2009-11-09 16:33:05 | MECHANICAL |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2009-11-10 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2009-11-10 |
Time |
13:53 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2009-11-10 |
Time |
13:53 |
Sent To |
|
|
Notes |
2009-11-10 13:56:24 | PROVISO | | 1) TEST AND BALANCE REPORT REQUIRED FOR FINAL | | INSPECTION | | 2) PLEASE REFER TO SECTION 507.2.1.1 OPERATIONS . THE | | ACTIVATION OF THE EXHAUST FAN SHALL OCCUR THROUGH AN | | INTERLOCK WITH THE COOKING APPLIANCES . | | 3) PLEASE REFER TO SECTION 805.1 MAKEUP AIR . FOR | | MECHANICAL MAKEUP AIR SYSTEMS THE EXHAUST AND MAKEUP | | AIR SYSTEMS SHALL BE ELECTRICALLY INTERLOCKED TO INSURE | | THAT MAKEUP AIR IS PROVIED WHENEVER THE EXHAUST SYSTEN | | IS IN OPERATION . | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
|