Plan Review Details - Permit 09110379
Plan Review Stops For Permit 09110379 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2009-11-17 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2009-11-17 |
Time |
15:37 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2009-11-17 |
Time |
15:37 |
Sent To |
PC |
|
Notes |
2009-11-17 15:39:48 | TALKED TO MIKE GUSTAFSON. HE SAID TO USE SYSTEM W31 TO | | MEET THE DESIGN PRESSURES. HE ALSO CLARIFIED THAT WORK | | IS ON THE GUEST HOUSE ONLY. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2009-11-17 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2009-11-17 |
Time |
14:51 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2009-11-17 |
Time |
14:51 |
Sent To |
PC |
|
Notes |
2009-11-17 15:08:01 | RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST. | | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO | | THE 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS | | LOCATED ON EXPOSURE "C" NOT "B". THEREFORE THE DESIGN | | PRESSURES ARE HIGHER THAN -90PSF. SELECTED ASSEMBLY ON | | PAGE 11 OF PRODUCT APPROVAL SUBMITTED IS GOOD FOR | | -90PSF. ACCORDING TO NOTE #7 ON PAGE 2 OF PRODUCT | | APPROVAL SUBMITTED FULLY BONDED ASSEMBLIES DESIGN | | PRESSURES CAN'T BE INCREASED NOT EVEN BY RATIONAL | | ANALYSIS. NEED TO SELECT A DIFFERENT APPROVED ASSEMBLY | | THAT MEET THE DESIGN PRESSURES AS REQUIRED BY SEC. R301 | | OF 2007 FLORIDA RESIDENTIAL CODE. | | | | 2- CLARIFY SCOPE OF WORK. PERMIT APPLICATION STATES | | 700SF OF ROOF AREA INCLUDING THE GUEST HOUSE. ACCORDING | | TO THE PROPERTY APPRAISAL WEBSITE THIS SQUARE FOOTAGEE | | DOESN'T MATCH THE SQUARE FOOTAG FOR THE HOUSE AND THE | | GUEST HOUSE. REVISE SQUARE FOOTAGE AS REQUIRED. PERMIT | | FEES WILL BE ADJUST ACCORDINGLY. | | | | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. | | NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
2009-11-17 09:59:37 | OK PER J PAPA 11-17-09 |
|
|
|