Plan Review Details - Permit 09120028
Plan Review Stops For Permit 09120028
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-05-18 Cont ID  
Sent By mawillia Date 2010-05-18 Time 16:29 Rev Time 0.00
Received By mawillia Date 2010-05-17 Time 15:27 Sent To  
Notes
2010-05-18 15:37:56*****PROVISO*****
  
 READY FOR PERMIT ISSUANCE; PLAN SHEET FA-1 STAMPED,
 INITIALED, AND DATED WITH THE FOLLOWING ATTACHED
 PROVISO.
  
 PRIOR TO THE FIRE ALARM FINAL (302), REVISED PLAN SHALL
 BE REQUIRED WITH THE FOLLOWING INFORMATION:
  
 1. FIRE ALARM PLAN DEPICTING THE LAYOUT OF ROOMS FOR
 THIS NEW DAY CARE OCCUPANCY.
 2. PROVIDE INFORMATION ON THE HEAT DETECTOR DEVICE AND
 HOW IT RELATES TO THE FIRE ALARM SYSTEM, AND SHOWN IN
 THE FIRE ALARM RISER.
 3. THE CORRECT ADDRESS SHALL BE IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET. IT SHOULD BE 724 BUNKER
 ROAD, NOT 724 N. BUNKER ROAD.
 4. RELOCATE THE FIRE ALARM CONTROL PANEL (FACP) FROM
 THE KITCHEN. REASONING: A SMOKE DETECTOR IS REQUIRED
 ABOVE THE FACP, BUT WITH THE SMOKE DETECTOR BEING IN
 THE KITCHEN, IT IS SUSCEPTIBLE TO FIRE ALARM ACTIVATION
 FROM SMOKE CAUSED BY NORMAL COOKING OPERATIONS (WHICH
 CAN BECOME A NUISANCE TO THE OCCUPANTS, NEIGHBORS, AND
 FIRE EMERGENCY RESPONSE UNITS) .
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-05-17 Time 16:00 Rev Time 0.00
Received By lmartine Date 2009-12-02 Time 09:06 Sent To FIRE
Notes
2009-12-02 09:07:13IN FIRE BOX