Plan Review Details - Permit 09120046
Plan Review Stops For Permit 09120046
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-02-04 Cont ID  
Sent By jwitmer Date 2010-02-04 Time 15:18 Rev Time 2.00
Received By jwitmer Date 2010-02-02 Time 16:27 Sent To  
Notes
2010-02-03 07:59:01 
 BUILDING PLAN REVIEW
 PERMIT: 09120046
 ADD: 340 CLEMATIS ST
 CONT: GERARD CONTRACTING, INC.
 TEL: (561)281-5225
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING APPROVED WITH EXCEPTION!
  
 1)THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).PRODUCT APPROVALS
 SHALL BE SUBMITTED BEFORE ROUGH BUCK / FRAMING
 INSPECTION.
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 A) EXTERIOR GLAZED DOOR
 B) EXTERIOR BI-FOLD DOORS SOLAR INNOVATIONS
 C) FRENCH DOORS
 D) FIXED IMPACT WINDOWS
 E) PRE-MANUFACTURED A/C STANDS
 F) WALL LOUVER
 G) BAHAMA SHUTTERS
  
 2) BUILDING APPROVED WITH EXCEPTION! THIS PLAN HAS BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND THE ASSESSMENT OF
 RE-INSPECTION FEE(S). 106.3.3 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 3) BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). PLEASE PROVIDE
 MANUFACTURERS SPECS FOR WALK IN COOLER AND ACCORDANCE
 WITH 2603.4.1.3.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-01-12 Cont ID  
Sent By jwitmer Date 2010-01-12 Time 08:15 Rev Time 0.00
Received By jwitmer Date 2010-01-12 Time 08:01 Sent To  
Notes
2010-01-12 08:25:09BUILDING PLAN REVIEW
 PERMIT: 09120046
 ADD: 340 CLEMATIS ST
 CONT: GERARD CONTRACTING, INC.
 TEL: (561)281-5225
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 JAN. 12/2009
  
 1) COMPLIED, UPDATE VALUE TO $220,000.00.
  
 2) COMPLIED.
  
 3) COVER SHEET INDICATES THIS BUILDING TO BE CONSIDERED
 A III-B SPRINKLERED BUILDING LEVEL IL ALTERATION.
 PLEASE SEE EXISTING BUILDING CODE (CHAPTER 9- CHANGE OF
 OCCUPANCY) AND SECTION 912.
  
 3A) COMPLIED.
  
 3B) COMPLIED.
  
 3C) 2ND REQUEST, THE PLAN REVISION COVERSHEET INDICATES
 NOW THE SPACE TO BE FIRE SPRINKLERED, BUT NO FIRE
 SPRINKLER SCHEMATIC PLANS WERE SUBMITTED. 912.2 FL
 EXISTING BUILDING CODE. 912.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 912.2.1 AND 912.2.2.
  
 912.2.1 FIRE SPRINKLER SYSTEM. WHERE A CHANGE IN
 OCCUPANCY CLASSIFICATION OCCURS THAT REQUIRES AN
 AUTOMATIC FIRE SPRINKLER SYSTEM TO BE PROVIDED BASED ON
 THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF THE
 FLORIDA BUILDING CODE, BUILDING , SUCH SYSTEM SHALL BE
 PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS.
  
 2007 FBC- BUILDING, 903.2.1.2 GROUP A-2. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE PROVIDED FOR GROUP A-2
 OCCUPANCIES WHERE ONE OF THE FOLLOWING CONDITIONS
 EXISTS:
 (2). THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE.
  
 4-6) COMPLIED.
  
 7) COMPLIED.
 8) COMPLIED.
  
 9) BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 9A) EXTERIOR GLAZED DOOR
 9B) EXTERIOR BI-FOLD DOORS SOLAR INNOVATIONS
 9C) FRENCH DOORS NOTE# 6
 9D) FIXED IMPACT WINDOWS
 9E) PRE-MANUFACTURED A/C STANDS
 9F) WALL LOUVER
 9G) BAHAMA SHUTTERS
  
 10)BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
 2ND REQUEST. PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 11) BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 12) COMPLIED, NO BUCKS TO BE INSTALLED PER DESIGNER OF
 RECORD.
  
 13) BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
 PLEASE PROVIDE MANUFACTURERS SPECS FOR WALK IN COOLER
 AND ACCORDANCE WITH 2603.4.1.3.
  
 14) COMPLIED.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-07 Cont ID  
Sent By jwitmer Date 2009-12-07 Time 12:22 Rev Time 2.00
Received By jwitmer Date 2009-12-07 Time 12:22 Sent To  
Notes
2009-12-07 18:24:00BUILDING PLAN REVIEW
 PERMIT: 09120046
 ADD: 340 CLEMATIS ST
 CONT: GERARD CONTRACTING, INC.
 TEL: (561)281-5225
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 DEC. 07/2009
  
 1) LOW EVALUATION PLEASE REVIEW WORK TO BE COMPLETED
 UNDER THIS PERMIT AND CONSTRUCTION VALUE. W P B
 ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON
 BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, AND
 PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A
 FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) CHANGE OF OCCUPANCY: BEFORE A PERMIT TO CONSTRUCT,
 MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 3) COVER SHEET INDICATES THIS BUILDING TO BE CONSIDERED
 A III-B UNSPRINKLERED BUILDING LEVEL ???LL ALTERATION.
 PLEASE SEE EXISTING BUILDING CODE (CHAPTER 9- CHANGE OF
 OCCUPANCY) AND SECTION 912.
  
