Plan Review Details - Permit 09110183
Plan Review Stops For Permit 09110183
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-12-21 Cont ID  
Sent By jwitmer Date 2009-12-21 Time 13:29 Rev Time 0.77
Received By jwitmer Date 2009-12-21 Time 13:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-07 Cont ID  
Sent By jwitmer Date 2009-12-07 Time 11:02 Rev Time 3.00
Received By jwitmer Date 2009-12-07 Time 08:05 Sent To  
Notes
2009-12-07 11:05:30BUILDING PLAN REVIEW
 PERMIT: 09110183
 ADD: 1901 N FLAGLER DR
 CONT: LCI CONSTRUCTION
 TEL: (561)307-4951
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 DEC. 07/2009
  
 1) A1.1DETAIL# 03 AT THE TOP AND BOTTOM OF THE SHEET
 THE PLANS INDICATE STAIRS WITH A NOTE TO PROVIDE A NEW
 POWDER COAT HANDRAIL (SINGULAR) PLEASE REVIEW SECTION
 1009.10., REQUIRED ON BOTH SIDES OF THE STAIRS, THEY DO
 NOT MEET ANY OF THE EXCEPTIONS. PLANS DO NOT HAVE
 DETAILS PLEASE ALSO REVIEW SECTION 1012.5, REQUIRED
 HANDRAIL EXTENSIONS.
  
 2) A1.1 DETAIL# 3 SAME DETAIL THE BOTTOM SET OF STAIRS
 INDICATES THE USE OF A NEW CURTAIN THAT WILL HIDE THE
 STAIRS, ALTHOUGH IT IS NOT A DOOR THE CURTAIN STILL
 WILL BLOCK YOUR VIEW AS A DOOR WOULD PLEASE REVIEW
 SECTION 1008.1.5 FOR BOTH THE STAIR CONDITIONS.
  
 3) SHEET A1.1 AND SHEET A5.1DETAIL# 2 INDICATES NEW
 TRAVERTINE TO BE LAMINATED TO THE TOP OF THE EXISTING
 STAIRS AND THE FLOOR FINISH TO REMAIN AS IS ON THE
 EXISTING STAGE, PLEASE PROVIDE THE RISER OF EACH OF THE
 STEPS AND REVIEW SECTION 1009.3 DIMENSIONAL UNIFORMITY,
 THE RISERS SHALL DEVIATE NO MORE THAN 0.375 OF AN INCH.
  
 4A) SHEET A5.1 INDICATES THE USE OF ARMSTRONG
 SERPENTINA CURVED CLOUD SYSTEM, PLEASE PROVIDE THE
 MANUFACTURER???S SPECIFICATIONS. ADDITIONAL INFORMATION
 IS REQUIRED 106.1.2. FOR THE INSTALLATION OF CEILING
 TILE. 803.9.1.1.
  
 4B) ARMSTRONG SERPENTINA CURVED CLOUD SYSTEM: 803.9.1
 MATERIALS AND INSTALLATION. ACOUSTICAL MATERIALS
 COMPLYING WITH THE INTERIOR FINISH REQUIREMENTS OF
 SECTION 803 SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S RECOMMENDATIONS AND APPLICABLE
 PROVISIONS FOR APPLYING INTERIOR FINISH.
  
  
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2010-01-13 Cont ID  
Sent By dpalmer Date 2010-01-13 Time 12:03 Rev Time 0.00
Received By dpalmer Date 2010-01-13 Time 12:03 Sent To  
Notes
2010-01-13 12:04:53PLANS REDLINED,
  
  
 ALL HORN, STROBE, PULL STATIONS ARE REQUIRED TO MEET
 FBC 11-4.28.1,.2 AND .3. MIN CD LEVELS FOR STORBES ARE
 75 CD, MIN DB LEVELS AND HEIGHTS ARE TO BE REVISED ON
 PLANS BEFORE ROUGH ALONG WITH ANY OTHER CHANGES.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2010-01-06 Cont ID  
Sent By dpalmer Date 2010-01-06 Time 16:56 Rev Time 0.00
Received By dpalmer Date 2010-01-06 Time 16:56 Sent To  
Notes
2010-01-06 16:57:43** CALCULATIONS MAILED STANDARD MAIL 12/22. THESE WERE
 LOCATED IN OFFICE WITH NO DATE STAMP WHEN RECEIVED.
 LOCATED ON 1/4/10
  
