Plan Review Details - Permit 09110225
Plan Review Stops For Permit 09110225
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-02 Cont ID  
Sent By jwitmer Date 2009-12-02 Time 15:56 Rev Time 2.22
Received By jwitmer Date 2009-12-02 Time 15:56 Sent To  
Notes
2009-12-02 17:08:48BUILDING PLAN REVIEW
 PERMIT: 09110225
 ADD: 115 S OLIVE AVE
 CONT: TO BE DETERMINED/ CONTACT JOHN WEBB
 TEL: (561312-6247
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 DECEMBER 02/ 2009
 ACTION: DENIED
  
 1) A CONTRACTOR WITH THE CORRECT LICENSURE TO BE SIGNED
 ONTO THE PERMIT BEFORE ISSUANCE OF THE PERMIT FL S S
 489.
  
 2) BUILDING IS TO BE CONSIDERED A THRESHOLD BUILDING BY
 FL S S 553.71(7) AN ASSEMBLY BUILDING WHICH EXCEEDS
 5,000 SQUARE FT. AND AN OCCUPANT LOAD OF 500
 PERSONS.
  
 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 2C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 2D) INFORMATIONAL, 109.3.6 THRESHOLD BUILDINGS,
 OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26.
 ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4) SHEET A-2 FIRST FLOOR:
 4A) PLEASE REVIEW BUILDING TYPE OF CONSTRUCTION, PLANS
 INDICATE A TYPE V STRUCTURE TABLE 503 FOR A A2
 OCCUPANCY PLEASE DECLARE A "A OR B", NOTE 504.2 THE
 AUTOMATIC SPRINKLER INCREASE WILL ONLY PROVIDE A STORY
 INCREASE, THE MINIMUM COULD BE EITHER A VA (PROTECTED
 OR A IIIB UNPROTECTED).
  
 4B) THE PLANS ARE NOT CLEAR TO WHERE THE FRONT PROPERTY
 LINE IS LOCATED, IT APPEARS THE BAR STOOLS AND FOLDING
 DOORS MAY BE PAST THE PROPERTY LINE, PLEASE INDICATE
 THE LOCATION OF THE FRONT PROPERTY LINE. 3202.2 DOORS
 AND WINDOWS SHALL NOT OPEN OR PROJECT INTO THE PUBLIC
 RIGHT -OF-WAY.
  
 4C) THE BACK STAIRWAY APPEARS TO BE DUMPING TO THE
 INTERIOR OF THE BUILDING NOT WITHIN A VESTIBULE BUT
 INTO THE KITCHEN AREA PLEASE REVIEW EGRESS THROUGH
 KITCHENS, SECTION 1014.2(2).
  
 4D) THE FIRST FLOORA-2 ASSEMBLY AREA WITH THE CURRENT
 LAYOUT ONLY HAS ONE MEANS OF EGRESS, THROUGH THE FRONT
 ENTRY, NOTE TABLE 1019.2 BUILDING WITH ONE EXIT FOR AN
 ???A??? ASSEMBLY 49 OCCUPANT LOAD AND TRAVEL DISTANCE
 OF 75 FEET.
  
 4E) BAR SEATING 102 DOES NOT INDICATE IF THIS IS NEW
 CONSTRUCTION OR IF PART OF THE ALTERATIONS PLEASE
 REVIEW 11-5.4 & EXCEPTIONS TO PROVIDE VERTICAL
 ACCESSIBILITY.
  
 4F) THIS COMMENT WILL STAND FOR ALL THREE FLOOR LEVELS
 PLANS INDICATE A MERCANTILE OCCUPANCY FOR THE MINIMUM
 FLAME SPREAD AND SMOKE DEVELOPMENT, PLEASE UPDATE FOR
 AN A2 OCCUPANCY, TABLE 803.5. THE PLANS ARE DEFICIENT
 IN THE WALL & CEILING FINISHES. SHEET A1 DOES PROVIDE
 THE PARAMETERS FOR THE MATERIALS FOR FLAME SPREAD &
 SMOKE DEVELOPMENT BUT NOT THE ACTUAL FINISH MATERIALS.
 OUR CONCERNS ARE:
  
 4F)(1) 803.4.1 DIRECT ATTACHMENT AND FURRED
 CONSTRUCTION.
  