 3A) PLANS DO NOT INDICATE WHERE THE 2HR OCCUPANCY WALL
 WILL BE PLACED SEPARATING THE TENANCY FROM THE COMMON
 AREAS AND THE 2ND FLOOR BUSINESS OCCUPANCIES. 2009 FBC
 ??? BUILDING. 803.9.1.2 FIRE-RESISTANCE-RATED
 CONSTRUCTION. ACOUSTICAL CEILING SYSTEMS THAT ARE PART
 OF FIRE-RESISTANCE-RATED CONSTRUCTION SHALL BE
 INSTALLED IN THE SAME MANNER USED IN THE ASSEMBLY
 TESTED AND SHALL COMPLY WITH THE PROVISIONS OF CHAPTER
 7.
 912.5.3 EXISTING BUILDING CODE.
  
 3B) SHEET 1.0A DOOR# 4 DOES NOT INDICATE WHAT TYPE OF
 ROOM IS LOCATED BEHIND THIS DOOR. THIS MAY BE AN ISSUE
 DEPENDING ON (1) WHERE THE TENANT SEPARATION WALL IS
 LOCATED, AND THE USAGE OF THE ROOM. EXAMPLE IF THIS IS
 A ELEVATOR EQUIPMENT ROOM, 3006.1 ACCESS. AN APPROVED
 MEANS OF ACCESS SHALL BE PROVIDED TO ELEVATOR MACHINE
 ROOMS AND OVERHEAD MACHINERY SPACES. ELEVATOR MACHINE
 ROOMS CAN NOT BE LOCATED WITHIN A TENANT SPACE.
  
 3C) 912.2 FL EXISTING BUILDING CODE. 912.2 FIRE
 PROTECTION SYSTEMS. FIRE PROTECTION SYSTEMS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTIONS 912.2.1 AND
 912.2.2.
  
 912.2.1 FIRE SPRINKLER SYSTEM. WHERE A CHANGE IN
 OCCUPANCY CLASSIFICATION OCCURS THAT REQUIRES AN
 AUTOMATIC FIRE SPRINKLER SYSTEM TO BE PROVIDED BASED ON
 THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF THE
 FLORIDA BUILDING CODE, BUILDING , SUCH SYSTEM SHALL BE
 PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS.
  
 2007 FBC- BUILDING, 903.2.1.2 GROUP A-2. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE PROVIDED FOR GROUP A-2
 OCCUPANCIES WHERE ONE OF THE FOLLOWING CONDITIONS
 EXISTS:
 (2). THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE.
  
 4) 2007 EXIST BLDG CODE.912.3 INTERIOR FINISH. IN AREAS
 OF THE BUILDING UNDERGOING THE CHANGE OF OCCUPANCY
 CLASSIFICATION, THE INTERIOR FINISH OF WALLS AND
 CEILINGS SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING , FOR THE NEW OCCUPANCY
 CLASSIFICATION.
 COVER SHEET THE MINIMUM INTERIOR FINISH SCHEDULE TABLE
 803.5 PLEASE REVIEW ROOMS AND ENCLOSED SPACES FOR
 UNSPRINKLED BUILDING, A2 OCCUPANCY SCHEDULE WILL NEED
 TO BE REVISED FOR SPRINKLED BUILDINGS.
  
 5) SHEET 1.0A DOOR# 11 APPEARS TO BE AN EXIT DOOR
 LEADING TO THE EXTERIOR, THE DOOR IS LABELED AS A
 SERVICE DOOR. THE LIFE SAFETY PLANS INDICATE NO EXIT
 SIGN AT THIS DOOR BUT TAKES YOU DOWN A CORRIDOR AND
 THROUGH 2 OTHER DOORS BEFORE ENTERING THE EXIT TO THE
 EXTERIOR. WITHIN THE CORRIDOR THERE IS A ROOM AND DOOR
 THAT ARE NOT IDENTIFIED PLEASE PROVIDE ADDITIONAL
 INFORMATION. DOORS MARKED AS # 3 IN THIS CORRIDOR DO
 NOT HAVE A FIRE RATING IN THE DOOR SCHEDULE. TABLE
 715.4. DOOR # 11 SWINGS THE WRONG DIRECTION FBC-
 BUILDING 1008.1.2.
  
 6) SHEET 1.0A DOOR# 5 ALSO IS NOT IDENTIFIED AS A FIRE
 RATED DOOR IN THE DOOR SCHEDULE, TENANT SEPARATION WALL
 AND OCCUPANCY SEPARATION WALL. TABLE 715.4.
  
