Plan Review Details - Permit 09110254
Plan Review Stops For Permit 09110254
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2009-12-14 Cont ID  
Sent By dpalmer Date 2009-12-14 Time 14:32 Rev Time 0.00
Received By dpalmer Date 2009-12-14 Time 14:32 Sent To  
Notes
2009-12-14 14:33:08THIS IS FOR ELECTRICAL SERVICE EQUIPMENT FOR PORTABLE
 GENERATOR ONLY. NO PERMANANT GENERATOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-09 Cont ID  
Sent By jwitmer Date 2009-12-09 Time 13:45 Rev Time 0.77
Received By jwitmer Date 2009-12-09 Time 13:45 Sent To  
Notes
2009-12-09 13:58:56BUILDING PLAN REVIEW
 PERMIT: 09110254
 ADD: 901 45TH ST
 CONT: KNIGHT ELECTRIC
 TEL: (561) 689-3500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS WILL NEED TO PROVIDE WIND DESIGN CRITERIA PER
 1609.6.2 WIND DESIGN PROCEDURES
 1.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 1.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
  
  
  
 2) PLEASE PROVIDE DETAILS FOR ANCHORING TO RESIST THE
 EFFECTS OF OVERTURNING AND OR SLIDDING.1604.4 ANALYSIS.
 LOAD EFFECTS ON STRUCTURAL MEMBERS AND THEIR
 CONNECTIONS SHALL BE DETERMINED BY METHODS OF
 STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM,
 GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH
 SHORT- AND LONG-TERM MATERIAL PROPERTIES.EVERY
 STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING
 EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS
 CHAPTER. SEE SECTION 1609 FOR WIND LOADS, AND SECTION
 1610 FOR LATERAL SOIL LOADS.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-05-24 Cont ID  
Sent By btrobaug Date 2010-05-24 Time 11:35 Rev Time 0.00
Received By btrobaug Date 2010-05-24 Time 11:34 Sent To  
Notes
2010-05-24 11:35:51CONTRACTOR BROUGHT IN SWITCHBOARD SPEC'S./WRT

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-12-14 Cont ID  
Sent By btrobaug Date 2009-12-14 Time 12:05 Rev Time 0.00
Received By btrobaug Date 2009-12-14 Time 11:54 Sent To I
Notes
2009-12-14 12:05:32 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 PROVISO
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 TRANSFER SWITCHES THAT ARE TO BE INSTALLED UNDER THIS
 PERMIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2009-12-14 Cont ID  
Sent By dpalmer Date 2009-12-14 Time   Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-14 Cont ID  
Sent By btrobaug Date 2009-12-14 Time 14:40 Rev Time 0.00
Received By btrobaug Date 2009-11-16 Time 10:20 Sent To PC
Notes
2009-11-16 10:25:09B24
  

Review Stop Z ZONING
Rev No 2 Status N Date 2009-12-14 Cont ID  
Sent By dpalmer Date 2009-12-14 Time 14:32 Rev Time 0.00
Received By dpalmer Date 2009-12-14 Time 14:31 Sent To  
Notes
2009-12-14 14:32:51THIS IS FOR ELECTRICAL SERVICE EQUIPMENT FOR PORTABLE
 GENERATOR ONLY. NO PERMANANT GENERATOR.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-12-08 Cont ID  
Sent By lfranco Date 2009-12-08 Time 16:53 Rev Time 0.00
Received By lfranco Date 2009-12-08 Time 16:53 Sent To E
Notes
2009-12-08 16:56:13PLANNING AND ZONING: **** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING. THE SUBMITTAL OF THE
 REQUESTED INFORMATION MAY GENERATE ADDITIONAL COMMENTS.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY/SITE PLAN
 AND SHOW EXACT LOCATION OF GENERATOR AND MECHANICAL
 EQUIPMENT.
  
 3. THIS PROPERTY IS PART OF THE ST. MARY'S COMMUNITY
 SERVICE PLANNED DEVELOPMENT ("CSPD"), AN APPLICATION
 FOR A MINOR AMENDMENT TO THE CSPD SHOWING THE PROPOSED
 GENERATOR WILL BE REQUIRED TO BE FILED TO THE PLANNING
 AND ZONING DEPARTMENT AND APPROVED PRIOR TO THE
 BUILDING PERMIT BEING APPROVED. SEE
 HTTP://WWW.CITYOFWPB.COM/PLAN/INDEX.PHP, UNDER
 DEVELOPMENT APPLICATION FOR REQUIREMENTS OF A MINOR PD
 AMENDMENT.
  
 THE SITE PLAN SHALL INCLUDE THE FOLLOWING:
  
 A. SCREENING AND ELEVATION OF WALL/HEDGES AROUND
 GENERATOR/ FUEL TANK, AND SETBACK DISTANCE FROM
 PROPERTY LINE.
  
 4. PURSUANT TO SECTION 94-444(B) OPEN SPACE
 STANDARDS:
  
 (B) FUEL OR OIL OR PROPANE TANKS, GENERATORS SHALL NOT
 BE PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED.
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY, DURABLE WOOD AND
 STEEL.
  
 WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS. A FOUR-SIDED ENCLOSURE
 WITH MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL, AN
 OBSCURING GATE IS REQUIRED AS A CONDITION FOR SITE PLAN
 APPROVAL.
  
 THE SCREENING SHALL ENCLOSE BOTH FUEL TANK AND ROOFTOP
 EXHAUST.
  
 5. PURSUANT TO SECTION 94-305(B)(4) SETBACKS (B)(4)
 SETBACK ENCROACHMENT:
 MECHANICAL EQUIPMENT SHALL NOT PROJECT MORE THAN 4 FEET
 INTO A SETBACK.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  