 4F)(2) 803.4.2 SET-OUT CONSTRUCTION.
  
 4F)(3) 803.4.4 MATERIALS.
  
 4F)(4)803.6 TEXTILES.
  
 4G)(5) 803.9.1 MATERIALS AND INSTALLATION. ACOUSTICAL
 MATERIALS COMPLYING WITH THE INTERIOR FINISH
 REQUIREMENTS OF SECTION 803 SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND
 APPLICABLE PROVISIONS FOR APPLYING INTERIOR FINISH.
  
 4G)(6) 806.3 FOAM PLASTIC. FOAM PLASTIC USED AS TRIM IN
 ANY OCCUPANCY SHALL COMPLY WITH SECTION 2604.2.
  
 4G)(7)806.4 PYROXYLIN PLASTIC. IMITATION LEATHER OR
 OTHER MATERIAL CONSISTING OF OR COATED WITH A PYROXYLIN
 OR SIMILARLY HAZARDOUS BASE SHALL NOT BE USED IN GROUP
 A OCCUPANCIES.
  
 4G)(8) 806.5 INTERIOR TRIM. MATERIAL, OTHER THAN FOAM
 PLASTIC USED AS INTERIOR TRIM SHALL HAVE A MINIMUM
 CLASS C FLAME SPREAD AND SMOKE-DEVELOPED INDEX WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84, AS DESCRIBED IN
 SECTION 803.1. COMBUSTIBLE TRIM, EXCLUDING HANDRAILS
 AND GUARDRAILS, SHALL NOT EXCEED 10 PERCENT OF THE
 AGGREGATE WALL OR CEILING AREA IN WHICH IT IS LOCATED.
  
 4G)(9) PLANS INDICATE FALSE THATCHED ROOF BY OTHERS,
 PROVIDE INFO FOR 803.2/ 803.2.1.
  
 4H) PLANS INDICATE BATTERY BACK UP EMERGENCY BACK UP
 LIGHTS, BUT FAIL TO INCLUDE THE STAIRWELLS SECTION
 1006.2.
  
 4I) THIS COMMENT WILL STAND FOR ALL FLOORS , PLEASE
 INDICATE ON THE LIFE SAFETY PLAN THE ACCESSIBLE
 SEATING11-5.1 AND ACCESS AISLES 1014.3, 1014.3 (1)-(3).
  
 4J) PLANS FAIL TO INDICATE PORTABLE FIRE EXTINGUISHER
 LOCATIONS, 906.1.
  
 4K) PLANS DO NOT INDICATE IF THE ELEVATOR AND
 DUMBWAITER ARE NEW OR EXISTING ELEMENTS, PLEASE PROVIDE
 WALL TAGS IDENTIFYING FIRE RATED WALLS (SHAFTS) SECTION
 707.4.AND RATED DOORS SECTION 715,.
  
 4L) PLANS DO NOT HAVE ANY DOOR SCHEDULE INDICATING THE
 SIZE OF THE DOOR, FIRE RATING NOR
 GLAZING WITHIN THE DOOR ETC, 715.3 OPENING
 PROTECTIVE???S, 11-4.13.5.
  
 5) SHEET A-3:
  
 5A) THE COMMON PATH OF TRAVEL HAS BEEN EXCEEDED FROM
 THE MOST REMOTE POINT WITHIN THE LADIES RESTROOM TO THE
 CLOSET VERTICAL EXIT. 1014.3.
  
 5B) DOOR# 209 DOES NOT HAVE THE MANEUVERING CLEARANCES
 ON THE LATCH SIDE OF THE DOOR. PLEASE REVIEW 11-4.13.6
 AND FIGURE 25(A).
  