 7) SHEET 1.0A NOTE# 5 INDICATES THE USE OF BI-FOLD
 GLASS DOORS, NONE OF THE FLOOR PLANS INDICATE IF THE
 DOORS ARE TO SWING IN OR OUT, IF THEY SWING OUT PLEASE
 PROVIDE WHERE THE PROPERTY LINE IS LOCATED IN REGARDS
 TO THE BI-FOLD DOOR LOCATION.
 2007 FBC- BUILDING 3202.2 ENCROACHMENTS ABOVE GRADE AND
 BELOW 8 FEET IN HEIGHT. ENCROACHMENTS INTO THE PUBLIC
 RIGHT-OF-WAY ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN
 HEIGHT SHALL BE PROHIBITED EXCEPT AS PROVIDED FOR IN
 SECTIONS 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS
 SHALL NOT OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 8) SHEET 1.0A ALSO INDICATES THE USE OF BAHAMA
 SHUTTERS, THE SAME CONCERNS ABOUT ENCROACHMENT INTO THE
 RIGHT AWAY WITH REGARDS TO THE HEIGHT OF THE SHUTTERS.
 3202.2 FBC-BUILDING.
  
 9) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 9A) EXTERIOR GLAZED DOOR
 9B) EXTERIOR BI-FOLD DOORS SOLAR INNOVATIONS
 9C) FRENCH DOORS NOTE# 6
 9D) FIXED IMPACT WINDOWS
 9E) PRE-MANUFACTURED A/C STANDS
 9F) WALL LOUVER
 9G) BAHAMA SHUTTERS
  
 10) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 12) PLANS DO NOT INDICATE IF THERE IS TO BE USE OF WOOD
 BUCKS OR NOT. NORMALLY THE PRODUCT APPROVALS DO NOT
 INCLUDE THE ATTACHMENT OF WOOD BUCKS. COMPONENTS AND
 CLADDING
  
 13) PLEASE PROVIDE MANUFACTURERS SPECS FOR WALK IN
 COOLER AND ACCORDANCE WITH 2603.4.1.3.
  
 14) PLEASE PROVIDE COMPLIANCE WITH 11-5.1- 11-4.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-01-13 Cont ID  
Sent By dpalmer Date 2010-01-13 Time 17:14 Rev Time 0.00
Received By dpalmer Date 2010-01-13 Time 15:27 Sent To  
Notes
2010-01-13 17:14:42 
 ** PROVISO *
 ** FAILURE TO ADDRESS COMMENTS BEFORE INSPECTIONS AS
 NOTED MAY RESULT IN ADDITIONAL FEES.
  
 NOTE #1 BEFORE ROUGH
 NOTE #2 BEFORE FINAL
 NOTE #3 BEFORE ROUGH
 NOTE #4 BEFORE FINAL
 NOTE #5 *REDLINED*
  
  
 1) NOTE: PLEASE MAKE THE CONTROL OF CORRIDOR LIGHTING
 CLEAR ON PLANS. PLANS INDICATE THE LIGHTS BEING
 CIRCUITED TO BREAKER HOWEVER NO CONTROLS. IF THESE ARE
 NIGHT LIGHTS ON 24/7 PLEASE INDICATE.
 13-415.AB.1.1, .1.2.
 PER DESIGNER AND PLANS ALL LIGHTING FOR THE MOST PART
 WILL BE CONTROLLED BY OCCUPANCY SENSORS. HOWEVER THE
 PLANS STILL INDICATE A KEYPAD AT KITCHEN DOOR AREA. THE
 RISER ALSO STILL INDICATES A LIGHTING CONTROL PANEL
 WHICH THERE IS NO DETAILS FOR.
 PLEASE PROVIDE DETAIL ON PLANS FOR OCCUPANCY SENSORS
 AND MASTER OFF CONTROLS ARE FRONT DOOR. PLEASE ALSO
 PROVIDE FOR TYPICAL CONTROLS/WIRING METHOD. A DETAIL
 BOX ON THESE WOULD BE SUFFICIENT. TYPICAL DETAILS CAN
 BE FOUND ON MOST LIGHTING CONTROL MANUFACTURE WEBSITES.
 NO LIGHTING OR CONTROLS SHOWN ON PLANS FOR WALK-IN
 COOLER AND OTHER ARE OFF WALK IN COOLER AREA. PLANS ARE
 TO BE REVISED TO SHOW. THE COOLER IT SELF WILL BE UNDER
 SEPARATE PERMIT.
  
 2) NOTE: PLEASE PROVIDE FIXTURE LEGEND OF SPECIFIC
 FIXTURES ONCE KNOWN FOR FINAL RECORD PLANS.
 REVISE PERFORMANCE CALCULATIONS IF WATTAGE
 INCREASES.13-415.AB.5.
  
 3) NOTE: ALL DEVICES FOR HORN, STROBES DEVICES FOR ADA
 COMPLIANCE SHALL BE SHOWN ON FA PERMIT. PLANS NOW
 INDICATE CANDELA LEVEL HOWEVER NO OTHER DETAILS FOR
 HEIGHTS, DB LEVELS ETC.
 FBC 11-4.28.1,.2 AND .3.
  
