Plan Review Details - Permit 09110551
Plan Review Stops For Permit 09110551
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2009-12-01 Cont ID  
Sent By jnguyen Date 2009-12-01 Time 13:17 Rev Time 0.00
Received By jnguyen Date 2009-11-30 Time 15:54 Sent To  
Notes
2009-12-01 13:12:08THIS PARCEL WAS PREVIOUSLY UNADDRESSED. THIS
 PERMIT#09110551 WAS FOR A WIRE FLOOD CONTROL GATE FOR
 THE NEW CONSTRUCTION OF A CONTROL STRUCTURE NO. 4
 REPLACEMENT (PERMIT# 09110131) IN THE WATER SUPPLY
 CANAL WITHIN ITS BOUNDARIES. I HAVE EXAMINED THE SITE
 PLANS & ISSUED THE PRIMARY ADDRESS OF 5101 N HAVERHILL
 RD FOR PCN# 74424302000005010. I CREATED THE GIS
 ADDRESS POINT & UPDATED THE RECORD IN COMMUNITYPLUS. I
 SENT OUT A NOTIFICATION E-MAIL TO ALL OF THE RELEVANT
 PARTIES (INCLUDING PAPA). I CALLED THE CONTRACTOR,
 CHARLES FITCH OF C.R. DUNN & LEFT HIM A MESSAGE TO
 INFORM HIM OF THE NEW ADDRESS & FOR HIM TO CORRECT THE
 OWNER RECORD FROM NPBCID TO THE CITY OF WEST PALM BEACH
 FOR THIS PARCEL. I ADJUSTED THE ADDRESS ON THE ORIGINAL
 PERMIT APPLICATION. I HAVE RETURNED THE SITE PLANS BACK
 TO MIRELLE MILLER'S DESK.
  
  
 JOHN NGUYEN
 GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 MIS DEPARTMENT
 OFFICE: (561) 822-1239
 FAX: (561) 822-1249
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-12-21 Cont ID  
Sent By shill Date 2009-12-21 Time 09:47 Rev Time 0.00
Received By shill Date 2009-12-21 Time 09:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-03-31 Cont ID  
Sent By btrobaug Date 2010-03-31 Time 16:30 Rev Time 0.00
Received By btrobaug Date 2010-03-31 Time 16:22 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-09 Cont ID  
Sent By dpalmer Date 2009-12-09 Time 13:10 Rev Time 0.00
Received By dpalmer Date 2009-12-09 Time 13:10 Sent To B
Notes
2009-12-09 13:10:30** DENIED **
  
 ** REVIEW UNDER 2008 NEC.
  
 1) NOTE: PLEASE PROVIDE COPY OF CONTRACT FOR ALL NEW
 ELECTRICAL AS SHOWN ON PLANS. THE VALUE FOR THE
 COMPLETE SCOPE OF WORK AS SHOWN IS LOW. FBC 108.3
 REQUIRES THE VALUE TO INCLUDE ALL LABOR, EQUIPMENT,
 MATERIALS, DESIGN COST ETC EVEN IF ANY OF THESE ITEMS
 ARE OWNER SUPPLIED. THIS INCLUDES CONCRETE WORK FOR
 DUCT BANK, AND ALL ELECTRICAL EQUIPMENT FOR CONTROLS
 ETC.
  
 2) NOTE: PLEASE PROVIDE INFORMATION FOR WHICH PERMIT
 THE NEW GATES ARE GOING TO BE DONE. HAS THIS WORK BEEN
 APPLIED FOR? HAS THIS WORK ALREADY BEEN PERMITTED?
  
 3) NOTE: MORE THAN ONE GROUND ROD MAY BE REQUIRED.
 BASED ON SOUTH FLORIDA SOIL CONDITIONS AT THIS LOCATION
 PLEASE SEE NEC 250.56 AND ADJUST PLANS.
  
 4) NOTE: PLEASE SEE 2008 NEC 250.94 AND PROVIDE
 INTER-SYSTEM BOND.
  
 5) NOTE: PLEASE IDENTIFY THE TERMINATION OF THE TAPPED
 CONDUCTORS ON THE LOAD SIDE OF THE TRANSFORMER. 240.21.
 THE TAPS ARE SHOWN TO PANEL PP HOWEVER NOT MAIN
 INDICATED?
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-11-30 Cont ID  
Sent By dpalmer Date 2009-11-30 Time 13:23 Rev Time 0.00
Received By dpalmer Date 2009-11-30 Time 13:23 Sent To AD
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-12-09 Time   Rev Time 0.00
Received By mmiller Date 2009-11-24 Time 12:10 Sent To  
Notes
2009-11-24 12:10:24ROUTE TO ADDRESSING