 6)SHEET A4:
 6A) PLANS ARE MISSING ARCHITECTURAL DETAIL FOR THIS
 LEVEL THEY APPEAR TO BE CONCEPTUAL IN MANNER AT THIS
 POINT, ADDITIONAL INFORMATION REQUIRED.106.1.2.
  
 6B) WHAT TYPE OF FLOOR CEILING ASSEMBLY IS INSTALLED ON
 THIS BUILDING? PLEASE INDICATE THE FLOOR LOADING OF THE
 FLOOR CEILING ASSEMBLY TABLE1607.1.
  
 6C) CURRENTLY THE PLANS DO NOT PROVIDE ENOUGH DETAILS,
 BUT A CONCERN IS THE AMOUNT OF OPENNESS TO THE SOUTH
 SIDE OF THE ISLAND BAR VERSES THE PROPERTY LINE. TABLE
 602 WILL REQUIRE A FIRE RATING DEPENDING ON THE
 BUILDING TYPE, TABLE 704.8 ALLOWS 25% OPENINGS FOR
 PROTECTED OPENINGS ( SPRINKLERS), THE ISSUE WILL BE THE
 FOOTNOTE ???I??? UNLIMITED UNPROTECTED OPENINGS! THE
 PLANS ALSO INDICATE A PARAPET WALL ON THE SOUTH SIDE
 WITH THE HEIGHT UNKNOWN, BUT COULD BE USED AS PART OF
 THE WALL PER CENT AGE.
  
 6D) THE NORTH STAIRWELL ADDITION AND THE SOUTH RESTROOM
 AND BEER COOLER WILL ALSO NEED TO PROVIDE WALL TAGS TO
 IDENTIFY WALL TYPES IN REQUIRED RATED HOURS TABLE 602.
  
 6E) THERE IS NO ROOFING PLAN FOR THIS ADDITIONAL STORY,
 PLANS ARE CONCEPTUAL.
  
 7A) SHEET A-7 INDICATES A NEW BALCONY, THE BOTTOM BEING
 LOCATED APPROXIMATELY 12???-6?????? TO THE BOTTOM OF
 THE NEW BALCONY. PLEASE REVIEW 3202.3.2 FOR ALLOWABLE
 ENCROACHMENT.
 CONCEPTUAL IN NATURE.
  
 7B) SHEET A-7 ALSO NEEDS TO PROVIDE DETAIL FOR THE
 CANOPY/ EYEBROW ABOVE THE 2ND FLOOR.
 WIND INFO FOR CANOPY, DESIGN INFO, CONCEPTUAL IN
 NATURE.
  
 8A) SHEET A8 CONCEPTUAL IN NATURE, CONCERNS ARE THE
 EGRESS DOORS BENEATH THE EXTERIOR STAIR TO BE 1 HR
 RATED.
  
 8B) PROVIDE A STAIR DESIGN WITH LOADING TABLE 1607.1,
 HANDRAILS 1012/ GUARDRAIL 1013.
  
 8C) A CONCERN ABOUT THE EXTERIOR STAIR BEING A REQUIRED
 EXIT AND LOCATED WITHIN 10???-0??? OF THE PROPERTY
 LINE. SECTION 1024.3 THIS SECTION IDENTIFIES THE
 PROTECTION NEEDED FROM FIRE FROM ADJACENT BUILDINGS,
 AND OR FUTURE BUILDINGS. WHILE THIS BUILDING IS A
 SPRINKLERED BUILDING THIS PORTION (EXTERIOR STAIR) DOES
 NOT INDICATE IT TO BE SPRINKLERED. THE OTHER ISSUE
 IS IS THIS AN EXIT OR EXIT ACCESS, FOR A FULLY
 SPRINKLERED BUILDING THE TRAVEL DISTANCE IS 250??? FROM
 THE MOST REMOTE POINT ON THE ROOF TOP AND TRAVEL
 DISTANCE DOWN THE STAIRS IT APPEARS TO BE LESS THAN 250
 FEET PLEASE VERIFY TRAVEL DISTANCE AND CONSIDER THE
 SPRINKLERING OF THE STAIRS.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW. NO PRODUCT APPROVALS WERE SUBMITTED FOR
 REVIEW. THIS REVIEW WAS FOR A CONCEPTUAL CONCEPT SINCE
 MUCH OF THE REQUIRED INFORMATION WAS NOT AVAILABLE!
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-12-09 Cont ID  
Sent By mcarsill Date 2009-12-09 Time 08:47 Rev Time 0.00
Received By mcarsill Date 2009-12-08 Time 13:48 Sent To  
Notes
2009-12-09 08:47:16 
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 3. EXITS ARE TO REMAIN CLEAR AND ACCESSIBLE.
  
