Plan Review Details - Permit 09110430
Plan Review Stops For Permit 09110430
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-12-02 Time   Rev Time 0.00
Received By jgomez Date 2009-11-23 Time 10:43 Sent To  
Notes
2009-11-23 10:44:15SENT TO R. REGUEIRO'S DESK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-12-02 Cont ID  
Sent By rregueir Date 2009-12-02 Time 10:27 Rev Time 0.00
Received By rregueir Date 2009-12-02 Time 10:27 Sent To  
Notes
2009-12-02 10:45:40REVISED M-101 DELTA 5, M-201 DELTA 4
  
 NOTE: M-201 DETAIL F, FLOAT SWITCH MUST BE INSTALLED IN
 THE DRAIN PAN OR ON THE SECONDARY DRAIN OUTLET. THE
 FLOAT SWITCH MAY NOT BE INSTALLED IN THE PRIMARY DRAIN
 LINE UNLESS IT IS SUPPLEMENTAL TO THE FLOAT SWITCH
 INSTALLED IN ONE OF THE REQUIRED LOCATIONS.
  