 ** DENIED **
  
  
 1) NOTE: THE NEW SUBMITTED ENERGY PERFORMANCE
 CALCULATIONS ARE NOT COORDINATING WITH PLANS. A CALL
 WAS PLACED TO ENGINEERING FIRM TO GO OVER COMMENTS,
 FIXTURES ETC.
 THERE ARE FIXTURES WHICH ARE NOT ON THE INPUT DATA
 REPORT.
 TRACK LIGHTING IS REQUIRED TO BE FIGURED AT THE WATTAGE
 PER EACH FIXTURE TIMES THE NUMBER OF FIXTURES OR 30VA
 PER FT (WHICHEVER IS GREATER). PLEASE SEE 13-415.AB.5,
 AND APPENDIX B4.1.1
 ** SOME FIXTURES SUCH AS S TYPE NEED TO BE INCLUDED.
 ** THE W FIXTURES ARE NOT LISTED ON THE FIXTURE LEGEND
 AS ANY SPECIFIC WATTAGE OR FIXTURE. BASED ON
 CONVERSATION WITH ENGINEER PLANS CAN BE REDLINED BY
 THIS OFFICE FOR A MAXIMUM WATTAGE FIXTURE HOWEVER THAT
 WATTAGE NEEDS TO BE INCLUDED ON THE IDR.
 ** THE T FIXTURES WHICH DO NOT FALL UNDER EXEMPTIONS IN
 13-415.AB.5 NEED TO BE INCLUDED. ( T3).
 ** THERE ARE NO P1 FIXTURES LISTED.
 ** THERE ARE NO P2 FIXTURES LISTED.
 ** ANY S OR S2 FIXTURES WHICH ARE ON FOR GENERAL
 LIGHTING AND ALSO COME ON FOR BATTERY BACK ARE REQUIRED
 TO BE INCLUDED. ONLY FIXTURES WHICH DO COME ON FOR ANY
 GENERAL LIGHTING PURPOSE AND ONLY COME ON DURING POWER
 FAILURE ARE NOT INCLUDED.
 ** D FIXTURES?
 ** PLEASE REVISE METHOD OF CONTROLS. THE IDR SHOWS
 MANUAL ON/OFF WHEN PLANS INDICATE AUTOMATED LIGHTING
 CONTROLS. ( THIS WOULD BE REDLINED IF ONLY ITEM.
 ** PLEASE EXPLAIN THE 32-200W METAL HALIDES SHOWN ON
 THE IDR AND THE 4-250 METAL HALIDES SHOWN ON THE IDR.
 WHERE ARE THESE FIXTURES ON THE PLANS?
  
  
 PLEASE CALL TO GO OVER FOR ANY QUESTIONS. THE
 ALLOWANCES UNDER THE 2007 FBC W/ 2009 SUPPLEMENTS HAVE
 COMPLETELY CHANGED FROM PREVIOUS CODES.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-12-22 Cont ID  
Sent By dpalmer Date 2009-12-22 Time 15:19 Rev Time 0.00
Received By dpalmer Date 2009-12-22 Time 15:19 Sent To  
Notes
2009-12-22 15:21:56REVIEW ON HOLD WAITING FOR PERFORMANCE CALCULATIONS.
 SPOKE TO DESIGN TEAM, NEW CALCS ARE BEING DONE AND WILL
 BE SUBMITTED.
 CALLED CONTRACTOR AND THEY ARE AWARE THAT NEW CALCS ARE
 TO BE SUBMITTED. ALSO AWARE THE PLANS WHICH ARE DONE IN
 DATED ORDER ARE BEING PASSED OVER FOR REVIEW. REVIEW
 WILL BE DONE ONCE CALCULATIONS ARE SUBMITTED.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-01 Cont ID  
Sent By dpalmer Date 2009-12-01 Time 16:10 Rev Time 0.00
Received By dpalmer Date 2009-12-01 Time 16:10 Sent To  
Notes
2009-12-01 16:11:08** DENIED **
  
