Plan Review Details - Permit 09110352
Plan Review Stops For Permit 09110352
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-12-03 Cont ID  
Sent By shill Date 2009-12-03 Time 16:50 Rev Time 0.00
Received By shill Date 2009-12-03 Time 16:50 Sent To  
Notes
2009-12-03 16:51:16EXISTING WINDOWS ARE S/H PER CONTRACTOR
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-11-30 Cont ID  
Sent By shill Date 2009-11-30 Time 11:24 Rev Time 0.00
Received By shill Date 2009-11-30 Time 11:24 Sent To  
Notes
2009-11-30 11:26:16****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PROVIDE INFORMATION REGARDING EXISTING BEDROOM
 WINDOWS, SUCH AS WINDOW TYPE AND CLEAR OPENING. THE
 CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%.
 APPLICATION STATES "EXISTING TO EXISTING;" THIS DOES
 NOT PROVIDE ANY INFORMATION TO SHOW COMPLIANCE WITH FBC
 EB 604.1, FBC R310.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-11-30 Cont ID  
Sent By shill Date 2009-11-30 Time 11:26 Rev Time 0.00
Received By shill Date 2009-11-17 Time 12:55 Sent To  
Notes
2009-11-17 12:56:05TO MISC.#1
  
  