 4. OCCUPANT LOAD WILL BE DETERMINED BY THIS OFFICE.
  
 5. TACTILE SIGNAGE REQUIRED AT EXIT DOORS.
  
 6. EMPLOYEES SHALL BE TRAINED IN CROWD MANAGEMENT
 PROCEDURES. PLEASE GO TO MARYLAND STATE FIRE MARSHAL'S
 WEB SITE AND CLICK ON THE CROWD MANAGEMENT TRAINING
 ICON. EMPLOYEES ARE TO WATCH THE TRAINING VIDEO AND
 COMPLETE THE TEST. CERTIFICATES ARE TO BE PROVIDED TO
 THIS OFFICE.
  
 7. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL HANDRAILS AND GUARDRAILS.
  
 8. EXIT DOORS ON SOME SHEETS ARE SWINGING IN THE WRONG
 DIRECTION.
  
 9. SEPARATE PLANS AND PERMITS REQUIRED FOR THE HOOD,
 DUCT, AND FIRE SUPPRESSION SYSTEMS.
  
 10. INTERIOR FINISH MATERIALS SUCH AS THE THATCH ROOF
 MATERIALS SHALL BE FIRE RETARDANT.
  
 11. PLANS INDICATE INTERIOR FINISH FOR A MERCANTILE
 OCCUPANCY. THE OCCUPANCY WILL BE AN ASSEBLY OCCUPANCY.
  
 12. BUILDING ADDRESS REQUIRED ON PROPER ELEVATION. A
 MINIMUM OF AT LEAST 6" HIGH AND AT LEAST 1" WIDE
 NUMBERS ARE REQUIRED.
  
 13. PLEASE INDICATE SLIP RESISTANT METHODS PLANNED FOR
 THE EXTERIOR STAIRS.
  
 14. NO FIRE SPRINKLER SYSTEM DRAWINGS PROVIDED. PLEASE
 PROVIDE FIRE SPRINKLER DRAWINGS AND HYDRAULIC
 CALCULATIONS. SEPARATE PLANS AND PERMITS REQUIRED.
  
 15. NO FIRE ALARM SYSTEM INFORMATION PROVIDED. THE FIRE
 ALARM SYSTEM SHALL BE A VOICE EVACUATION TYPE. SEPARATE
 PLANS AND PERMITS REQUIRED.
  
 16. NO DOOR SCHEDULE PROVIDED. PLEASE PROVIDE A DOOR
 SCHEDULE INDICATING THE TYPE OF HARDWARE PLANNED. EXIT
 DOORS SUBJECT TO AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS SHALL BE EQUIPPED WITH PANIC HARDWARE. FIRE
 RATED DOORS SHALL BE EQUIPPED WITH LISTED FIRE RATED
 EXIT HARDWARE. ALL RATED DOORS SHALL BE EQUIPPED WITH
 SELF-CLOSING DEVICES.
  