 1) NOTE: PLANS STATE 2007 FBC ON COVER SHEET, HOWEVER
 BASED ON REVISED 2007 FBC WHICH NOW HAS TWO REVISED
 SUPPLEMENTS, CODES FOR DESIGN SHOULD BE SPECIFIC ON
 PLANS.
 THE 2008 NFPA-70 WAS ADOPTED ON OCTOBER 1ST,2009.
 PLEASE ADJUST DESIGNS FOR NEW REVISED CODES.
 2006 NFPA-101
 2002 NFPA-72
 2006 NFPA-1 ( TO BE NOTED BY FIRE REVIEW
 2007 FLORIDA FIRE PREVENTION CODE. ( TO BE NOTED BY
 FIRE REVIEW)
  
 PER
 FAC 69A-60..03,.004, 69A-13.012
  
 2) NOTE: PLANS SUBMITTED CONTAIN TWO SETS OF ELECTRICAL
 PLANS IN ONE OF THE SETS AND ONE SET IN THE OTHER. WE
 ONLY NEED TWO TOTAL SETS.
 ** PLEASE ALSO KNOW THE ELECTRICAL PLANS DO NOT CONTAIN
 A SYMBOL LEGEND THEREFORE SOME COMMENTS BELOW ARE
 DERIVED BECAUSE ELECTRICAL DEVICES ARE NOT CLEAR. SEE
 NOTE # 5.
  
 3) NOTE: MINIMUM COMPLIANCE WITH FLORIDA BUILDING CODE
 CHAPTER 13 HAS NOT BEEN MET. THE SUBMITTED FORM C FROM
 THE 2004 FBC MAY NOT BE USED.
 THE 2004 FLORIDA BUILDING CODE HAS NOT BEEN ADOPTED IN
 THE STATE OF FLORIDA SINCE MARCH 1ST, 2009. PLEASE KNOW
 AT THAT TIME THERE WAS 2009 SUPPLEMENTS TO THE 2007
 FBC. PLEASE ALSO KNOW THAT AS OF OCTOBER 1ST, 2009 THE
 FBC WAS ONCE AGAIN REVISED WITH SEVERAL ITEMS IN
 CHAPTER 13. PLEASE SEE PERFORMANCE METHODS FROM THE
 2007 FBC W/2009 SUPPLEMENTS.
  
 PLEASE SEE 13-101.1.3, 13-101.4.1, 13-400.0.B,
 13-400.0.B.4, 13-400.2.
  
 PLEASE SEE 13-415.AB.5 FOR INTERIOR LIGHTING
 PERFORMANCE CALCULATIONS REQUIRED. PLEASE KEEP IN MIND
 IF USING A FORM FROM THE FLORIDA BUILDING CODE FOR
 SPACE BY SPACE, THEN ONE FORM IS REQUIRED FOR EACH
 SPACE. IF USING FLA-COM THEN PLEASE BE SURE TO COMPLETE
 THE INPUT DATA REPORT WHICH IS PART OF THE FLA COM
 PROGRAM.
  
 PLEASE SEE 13-415.AB.2 FOR ANY EXTERIOR ALLOWANCES.
  