 4) NOTE: PANEL SCHEDULES TO BE REVISED FOR SPECIFIC
 CIRCUITS TO ALL ROOMS AND AREAS IN WHICH THEY FEED.
 EXAMPLE: LIGHTING FRONT, LIGHTING OFFICES/KITCHEN AREA
 ETC.
 408.4
  
 5) NOTE: PLANS INDICATE A 2008 EDITION OF NFPA-101
 HOWEVER THIS SHOULD BE 2006. THIS WAS REDLINED ON
 PLANS. ( FOR INFORMATION, 101 CODES ARE 2003, 2006 AND
 2009. THERE IS NO 2008 101. ( MISPRINT ON PLANS)
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-04 Cont ID  
Sent By dpalmer Date 2009-12-04 Time 09:27 Rev Time 0.00
Received By dpalmer Date 2009-12-04 Time 07:45 Sent To  
Notes
2009-12-04 09:28:08 
 ** DENIED**
  
 1) NOTE: THE FOLLOWING CODES INDICATED ON THE SHEET ARE
 NOT ADOPTED BY THE STATE OF FLORIDA.
 PLANS LIST THE 2005 EDITION OF NFPA-70 ( NEC) HOWEVER
 THIS SHOULD BE 2008. THIS COULD HAVE BEEN REDLINED
 HOWEVER PLANS ARE COMING BACK FOR OTHER COMMENTS.
  
 ** SIDE NOTE** CODE SECTIONS REFLECTED ON PLANS ARE
 FROM THE 2004 FBC ON ELECTRICAL SHEETS.( ELECTRICAL
 NOTES)
  
 2) NOTE: THE APPLIED VALUE FOR COMPLETE SCOPE OF WORK
 IS REQUIRED TO INCLUDE VALUE FOR THE FOLLOWING; DESIGN
 COST, ALL LABOR, ALL EQUIPMENT, ALL MATERIALS/BUILDING
 MATERIALS FOR ALL TRADES WHETHER OR NOT ANY OF THESE
 ITEMS ARE OWNER SUPPLIED. VALUE APPLIED IS LOW.
 ** FBC 108.3
 ** ONCE APPROPRIATE VALUE IS ASSESSED THEN ADDITIONAL
 FEES WILL BE REQUIRED BEFORE PERMIT ISSUANCE.
  
 3) NOTE: RISER ONLY INDICATES ONE SET OF 3/0 AWG
 CONDUCTORS FOR FEEDERS AND SUB PANELS FOR 400AMPS.
 PLEASE SEE NEC 310.16 AS THESE ARE ONLY RATED FOR
 200AMPS. HOWEVER THE SERVICE SIZE BEING PROVIDED IS
 400AMPS.
 240.4, 310.16
  
 4) NOTE: THIS IS A CHANGE IN OCCUPANCY UNDER THE
 EXISTING BUILDING CODE CHAPTER 9. PLEASE SEE 13-101.3
 FOR CHANGES IN OCCUPANCY FOR ENERGY CODE COMPLIANCE.
 PLEASE SEE THE FOLLOWING ITEMS WHICH WERE NOT SHOWN ON
 PLANS FOR CODE COMPLIANCE OR OTHER ITEMS NOT SUBMITTED.
 MINIMUM COMPLIANCE WITH FLORIDA BUILDING CODE CHAPTER
 13 HAS NOT BEEN MET.
 PLEASE SEE THE 2007 FBC W/2009 SUPPLEMENTS INCLUDING
 SECOND SET OF 2009 SUPPLEMENTS ADOPTED BY THE STATE ON
 OCTOBER 1ST, 2009.
 ALONG WITH THE SHOWN METHOD B ON PLANS, A FIXTURE
 LEGEND WITH SPECIFIC FIXTURES NEEDS TO BE SHOWN TO
 REVIEW FOR MINIMUM CODE COMPLIANCE. SHOWING A 2X4
 FIXTURE WITH 2-32W BULBS DOES NOT GIVE THE ACTUAL
 ACCURATE WATTAGE/VA CONSUMPTION OF FIXTURE. PLEASE SEE
 13-415.AB.5 FOR INTERIOR ALLOWANCES AND APPENDIX FOR
 FIGURING.
  
 5) NOTE: PLEASE SUBMIT LIGHTING CONTROL INFORMATION,
 LEGEND, DETAILS TO MEET MINIMUM CODE COMPLIANCE FOR FBC
 13-415.AB.1.1,.1.2 AND .1.3.
 THERE IS NO CONTROLS SHOWN ON PLANS FOR LIGHTING.
 PLANS HAVE SOME SORT OF INDICATION FOR A LIGHTING
 CONTROL PANEL AND THE RISER SHOWS A LIGHTING CONTROL
 PANEL. HOWEVER NO INFORMATION OR DETAILS ARE SHOWN???
 PLANS DO NOT SHOW CONTROLS AS REQUIRED FOR THE OCCUPANT
 TO OVER RIDE ANY TIME OF DAY SCHEDULING.
 PLANS DO NOT SHOW CONTROLS IN LOCATIONS FOR THE
 OCCUPANT TO SEE *ALL* LIGHTING WHICH IS BEING
 OVERRIDDEN.
 PLANS NEED TO INDICATE ALL SEPARATE SPACE CONTROLS.(
 SHOWN IN OFFICE HOWEVER NOT OTHER AREAS)
  
 6) NOTE: IF THERE IS GOING TO BE ANY OUTSIDE LIGHTING
 PLEASE SEE 13-415.AB.1.4
  
 7) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND
 COORDINATE WITH PANEL SCHEDULES.408.4, 310.16, 240.4,
 220, GIVEN AS GENERAL SECTIONS BASED ON THE FACT LOAD
 CALCULATIONS, CIRCUITING AND SIXE OF OVER CURRENT
 PROTECTION DEVICES CAN NOT BE VERIFIED FOR CODE
 COMPLIANCE IF THE PLANS AND PANEL SCHEDULE DO NOT
 COORDINATE.
  
