Plan Review Details - Permit 09110337
Plan Review Stops For Permit 09110337
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-08 Cont ID  
Sent By lmartine Date 2009-12-07 Time 10:57 Rev Time 0.00
Received By lmartine Date 2009-12-07 Time 10:57 Sent To  
Notes
2009-12-08 10:57:34IN MECH BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-11-30 Time   Rev Time 0.00
Received By lmartine Date 2009-11-17 Time 10:04 Sent To  
Notes
2009-11-19 10:04:23IN MECH. BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-12-23 Cont ID  
Sent By rregueir Date 2009-12-23 Time 16:42 Rev Time 0.00
Received By rregueir Date 2009-12-23 Time 16:14 Sent To  
Notes
2009-12-23 16:39:09**PROVISO**
  
 1. PROVIDE MANUFACTURER'S DATA FOR SUPPLY AND EXHAUST
 FAN SHOWING EACH TO BE DESIGNED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.12. CABLE TIES ON THE EXHAUST
 FAN ARE NOT A SUBSTITUTE FOR A WIND RESISTANT DESIGN OF
 THE APPLIANCE. THE SUPPLY FAN WIND LOAD REQUIREMENT WAS
 NOT ADDRESSED IN ANY WAY.
  
 2. NEW MECHANICAL EQUIPMENT ON THE ROOF IS SUBJECT TO
 SCREENING AND CONCEALMENT REQUIREMENTS OF THE PLANNING
 DEPARTMENT. FOR ADDITIONAL INFORMATION CONTACT ANA
 MARIA APONTE AT 561-822-1439.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-11-30 Cont ID  
Sent By rregueir Date 2009-11-30 Time 15:49 Rev Time 0.00
Received By rregueir Date 2009-11-30 Time 13:21 Sent To  
Notes
2009-11-30 15:49:12REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE MANUFACTURER'S DATA SHOWING EXHAUST AND
 MAKEUP AIR FANS ARE DESIGNED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.12. IF MANUFACTURER'S WIND
 RESISTANCE DATA INCLUDES INSTALLATION INSTRUCTIONS,
 COORDINATE PLANS WITH THE MANUFACTURER'S INSTRUCTIONS
 PER FBC-M 304.1.
  
 2. MUA DUCT SUPPORT DETAIL IS INSUFFICIENT. EXAMPLE:
 THERE IS NO INDICATION AS TO THE SIZE, THICKNESS OR
 MATERIAL FOR THE ANGLE SUPPORT LEGS. EXAMPLE: DETAIL
 CALLS FOR SCREWS AT 12 INCHES ON-CENTER TO ATTACH LEGS
 TO ROOF. PLEASE INDICATE THE NUMBER AND LOCATION OF
 FASTENERS IN THE DETAIL AT THIS POINT. ALSO, SHOW HOW
 THE ANGLES ARE TO BE ATTACHED TO EACH OTHER AT THE BASE
 OF THE LEGS AND AT THE CORNERS OF THE DUCTS. PROVIDE
 SUFFICIENT DETAIL FOR EACH TYPE OF MATERIAL AND EACH
 TYPE OF CONNECTION TO BE USED IN ACCORDANCE WITH FBC-M
 301.12.
  
 3. GREASE DUCT AND HOOD APPEAR TO BE IN CLOSE PROXIMITY
 TO WOOD CONSTRUCTION AT ROOF/CEILING ASSEMBLY. SHOW
 PROPER CLEARANCES ON PLAN OR PROVIDE DETAIL FOR ANY
 PROPOSE CLEARANCE REDUCTION METHODS TO BE USED IN
 ACCORDANCE WITH FBC-M 506.3.6.
  
 4. GUARDS SHALL BE INSTALLED AT ROOF EDGE WHERE NEW
 EQUIPMENT IS INSTALLED WITHIN 10 FEET OF THE ROOF EDGE
 IN ACCORDANCE WITH FBC-M 304.10.
  
 5. TYPE I HOOD SYSTEMS SHALL BE DESIGNED AND INSTALLED
 TO AUTOMATICALLY ACTIVATE THE EXHAUST FAN WHENEVER
 COOKING OPERATIONS OCCUR IN ACCORDANCE WITH FBC-M
 507.2.1.1. THE ACTIVATION OF THE EXHAUST FAN SHALL
 OCCUR THROUGH AN INTERLOCK WITH THE COOKING APPLIANCES,
 BY MEANS OF HEAT SENSORS OR BY MEANS OF OTHER APPROVED
 METHODS.
  
 6. PROVIDE ELEVATION DRAWINGS WITH PHOTOGRAPHIC
 DEPICTIONS OF EXISTING CONDITIONS TO FACILITATE A
 ZONING PLAN REVIEW FOR SCREENING AND OTHER MUNICIPAL
 REQUIREMENTS. A ZONING REVIEW IS NOT BEING PERFORMED AT
 THIS TIME DUE TO LACKING INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]