Plan Review Details - Permit 09110210
Plan Review Stops For Permit 09110210
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-12-07 Cont ID  
Sent By rmcdouga Date 2009-12-07 Time 11:09 Rev Time 0.00
Received By rmcdouga Date 2009-12-07 Time 11:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-11-30 Cont ID  
Sent By rmcdouga Date 2009-11-30 Time 10:36 Rev Time 0.00
Received By rmcdouga Date 2009-11-30 Time 10:36 Sent To  
Notes
2009-11-30 10:40:13DENIED BY BUILDING
  
 1) THE EXISTING FENCE IS REQUIRED TO COMPLY WITH THE
 BARRIER REQUIREMENTS OF FBC R4101.17. SPECIFY THIS ON
 THE PLANS.
  
 2) THE ALARMS ON THE HOUSE ARE REQUIRED TOP COMPLY WITH
 FBC R4101.17.1.9. SPECIFY THIS ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-12-07 Cont ID  
Sent By rmcdouga Date 2009-12-07 Time 11:14 Rev Time 0.00
Received By rmcdouga Date 2009-12-07 Time 11:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-11-30 Cont ID  
Sent By rmcdouga Date 2009-11-30 Time 10:40 Rev Time 0.00
Received By rmcdouga Date 2009-11-30 Time 10:40 Sent To  
Notes
2009-11-30 10:49:41DENIED BY ELECTRICAL
  
 1) SHOW COMPLIANCE WITH 2008 NEC 680.26 (B) (2) FOR
 EQUIPOTENTIAL BONDING OF PERIMETER SURFACES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-11-30 Cont ID  
Sent By rmcdouga Date 2009-11-30 Time 10:40 Rev Time 0.00
Received By rmcdouga Date 2009-11-17 Time 14:28 Sent To  
Notes
2009-11-17 14:27:35TO RES SWIMMING POOL BOX
  
2009-11-09 16:40:46TO ZONING
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-12-07 Cont ID  
Sent By rmcdouga Date 2009-12-07 Time 11:14 Rev Time 0.00
Received By rmcdouga Date 2009-12-07 Time 11:14 Sent To  
Notes
2009-12-07 11:14:34CALCULATONS SHOWING THAT WATER VELOCITY IN POOL
 PRESSURE PIPING DOES NOT EXCEED 10 FT/SEC PER FBC R
 4101.6.3 TO BE PROVIDED TO PLUMBING INSPECTOR.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-11-30 Cont ID  
Sent By rmcdouga Date 2009-11-30 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2009-11-30 Time 09:29 Sent To  
Notes
2009-11-30 10:35:342007 FBC W/2009 REVISIONS
  
  
 DENIED BY PLUMBING
  
 1) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS. FBC
 R4101.6.3
  
 2) PROVIDE A PIPING DIAGRAM WITH ALL PIPE SIZES
 SPECIFIED. FBC R4101.6
  
 3) SPECIFY THE WATER VELOCITY IN FEET PER SECOND FOR
 THE FOR THE SUCTION AND SUPPLY LINES. FBC R4101.6.3
  
 4) SPECIFY THE MAXIMUM FLOW RATE OF THE PUMP IN GALLONS
 PER MINUTE FOR THE TDH OF THE SYSTEM BEING INSTALLED.
 SUBMIT THE SPECIFICATIONS AND FLOW CHART FOR THE PUMP
 THAT WILL BE USED. FBC R4101.7
  
 5) THE PUMP CURVE CHART SUBMITTED HAS A 3/4 HP PUMP
 INDICATED ON IT AND THE PLANS SPECIFY A 2 HP PUMP.
 PLEASE CORRECT.
  
 6) THE POOL HEATER IS REQUIRED BY FBC R4101.14.2 TO
 HAVE A PERMANENT BY-PASS OR ANTI-SIPHON DEVICE. SHOW
 COMPLIANCE.
  
 7) THE PIPING DIAGRAM ON SHEET 2 SHOWS TWO MAIN DRAINS
 FOR THE POOL AND THE SPA. THE DRAWING ON SHEET 1 SHOWS
 CHANNEL DRAINS. PLEASE COORDINATE DRAWINGS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2009-11-16 Cont ID  
Sent By kdfreema Date 2009-11-16 Time 14:33 Rev Time 0.00
Received By kdfreema Date 2009-11-16 Time 14:33 Sent To  
Notes
2009-11-16 14:33:36POOL EQUIPMENT MUST BE SET BACK A MINIMUM OF FOUR FEET
 FROM THE SIDE PROPERTY LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-11-13 Cont ID  
Sent By kdfreema Date 2009-11-13 Time 08:28 Rev Time 0.00
Received By kdfreema Date 2009-11-13 Time 08:28 Sent To  
Notes
2009-11-13 08:30:32***FAILED***
  
 1. PLEASE PROVIDE THE PROPOSED SETBACKS FOR THE POOL
 EQUIPMENT. NOTE THAT IT MAY NOT BE CLOSER THAN FOUR
 FEET TO THE PROPERTY LINE.
  
 PLEASE CONTACT KELLY FREEMAN, GIS PLANNER, AT
 561-822-1458 OR [email protected] WITH QUESTIONS.