 EXAMPLE: PLEASE SEE SIGN J-BOX OUT FRONT FOR EXAMPLE
 WHICH INDICATES CIRCUIT A41- YET THE PANEL SCHEDULE IS
 BLANK. SEE 600.5 FOR MINIMUM VA REQUIRED TO BE
 ADDITIONAL SIGN CIRCUIT.
  
 EXAMPLE: PLEASE SEE ANOTHER EXAMPLE IS TO CIRCUIT
 EMERGENCY AND EXIT LIGHTS PER 700.12F. ( ONLY SOME
 SHOWN, HOWEVER SEE COMMENT BELOW)
  
 EXAMPLE: PLEASE SEE B37 IN CLOSET AREA, WHICH BY PANEL
 SCHEDULE THIS IS LABELED. *BAG IN BOX*?
  
 EXAMPLE: PLEASE SEE B16 WHICH IS NOT ON PLANS. THIS
 LIGHTING IS ALSO NOT SHOWN FOR LIGHTING CONTROLS PER
 NOTE #5 ABOVE.
  
 EXAMPLE: PLEASE SEE LIGHTING PLAN WHICH INDICATES B19
 ON PLAN AND PANEL SCHEDULE STATES BAR COOLER. HOW IS
 THIS ALSO A LIGHTING CIRCUIT?
  
 EXAMPLE: PLANS INDICATE CIRCUIT A-27 AT TWO COOLER DOOR
 LOCATIONS HOWEVER A-27/29 FEED THE EXHAUST HOOD.
  
 8) NOTE: PLEASE COORDINATE PLANS. THE REFLECTED CEILING
 PLANS AND THE LIFE SAFETY PLAN DOES NOT MATCH WITH THE
 ELECTRICAL LIGHTING PLANS. MOST OF THE EMERGENCY AND
 EXIT LIGHTS ARE IN DIFFERENT LOCATIONS.
 SEE REAR EXIT AND OTHER AREA FIXTURES. SOME ARE SHOWN
 AS EXIT/EMERGENCY LIGHTS AND THEN THE ELECTRICAL PLANS
 ONLY INDICATE THE SAME FIXTURES AS EXIT.
 PLEASE SEE 700.12F.
  
 9) NOTE: PLANS NEED TO COMPLETE BASE DESIGN FOR FIRE
 ALARM SYSTEM/DEVICES. ALL DEVICE LOCATIONS, HEIGHTS,
 LEVELS CANDELA AND DB RATINGS MUST BE SHOWN ON BASE
 PLANS FOR DESIGN INTENT. THE FIRE ALARM WILL BE
 REQUIRED UNDER SEPARATE PERMIT HOWEVER MINIMUM CODE
 COMPLIANCE DESIGN NEEDS TO BE SHOWN PER NFPA-72, FBC
 AND FS 633. SEE NEC 760 FOR CIRCUITING REQUIRED AS WELL
 AS NFPA 72 CHAPTER 4.
 ** THIS WILL NOT BE A PROVISO ITEM>
  
 10) NOTE: ELECTRICAL PLANS ONLY INDICATE THE LOCATION
 OF TWO OF THE PANELS WHEREAS THE LIFE SAFETY SHEET AND
 OTHER SHEETS INDICATE ALL THREE PANELS.
 110.26, 240.24
  
 11) NOTE: ALL LOW VOLTAGE SYSTEMS SUCH AS SOUND, CATV,
 PHONE ETC WILL BE UNDER SEPARATE PLANS AND PERMIT
 APPLICATION. THESE PLANS MAY NOT BE REFERENCED FOR ANY
 OF THESE ITEMS AS PLANS DO NOT SHOW COMPLETED SYSTEMS
 AT THIS TIME.
 ** NO SYMBOL LEGEND ON PLANS FOR ANY DEVICE WHICH MAY
 BE INCLUDED.
  
 12) NOTE: DETAIL FOR ELECTRICAL SYSTEMS UNDER HOOD AND
 PERTAINING TO HOOD FOR SHUT DOWN WILL ALSO BE REQUIRED
 UNDER SEPARATE PERMIT AND PLANS. ( NONE SHOWN AND HOOD
 IS UNDER SEPARATE PERMIT).
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2010-02-04 Cont ID  
Sent By mawillia Date 2010-02-04 Time 14:47 Rev Time 0.00
Received By mawillia Date 2010-02-04 Time 14:05 Sent To  
Notes
2010-02-04 14:47:12*****APPROVED*****
  
 PLAN SHEETS 1.0A, 1.2A, 1.6A, 2.0E, FP-1, AND FA-1 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2010-01-27 Cont ID  
Sent By mcarsill Date 2010-01-27 Time 08:27 Rev Time 0.00
Received By mcarsill Date 2010-01-27 Time 07:28 Sent To  
Notes
2010-01-27 08:27:211. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY HOOD,
 DUCT, AND FIRE SUPPRESSION SYSTEMS.
  
 2. THE EXISTING RATED SHAFT AND ORIGINAL GREASE DUCT
 DISPLAYED ON SHEET 3.3.M IS TO BE FIELD VERIFIED AND
 INSPECTED BY MECHANICAL INSPECTORS. ANY VIOLATIONS OF
 CODE DISCOVERED WILL NEED TO BE CORRECTED BY SUBMITTING
 PLANS AND PERMITS.
  
 3. NO FIRE SPRINKLER PLANS PROVIDED. PLEASE SUPPLY
 COMPLETE FIRE SPRINKLER PLANS ILLUSTRATING DESIGN, HEAD
 LOCATION, WATER SUPPLY, FIRE DEPARTMENT CONNECTION,
 VALVES AND ALL OTHER APPURTENANCES. SEPARATE SHOP
 DRAWINGS WILL BE REQUIRED PRIOR TO ANY INSTALLATION.
  
 4. ON PAGE 2.1E ONLY ONE HORN STROBE IS SHOWN IN THE
 LOUNGE PROPER. ANOTHER ONE IS DISPLAYED IN THE MAIN
 LOBBY OF THE BUILDING. ADDITIONAL HORN STROBES APPEAR
 TO BE NEEDED. CONFLICTS EXIST BETWEEN THE FIRE ALARM
 PLAN AND THE ELECTRICAL SHEETS. SEPARATE PLANS AND
 PERMITS REQUIRED FOR THE FIRE ALARM SYSTEM SHALL BE UL
 FOR CENTRAL STATION SERVICE.
  
 5. ON THE FIRE ALARM PLANS IT INDICATES THAT THAT AN
 ALARM, SUPERVISORY AND TROUBLE SIGNALS. A WATERFLOW
 SIGNAL IS ALSO REQUIRED TO BE SENT.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2010-01-26 Time   Rev Time 0.00
Received By mawillia Date 2010-01-26 Time   Sent To  
Notes
2010-01-27 17:33:11PANS TRANSFERRED FROM CONSTRUCTION SERVICES DEPARTMENT
 TO FIRE PREVENTION BUREAU TO BE REVIEWED BY FIRE
 MARSHAL MIKE CARSILLO.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-12-08 Cont ID  
Sent By mcarsill Date 2009-12-08 Time 08:18 Rev Time 0.00
Received By mcarsill Date 2009-12-08 Time 08:01 Sent To  
Notes
2009-12-08 08:18:51 
 1. DEADBOLT LOCKS NOTED ON DOOR SCHEDULE. DOORS THAT
 ARE USED FOR EXITING CANNOT BE EQUIPPED WITH
 DEAD-BOLTS. PLEASE PROVIDE MORE DETAILS.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR HOOD, DUCT,
 AND FIRE SUPPRESSION SYSTEMS.
  
 3. NO EMERGENCY LIGHTING OR EXIT SIGNS DISPLAYED WITHIN
 THE EXISTING EXIT CORRIDOR ON THE LIFE SAFETY PLAN.
  
 4. IT APPEARS THAT ONE OF THE EXITS TERMINATES INTO THE
 BUILDING'S COMMON AREA. NO INFORMATION PROVIDED RELATED
 TO THE DOORS AND HARDWARE FROM THIS LOCATION.
  
 5. THE OCCUPANT LOAD WILL BE ESTABLISHED BY THE BUREAU
 OF FIRE PREVENTION.
  
 6. DOES THE EXISTING BUILDING CONTAIN ANY FIRE ALARM
 EQUIPMENT. NO FIRE ALARM EQUIPMENT IS SHOWN.
  
 7. ON SHEET 2.0E, AN EMERGENCY LIGHT AND EXIT IS SHOWN
 ABOVE A DOOR THAT SWINGS IN THE WRONG DIRECTION.
  
 8. GAS INSTALLATIONS TO COMPLY WITH THE APPROPRIATE
 NFPA STANDARDS.
  
 9. PREVIOUSLY THIS SPACE WAS USED AS A BUSINESS
 OCCUPANCY. THE SPACE THEN BECAME VACANT AND THE PLANS
 ILLUSTRATE A CHANGE OF USE TO AN ASSEMBLY OCCUPANCY.
 THE NEW PROPOSED USE IS REQUIRED TO COMPLY TO THE
 REQUIREMENTS FOR NEW ASSEMBLY OCCUPANCIES.
  
 10. MORE DETAILS REQUIRED ON THE EXISTING RATED HOOD
 SHAFT ILLUSTRATED ON THE PLANS.
  
 11. FLOOR PLAN DOES NOT ILLUSTRATE SEATING FOR
 PHYSICALLY CHALLENGED INDIVIDUALS.
  
 12. MORE DETAILS REQUIRED FOR THE COMMON AREA OF THE
 BUILDING. PLEASE DESCRIBE INTERIOR FINISH, EXIT SIGNS,
 EMERGENCY LIGHTS, AND ANY OTHER SAFETY RELATED
 EQUIPMENT.
  
 13. THE PLANS INDICATE THAT THE SPACE IS NOT FIRE
 SPRINKLER PROTECTED. PLEASE BE ADVISED THAT "WHERE THE
 OCCUPANT LOAD EXCEEDS 100, THE FOLLOWING ASSEMBLY
 OCCUPANCIES SHALL BE PROTECTED THROUGHOUT BY AN
 APPROVED SUPERVISED AUTOMATIC FIRE SPRINKLER SYSTEM IN
 ACCORDANCE WITH 9.7.1.1(1)
 DANCE HALLS
 DISCOTHEQUES
 NIGHTCLUBS OR SIMILAR USAGE
 ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING.
  
 DENIED
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2010-01-11 Cont ID  
Sent By kstevens Date 2010-01-11 Time 10:17 Rev Time 0.00
Received By kstevens Date 2010-01-11 Time 10:17 Sent To  
Notes
2010-01-11 10:19:30PASSED/PROVISO:
 MANUF. SPECIFICATION SHEETS FOR ALL GAS APPLIANCES
 REQUIRED AT TIME OF PERMIT APPLICATION. -- PER PETE
 RUSSO, MAXITROL REGULATORS TO BE USED. - MODEL 325-3L
 REQUIRED FOR ALL EXCEPT THE RANGE WHICH REQUIRES A
 MODEL 325-5AL.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-12-10 Cont ID  
Sent By kstevens Date 2009-12-10 Time 08:08 Rev Time 0.00
Received By kstevens Date 2009-12-10 Time 08:08 Sent To  
Notes
2009-12-10 08:20:02DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 A. SEPARATE GAS PERMIT REQUIRED. THE FOLLOING
 INFORMATION IS REQUIRED:
  
 1. TYPE OF GAS, (LP OR NATURAL).
  
 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2.
  
 3. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 4. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 5. SUBMIT MANUF SPECIFICATIONS FOR THE 2PSI TO .5 PSI
 REGULATORS. INDICATE MODEL NUMBER FOR EACH REGULATOR.
 REGULATORS SHALL BE LISTED AND THE OUTPUT OF EACH
 REGULATOR SHALL BE SUFFICIENT FOR EACH APPLIANCE BTU
 LOAD. SECTION 410.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-02-01 Cont ID  
Sent By lmartine Date 2010-01-28 Time 17:04 Rev Time 0.00
Received By lmartine Date 2010-01-28 Time 17:04 Sent To  
Notes
2010-02-01 17:07:05****************************EXPEDITED******************
 ******
 3RD RUN
 C--18
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-01-05 Cont ID  
Sent By shill Date 2010-01-05 Time 14:59 Rev Time 0.00
Received By shill Date 2010-01-05 Time 14:59 Sent To  
Notes
2010-01-05 14:59:53********** $$ EXPEDITED $$ **********
 C 28
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-12-19 Time   Rev Time 0.00
Received By lmartine Date 2009-12-02 Time 17:01 Sent To  
Notes
2009-12-03 16:44:56*****************EXPEDITED******************
 ON 12/3/09
2009-12-02 17:01:48C--7

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-02-03 Cont ID  
Sent By jwitmer Date 2010-02-03 Time 08:32 Rev Time 0.00
Received By jwitmer Date 2010-02-03 Time 08:32 Sent To  
Notes
2010-02-03 08:32:08PLANS STAMPED NO FEE DUE!

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-01-23 Cont ID  
Sent By rregueir Date 2010-01-23 Time 15:22 Rev Time 0.00
Received By rregueir Date 2010-01-23 Time 15:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-12-19 Cont ID  
Sent By rregueir Date 2009-12-19 Time 15:20 Rev Time 0.00
Received By rregueir Date 2009-12-19 Time 14:49 Sent To  
Notes
2009-12-19 15:19:08REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. OUTSIDE AIR INTAKE FOR AHU 1, 2 IS FACING A STREET.
 MECHANICAL AND GRAVITY OUTSIDE AIR INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET FROM ANY
 HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS STREETS,
 ALLEYS, PARKING LOTS AND LOADING DOCKS IN ACCORDANCE
 WITH FBC-M 401.4.1.
  
 2. NO OUTSIDE AIR CALCULATIONS WERE PROVIDED. PROVIDE
 VANTILATION CALCULATIONS FOR THE PROPOSED NEW OCCUPANCY
 IN ACCORDANCE WITH FBC-EB 909.1 AND FBC-M SECTION 403.
  
 3. AHU 1 AND AHU 2 ARE BOTH MARKED ON FLOOR PLANS AS
 AHU 1. PLEASE CORRECT IN ACCORDANCE WITH FBC-M 304.11.
  
 4. NO INFORMATION IS PROVIDED REGARDING THE LOCATION OF
 NEW REMOTE CONDENSING UNITS. PROVIDE ROOF MECHANICAL
 PLAN AND ENSURE THE REQUIREMENTS OF FBC-M 304.10 FOR
 GUARDS AND FBC-M 306.5 FOR ACCESS HAVE BEEN MET.
  
 5. PROVIDE COOLING LOAD CALCULATIONS FOR THE PROPOSED
 NEW AC EQUIPMENT IN ACCORDANCE WITH FBC-B 13-407.AB.1.
  
 6. PROVIDE PRODUCT APPROVAL FOR ANY PRE-ENGINEERED A/C
 STANDS TO BE USED IN ACCORDANCE WITH FAC 9B-72.
  
 7. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN
 ACCORDANCE WITH FBC-M 307.2.1.
  