 17. PLEASE INDICATE RISE, RUN, AND TREAD DEPTH FOR ALL
 STAIRS.
  
 18. DOOR OPENINGS OBSERVED ON WEST ELEVATION NEAR EXIT
 DOORS.
  
 19. NO LIGHT FIXTURES OBSERVED FOR WEST EXIT STAIRS.
  
 20. ALL COOLERS AND FREEZERS SHALL BE PROVIDED WITH
 FIRE SPRINKLER PROTECTION.
  
 21. PLEASE INDICATE SEATING LOCATIONS FOR PHYSICALLY
 CHALLENGED PERSONS.
  
 22. PLEASE PROVIDE FIRESTOPPING DETAILS.
  
 23. PLEASE INDICATE HOURLY FIRE RATINGS OF EXISTING
 STAIRS AND ALL VERTICAL SHAFTS WHETHER NEW OR EXISTING.
  
 24. ONE OF THE EXIT STAIRS TERMINATES INTO KITCHEN 109.
 PLEASE REVIEW EXITING THROUGH KITCHEN REQUIREMENTS.
  
 25. ELEVATOR WARNING SIGNS ARE REQUIRED AT ELEVATOR
 LOCATIONS.
  
 26. WHO'S PROPERTY DOES THE REAR EXIT STAIR TERMINATES
 ONTO.
  
 27. EXISTING DOOR IS LOCATED WITHIN AN EXISTING STAIR.
 WHAT IS THE PURPOSE OF THIS DOOR. SINCE NO EXITING
 OCCURS THIS AREA NEEDS TO BE SEALED.
  
 28. SOME BUILDING ELEMENTS AND FURNITURE APPEAR TO BE
 LOCATED OVER THE PROPERTY LINE. AIR RIGHTS APPEAR TO BE
 REQUIRED.
  
 29. PLEASE ILLUSTRATE ANY NATURAL GAS SUPPLY LINES AND
 APPURTENANT EQUIPMENT.
  
 DENIED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX
 MCARSILLO@WPB,ORG
2009-12-08 13:48:36SENT TO MIKE CARSILLO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2009-11-10 Time 11:00 Sent To  
Notes
2009-11-10 11:00:35C13
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-12-01 Cont ID  
Sent By aaponte Date 2009-12-01 Time 14:23 Rev Time 0.00
Received By aaponte Date 2009-12-01 Time 14:23 Sent To  
Notes
2009-12-01 14:33:581. PLEASE SUBMIT FLOOR PLAN WITH EXISTING CONDITIONS
 AND DEMOLITION PLAN.
 2. PLEASE INDICATE THE PROPERTY LINE ON ALL FLOOR PLANS
 AND ELEVATIONS.
 3. FOLDINGS DOORS SHALL NOT ENCROACH INTO THE ROW.
 PLEASE VERIFY.
 4. PLEASE INDICATE DIMENSION OF NEW 2ND FLOOR BALCONY
 TO VERIFY COMPLIANCE. BALCONIES SHALL NOT BE LESS THAN
 4 FEET FROM THE BACK OF CURB.
 5. FOR THE FIRST FLOOR PLAN, PLEASE INDICATE EXISTING
 SIDEWALK CONDITIONS, MATERIALS, TREE GRATES AND TREES,
 AND LOCATE THE BACK OF CURB TO VERIFY COMPLIANCE WITH
 REQUIRED SETBACK.
 6. PLEASE SUBMIT LANDSCAPE DRAWINGS FOR ROOF TOP
 TERRACE. A MINIMUM OF 20% TREE CANOPY IS REQUIRED. SEE
 TABLE IV-8 ON SECTION 94-109 OF THE ZLDR.
 7. PLEASE STUDY THE POSIBILITY TO ENHANCE THE ALLEY
 FACADE WITH CERTAIN PERCENTAGE OF OPENINGS AND
 ARCHITECTURAL FEATURES.
 8. PLAES PROVIDE A DETAIL TABLE INDICATING THE TOTAL
 AREA OF THE SITE, AND THE AREA FOR THE BUILDING. PLEASE
 SEPARATE SQUARE FOOTAGE BASED OF DEFINITION FOR GROSS
 BUILIDNG AREA IN SECTION 94-109 OF THE ZLDR.
 9. PLEASE INDICATE TOTAL BUILDING HEIGHT AND BUILDING
 FOOTPRINT FOR EACH FLOOR.