Plan Review Stops For Permit 09120037 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2009-12-14 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2009-12-14 |
Time |
10:30 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2009-12-14 |
Time |
09:59 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2009-12-02 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2009-12-02 |
Time |
13:03 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2009-12-02 |
Time |
13:03 |
Sent To |
PC |
|
Notes |
2009-12-02 13:13:08 | REROOF BUILDING REVIEW CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- THIS BUILDING IS LOCATED ON EXPOSURE "C" NOT "B". | | SEC. 1609.4 FBC WITH 2009 REVISIONS. ENGINEER TO REVISE | | RAS 117 CALCULATIONS AND TAS 105 CALCULATIONS AS | | REQUIRED. | | ***NOTE: ENGINEER TO PROVIDE HIS NAME AND LICENSE # ON | | THE SIGNED SHEETS AS REQUIRED BY CHAPTER 471 FLORIDA | | STATUTES. | | | | 2- ENGINEER TAS 105 REPORT IS MISSING THE INFORMATION | | REGARDING THE SPECIFIC COMPONENT TO BE SECURED. NO | | COMPONENT WAS MARKED. | | | | 3- ENGINEER TAS REPORT IS REFERENCING THE 2001 FBC. SEE | | TAS-105 STATISTICAL ANALYSIS PAGE AND UPDATE AS | | REQUIRED. | | | | 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | FLORIDA STATUTE. | | | | 5- ANY ROOF EQUIPMENT REQUIRES SEPARATE PERMIT FOR | | RE-INSTALLATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
|