 8. SHOW AUXILIARY DRAIN PROTECTION IN ACCORDANCE WITH
 FBC-M 307.2.3.
  
 NOTE: SEPARATE PLANS AND PERMIT APPLICATIONS REQUIRED
 FOR EACH OF THE FOLLOWINGMECHANICAL SYSTEMS: COMMERCIAL
 KITCHEN HOOD EXHAUST SYSTEM, HOOD SUPPRESSION SYSTEM
 AND WALK-IN COOLER/FREEZER SYSTEM.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2010-02-03 Cont ID  
Sent By kstevens Date 2010-02-03 Time 14:15 Rev Time 0.00
Received By kstevens Date 2010-02-03 Time 14:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-01-11 Cont ID  
Sent By kstevens Date 2010-01-11 Time 08:50 Rev Time 0.00
Received By kstevens Date 2010-01-11 Time 08:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-12-10 Cont ID  
Sent By kstevens Date 2009-12-10 Time 17:42 Rev Time 0.00
Received By kstevens Date 2009-12-10 Time 17:42 Sent To  
Notes
2009-12-10 18:08:35DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
  
 1. SHT 1.1A FLOOR PLAN DOES NOT REFLECT THE EQUIPMENT
 SCHEDULE FOR ITEM #4. PLEASE CORRELATE. FLOOR PLAN
 SHOWS A 3 COMPARTMENT SINK BUT THE EQUIP. SCHED
 INDICATES A DISHTABLE STRAIGHT WITH NO WATER SUPPLY NOR
 DOES IT INDICATE A DRAIN. PLEASE CLARIFY. SECTIONS
 106.1.1, 601.1, 701.1 & 801.1.
  
 2. SHT 1.1A FLOOR PLAN SHOWS ITEM 2 AS A SINK, PRE-
 WASH OR GARBAGE DISPOSAL BUT THE EQUIPMENT SCHEDULE
 INDICATES IT AS A DISHTABLE STRAIGHT. PLEASE CLARIFY
 SECTION 106.1.1.
  
 3. SHT 1.1A ITEMS 6 & 23 DO NOT INDICATE WATER SUPPLIES
 OR DRAINAGE CONNECTION. PLEASE CLARIFY. SECTIONS
 106.1.1, 601.1 & 701.1.
  
 4. SHT 3.1M THE HAND SINKS IN THE FOOD PREP AREA SHALL
 CONNECT TO THE GREASE INTERCEPTOR. SECTION 1003.3.1.
 ITEM #2 MAY BE REQUIRED TO CONNECT TO THE GREASE SYSTEM
 AS WELL WHEN THE FIXTURE IS IDENTIFIED.
  
 5. SHT 3.1M IDENTIFY WHAT FIXTURE IS DRAINED INTO THE
 FLOOR SINK ACROSS FROM THE 6 BURNER GRILL. SECTIONS
 106.1.1 & 801.1.
  
 6. PER TABLE 1003.3.4.1 THE FLOW-THROUGH RATING FOR ALL
 FIXTURES SHALL BE INDICATED ON THE PLANS. SEE SECTIONS
 1003.3.4.1 & 1003.3.4.2.
  
 7. SHT 3.1M TRAPZILLA DETAIL. 2-WAY CLEANOUTS ARE
 REQUIRED ON THE INLET AND OUTLET PIPING. UTILITY
 STANDARD AND TRAPZILLA INSTALLATION INSTRUCTIONS.
  
 8. SHT 3.2M WATER RISER DIAGRAM. PER SECTION 604.9
 WATER HAMMER ARRESTORS ARE REQUIRED AT THE ICE MAKER &
 THE DISHWASHER. PER PDI-WH 201 AIR CHAMBERS ARE NOT
 APPROVED. PLEASE DELETE FROM RISER DIAGRAM.
  
 9. SHTS 3.1M & 3.2M SHOW DIFFERENT TRAPZILLA MODELS.
 THE TRAPZILLA MODEL TZ-600 SHOULD BE INSTALLED. SECTION
 1003.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2010-01-19 Cont ID  
Sent By aaponte Date 2010-01-19 Time 14:30 Rev Time 0.00
Received By aaponte Date 2010-01-19 Time 14:29 Sent To  
Notes
2010-01-19 14:40:57A SIDEWALK CAFE PERMIT IS REQUIRED FOR TABLES LOCATED
 ON THE SIDEWALK. PLEASE CONTACT ANA MARIA APONTE AT
 822-1439 ONCE THE RESTAURANT IS READY TO START
 OPERATIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-12-15 Cont ID  
Sent By aaponte Date 2009-12-15 Time 15:18 Rev Time 0.00
Received By aaponte Date 2009-12-15 Time 15:18 Sent To  
Notes
2009-12-15 15:26:30PLEASE INDICATE THE PROPERTY LINE ON ALL THE FLOOR
 PLANS.
 NEW BI-FOLD GLASS DOORS AND FRENCH DOORS ALONG CLEMATIS
 STREET CANNOT ENCROACH INTO THE ROW. IN GENERAL, DOORS
 CANNOT ENCROACH INTO THE ROW.