA CODES REFERENCED BY THE FLORIDA
 BUILDING CODE ADOPTION PROCESS AND BY THE STATE FIRE
 MARSHAL CAN BE FOUND IN FAC 69A-60.003,.004, 69A-3.012
 THE ARCHITECTURAL PLANS AND ELECTRICAL PLANS NEED TO
 CONTAIN THE FOLLOWING CODES WHICH ARE RELEVANT TO THE
 DESIGN.
  
 2007 FBC W/2009 SUPPLEMENTS. ( INCLUDING 2ND SET OF
 2009 SUPPLEMENTS).
 2008 NFPA-70
 2002 NFPA-72
 2006 NFPA-101
  
 POSSIBLE TO BE NOTED BY FIRE PLAN REVIEW:
 2006 NFPA-1
 2007 FLORIDA FIRE PREVENTION CODE
  
 3) NOTE: NOTE #1 ON SHEET E2 MENTIONS SOME SORT OF
 LIGHTING SWITCHING TO ALLEVIATE MORE LIGHTING BEING ON
 FOR ENERGY CODE COMPLIANCE. HOWEVER PLEASE PROVIDE
 DETAIL ON WHAT WILL TAKE PLACE OR HOW THIS DEVICE WILL
 ACHIEVE COMPLIANCE. HOW WILL LIGHTING BE AUTOMATED?
 WILL THE SWITCHING LOCATIONS BE ON THE LOAD SIDE OF THE
 OCCUPANCY SENSORS?
 13-415.AB.1.1, .1.2.
  
  
  
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-12-23 Cont ID  
Sent By mawillia Date 2009-12-23 Time 14:25 Rev Time 0.00
Received By mawillia Date 2009-12-23 Time 13:06 Sent To  
Notes
2009-12-23 13:43:53******DENIED*****
  
  
 1. THE SCOPE OF WORK IS PROJECTED IN SUITE 550 WHICH IS
 ADJACENT TO SUITE 800. IS THIS THE 5TH FLOOR OR THE 8TH
 FLOOR? PLEASE EXPLAIN.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 3. AS OF 12/31/08, THE 2007 FLORIDA FIRE PREVENTION
 CODE BASED ON NFPA 101, LIFE SAFETY CODE, 2006 EDITION
 AND NFPA 1, UNIFORM FIRE CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 4. PLEASE DECLARE THE NEW OCCUPANCY TYPE/USAGE AND THE
 OCCUPANT LOAD BASED ON THAT OCCUPANCY TYPE.
  
 5. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFYING THE 75; TRAVEL
 DISTANCE.
  
 6. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS
 AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-12-23 Time 14:28 Rev Time 0.00
Received By kstevens Date 2009-12-03 Time 12:51 Sent To  
Notes
2009-12-15 16:43:17********************EXPEDITED***********************
 AS OF 12/15/09
2009-12-03 12:54:59SENT TO C-2.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-12-21 Cont ID  
Sent By rregueir Date 2009-12-21 Time 15:52 Rev Time 0.00
Received By rregueir Date 2009-12-21 Time 15:52 Sent To  
Notes
2009-12-21 15:53:11**PROVISO**
  
 PROVIDE DUCT SMOKE DETECTORS ON SUPPLY SIDE OF EACH NEW
 HEAT PUMP IN ACCORDANCE WITH FBC-M 606.2.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-12-21 Cont ID  
Sent By kstevens Date 2009-12-21 Time 07:32 Rev Time 0.00
Received By kstevens Date 2009-12-16 Time 17:56 Sent To  
Notes
2009-12-21 07:48:50DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 BUILDING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
 FBC-2007 EXISTING BLDG
 FLORIDA STATUTES
 FLORIDA ADMINISTRATIVE CODE
  
 1. ALL SHEETS WITH G3 ARCHITECTURAL TITLE BLOCKS SHALL
 HAVE THE BUSINESS LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION) IN THE TITLE BLOCK. FAC 61G1-14.004(2) &
 FS 481.2055.
  
 2. PER SECTION 401.1 A LEVEL OF ALTERATION SHALL BE
 ELECTED.
  
 3. SHT A2.0 ACCESSIBLE TOILET STALLS SHALL REQUIRE A
 LAV. SECTION 11-4.17.3 & FIG 30E.
  
 4. SHOW COMPLIANCE WITH THE FOLLOWING:
 ___FOR DRINKING FOUNTAIN:
 A. 11-4.15.3 SPOUT LOCATION/HEIGHT
 B. 11-4/15/5 CLEARANCES & CLEAR FLOOR SPACE
 C. 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ___FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 ___FOR BATHROOMS:
 A. 11-4.22.3 TURNING AREA
  
 5. SHT A5.0 PER SECTION 1210.2 WALLS WITHIN 2 FEET OF
 THE W/C'S SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT
 SURFACE TO A HEIGHT OF 4 FEET ABOVE THE FLOOR. PLEASE
 CLARIFY HOW VINYL WALL COVERING WILL COMPLY. SUBMIT
 MANUF. SPECIFICATIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved