Plan Review Details - Permit 09110267
Plan Review Stops For Permit 09110267
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-01-06 Cont ID  
Sent By jwitmer Date 2010-01-06 Time 11:23 Rev Time 0.50
Received By jwitmer Date 2010-01-06 Time 11:23 Sent To  
Notes
2010-01-06 11:27:54BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 1) PLANS ARE MISSING THE ROOF PRESSURE ZONES, 1,2 & 3
 PLEASE PROVIDE BEFORE ROOF SHEATHING INSPECTION.
  
 2) MISSING ROOFING PRODUCT APPROVAL AND ROOFING
 CONTRACTOR, WILL REQUIRE A SEPERATE PERMIT, FEES AND
 ASSOCIATED REVIEW.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-08 Cont ID  
Sent By jwitmer Date 2009-12-08 Time 09:00 Rev Time 1.50
Received By jwitmer Date 2009-12-08 Time 07:23 Sent To  
Notes
2009-12-08 09:17:30BUILDING PLAN REVIEW
 PERMIT: 09110267
 ADD: 11125 CLARE AVE
 CONT: BUTLER CONSTRUCTION
 TEL: (561)832-9700
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 DECEMBER 08/ 2009
  
 1) MISSING WIND DESIGN, 1609.6.2 WIND DESIGN PROCEDURES
 1.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 1.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
 PROVIDE POSITIVE & NEGATIVE PRESSURES FOR ROOF ZONES
 1,2 & 3.
  
 2) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 2.1) STANDING SEAM METAL ROOF
  
 3) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) PLEASE REVIEW ROOF SHEATHING NAILING PATTERNS IN THE
 2007 FBC (DOUBLE LINED IN MARGIN, CODE CHANGE)
 SECTIOIN, TABLE 2304.9.1(31)
 6 INCH O.C. EDGES AND INTERMEDIATE, 4 INCH O.C. AT
 COMPONENT AND CLADDING EDGE STRIP #3 [REFER TO FIGURE
 6-3 OF ASCE 7]
  
 7) CANOPY PLAN INDICATES A 8"X16" BEAM:
  
 7.1) THE MINIMUM DESIGN MIX FOR CONCRETE BEAMS IS NOT
 PROVIDED PER SECTION 1905.1.1.
  
 7.2) PLANS DO NOT INDICATE SPACING OF STIRRUPS PER:
 907.13 REQUIREMENTS FOR STRUCTURAL INTEGRITY. THE
 DETAILING OF REINFORCEMENT AND CONNECTIONS BETWEEN
 CONCRETE MEMBERS SHALL COMPLY WITH THE PROVISIONS OF
 ACI 318, SECTION 7.13, TO IMPROVE STRUCTURAL INTEGRITY.
  
 ACI 530 BEAMS 7.5.3.1 SHEAR REINFORCEMENT SHALL BE
 PARALLEL TO THE DIRECTION OF APPLIED SHEAR FORCE.
 SPACING OF SHEAR REINFORCEMENT SHALL NOT EXCEED THE
 LESSER OF D/2 OR 48 INCHES.
  
 8) THE FOUNDATION PLAN INDICATES A 24 INCH BY 24 INCH
 BY 8 INCH COLUMN BUT PLANS INDICATE A 24 INCH BY 8
 INCH, COLUMN LOCATION FURTHEST TO THE RIGHT. THERE
 APPEARS TO BE A DISCREPANCY, POSSIBLY A TYPE-O. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-01-07 Cont ID  
Sent By dpalmer Date 2010-01-07 Time 08:08 Rev Time 0.00
Received By dpalmer Date 2010-01-07 Time 08:08 Sent To  
Notes
2010-01-07 08:12:43PROVISO
  
 1) NOTE: NO CHANGES OR INFORMATION SHOWN FOR EXTERIOR
 LIGHTING CONTROLS. MUST MEET 13-415.AB.1.4. IF
 EXISTING, STILL NEEDS TO MEET REQUIREMENTS GOING BACK
 EVEN FOR THE LAST 8 CODE CYCLES. (
 PHOTO-SENSOR/TIME-CLOCK/ ASTRONOMICAL TIME CLOCK WITH
 PROGRAMMING BACK UP.
 MAY NOT BE BY BREAKER OR SP SWITCH ONLY.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 561-805-6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-03 Cont ID  
Sent By dpalmer Date 2009-12-03 Time 15:25 Rev Time 0.00
Received By dpalmer Date 2009-12-03 Time 15:25 Sent To  
Notes
2009-12-03 15:25:42 
 ** DENIED**
  
 1) NOTE: THE FOLLOWING CODES INDICATED ON THE SHEET ARE
 NOT ADOPTED BY THE STATE OF FLORIDA.
 PLANS LIST THE 2009 NFPA-101, HOWEVER THIS SHOULD BE
 2006. THIS COULD BE RED-LINED HOWEVER COMING BACK FOR
 OTHER COMMENTS.
 PLANS LIST A 2006 EDITION OF NFPA-70 ( NEC) HOWEVER
 THIS SHOULD BE 2008. FOR INFORMATION THERE WAS NOT A
 2006 NEC.
  
 2) NOTE: PLANS INDICATE NEW LIGHTING HOWEVER NO
 INFORMATION ON TYPE OF LIGHTS, HOW MANY LIGHTS, AND
 CONTROL OF LIGHTS ETC.
 13-415.AB.2 FOR EXTERIOR LIGHTING ALLOWANCES.
 13-415.AB.1.4 FOR TYPE OF CONTROL REQUIRED.
 NEC 310.16,240.4, 220.12, 220.42 FOR LOADS, CIRCUITING
 AND OVER CURRENT PROTECTION.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-01-11 Cont ID  
Sent By mawillia Date 2010-01-11 Time 13:40 Rev Time 0.00
Received By mawillia Date 2010-01-11 Time 13:35 Sent To B
Notes
2010-01-11 13:40:02*****APPROVED*****
  
  
 THE COMMENT FROM THE PREVIOUS PLAN REVIEW HAS BEEN
 ADDRESSED; SINGLE SHEET A1.1 STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-12-07 Cont ID  
Sent By mawillia Date 2009-12-07 Time 12:45 Rev Time 0.00
Received By mawillia Date 2009-12-07 Time 12:29 Sent To  
Notes
2009-12-07 12:43:42*****PARTIAL APPROVAL*****
  
  
 THE SINGLE PLAN SHEET (A1.1) TO BE FIRE-STAMPED WHEN
 THE FOLLOWING APPLICABLE CODE INFORMATION FLORIDA FIRE
 PREVENTION CODE 2007 AND NFPA 101, LIFE SAFETY CODE,
 2006 EDITION ARE CORRECTLY REFERENCED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-30 Cont ID  
Sent By lmartine Date 2009-12-29 Time 09:26 Rev Time 0.00
Received By lmartine Date 2009-12-29 Time 09:26 Sent To  
Notes
2009-12-30 09:29:15C--13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-30 Cont ID  
Sent By lmartine Date 2009-12-08 Time 09:25 Rev Time 0.00
Received By lmartine Date 2009-11-16 Time 14:27 Sent To  
Notes
2009-11-16 14:27:50C-34

Review Stop Z ZONING
Rev No 1 Status P Date 2009-12-07 Cont ID  
Sent By astelly Date 2009-12-07 Time 10:36 Rev Time 0.00
Received By astelly Date 2009-12-07 Time 10:36 Sent To B
Notes
***NONE***