Plan Review Details - Permit 09110551
Plan Review Stops For Permit 09110551 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2009-12-01 |
|
|
Cont ID |
|
Sent By |
jnguyen |
Date |
2009-12-01 |
Time |
13:17 |
Rev Time |
0.00 |
Received By |
jnguyen |
Date |
2009-11-30 |
Time |
15:54 |
Sent To |
|
|
Notes |
2009-12-01 13:12:08 | THIS PARCEL WAS PREVIOUSLY UNADDRESSED. THIS | | PERMIT#09110551 WAS FOR A WIRE FLOOD CONTROL GATE FOR | | THE NEW CONSTRUCTION OF A CONTROL STRUCTURE NO. 4 | | REPLACEMENT (PERMIT# 09110131) IN THE WATER SUPPLY | | CANAL WITHIN ITS BOUNDARIES. I HAVE EXAMINED THE SITE | | PLANS & ISSUED THE PRIMARY ADDRESS OF 5101 N HAVERHILL | | RD FOR PCN# 74424302000005010. I CREATED THE GIS | | ADDRESS POINT & UPDATED THE RECORD IN COMMUNITYPLUS. I | | SENT OUT A NOTIFICATION E-MAIL TO ALL OF THE RELEVANT | | PARTIES (INCLUDING PAPA). I CALLED THE CONTRACTOR, | | CHARLES FITCH OF C.R. DUNN & LEFT HIM A MESSAGE TO | | INFORM HIM OF THE NEW ADDRESS & FOR HIM TO CORRECT THE | | OWNER RECORD FROM NPBCID TO THE CITY OF WEST PALM BEACH | | FOR THIS PARCEL. I ADJUSTED THE ADDRESS ON THE ORIGINAL | | PERMIT APPLICATION. I HAVE RETURNED THE SITE PLANS BACK | | TO MIRELLE MILLER'S DESK. | | | | | | JOHN NGUYEN | | GIS SUPPORT SPECIALIST | | CITY OF WEST PALM BEACH | | MIS DEPARTMENT | | OFFICE: (561) 822-1239 | | FAX: (561) 822-1249 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2009-12-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-12-21 |
Time |
09:47 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-12-21 |
Time |
09:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2010-03-31 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2010-03-31 |
Time |
16:30 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2010-03-31 |
Time |
16:22 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2009-12-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-12-09 |
Time |
13:10 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-12-09 |
Time |
13:10 |
Sent To |
B |
|
Notes |
2009-12-09 13:10:30 | ** DENIED ** | | | | ** REVIEW UNDER 2008 NEC. | | | | 1) NOTE: PLEASE PROVIDE COPY OF CONTRACT FOR ALL NEW | | ELECTRICAL AS SHOWN ON PLANS. THE VALUE FOR THE | | COMPLETE SCOPE OF WORK AS SHOWN IS LOW. FBC 108.3 | | REQUIRES THE VALUE TO INCLUDE ALL LABOR, EQUIPMENT, | | MATERIALS, DESIGN COST ETC EVEN IF ANY OF THESE ITEMS | | ARE OWNER SUPPLIED. THIS INCLUDES CONCRETE WORK FOR | | DUCT BANK, AND ALL ELECTRICAL EQUIPMENT FOR CONTROLS | | ETC. | | | | 2) NOTE: PLEASE PROVIDE INFORMATION FOR WHICH PERMIT | | THE NEW GATES ARE GOING TO BE DONE. HAS THIS WORK BEEN | | APPLIED FOR? HAS THIS WORK ALREADY BEEN PERMITTED? | | | | 3) NOTE: MORE THAN ONE GROUND ROD MAY BE REQUIRED. | | BASED ON SOUTH FLORIDA SOIL CONDITIONS AT THIS LOCATION | | PLEASE SEE NEC 250.56 AND ADJUST PLANS. | | | | 4) NOTE: PLEASE SEE 2008 NEC 250.94 AND PROVIDE | | INTER-SYSTEM BOND. | | | | 5) NOTE: PLEASE IDENTIFY THE TERMINATION OF THE TAPPED | | CONDUCTORS ON THE LOAD SIDE OF THE TRANSFORMER. 240.21. | | THE TAPS ARE SHOWN TO PANEL PP HOWEVER NOT MAIN | | INDICATED? | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2009-11-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-11-30 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-11-30 |
Time |
13:23 |
Sent To |
AD |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2009-12-09 |
Time |
|
Rev Time |
0.00 |
Received By |
mmiller |
Date |
2009-11-24 |
Time |
12:10 |
Sent To |
|
|
Notes |
2009-11-24 12:10:24 | ROUTE TO ADDRESSING |
|
|
|