 4) NOTE: THE FORM C WAS SIGNED, BUT NOT SEALED BY THE
 RESPONSIBLE DESIGNER OF RECORD. PLEASE BE SURE WHEN
 SUBMITTING NEW ENERGY COMPLIANCE FORMS THAT THE
 SIGNATURE, DATE AND SEALS AS REQUIRED PER FBC 13-103.1,
 FAC 61G15-23.002, FS 471.025
  
 5) NOTE: PLEASE SUBMIT AND SHOW MORE INFORMATION
 SHOWING COMPLIANCE WITH FBC 13-415.AB.1.1,.1.2,.1.3 AND
 .1.4.
 PLANS INDICATE WHAT APPEARS TO BE A LIGHTING CONTROL
 SYSTEM WHICH IS OK, HOWEVER BASED ON SECTIONS GIVEN THE
 SEPARATE SPACES ON PLANS DO NOT COMPLY. SEPARATE SPACES
 ON PLANS SHOW WHAT WOULD BE STANDARD SINGLE POLE
 SWITCHES. IF THIS IS THE CASE THEY MUST MEET
 13-415.AB.1.1 AND .1.2 FOR SEPARATE SPACE UNDER
 AUTOMATED CONTROLS AND OVER RIDES OF SYSTEM. THERE ARE
 OTHER CODE ACCEPTABLE OPTIONS AND THESE MAY BE GONE
 OVER BY CONTACTING THIS REVIEWER.
 PLEASE BE SURE TO SHOW COMPLIANCE AND TIMES FOR MAXIMUM
 OVER RIDES OF THE AUTOMATED LIGHTING CONTROLS. REVISE
 LIGHTING CONTROLS AS REQUIRED.
  
 6) NOTE: PLEASE SEE SECTION 13-415.AB.1.4 FOR EXTERIOR
 LIGHTING. THE CODE ALLOWS TWO METHODS OF CONTROLS.
 PLEASE INDICATE WHICH ONE WILL BE DONE IF NOT EXISTING.
 SEE COMMENT NUMBER 7 AS THIS WILL BE RELEVANT TO THIS
 COMMENT.
  
 7) NOTE: PLEASE INDICATE MINIMUM LIGHTING FOR EGRESS
 PATHS TO THE PUBLIC RIGHT OF WAY UNDER NORMAL AND
 EMERGENCY CONDITIONS. PLEASE SEE NFPA-101
 7.8.1.3,7.9.1.1,.1.2.
 IF LIGHTING IS EXISTING, PLEASE SHOW. PLEASE ALSO SEE
 MINIMUM CODE REQUIRED FOR STAIRS AND OTHER EXIT PATHS
 TO RIGHT OF WAY UNDER SOME SORT OF EMERGENCY BACK UP
 POWER MEETING NFPA-70 700.12 AND NFPA-101 SECTIONS.
 IF THERE IS EXISTING EMERGENCY EGRESS LIGHTING MEETING
 MINIMUM LEVELS UNDER NORMAL AND EMERGENCY (POWER
 OUTAGE) CONDITIONS, PLEASE SHOW.
 IF THERE IS NO EXISTING LIGHTING MEETING MINIMUMS FOR
 LIFE SAFETY PLEASE SHOW NEW AND CIRCUIT PER 700.12F.
 (SEE COMMENT #8)
 PLEASE ALSO SEE COMMENT #6 ABOVE WITH RESPECT TO
 LIGHTING CONTROLS FOR EXTERIOR LIGHTS.
  
 8) NOTE: CIRCUITING OF EMERGENCY LIGHTING AND EXIT
 LIGHTS SHALL BE CIRCUITED PER 700.12F. PLANS CONTAIN A
 NOTE#2 WHICH MENTIONS TO WIRED TO UN-SWITCHED LEG OF
 D-20.
 THIS IS NOT PERMITTED AS D-20 ON REVISED PANEL D IS
 ACTUALLY IDENTIFIED AS A RECEPTACLE CIRCUIT. PLEASE SEE
 CODE SECTION GIVEN WHICH REQUIRES EMERGENCY AND EXIT
 LIGHTS TO BE CIRCUITED TO THE HOT SIDE OF THE LOCAL
 LIGHTING BRANCH CIRCUIT IN ANY ONE AREA. BASED ON THE
 PLANS MANY AREAS DO NOT MEET THE EXCEPTION IN 700.12F.
 PLEASE REVISE ALL CIRCUITING.
  
 9) NOTE: IT IS CONFUSING HOW THE SUBMITTED EXISTING
 PANEL *D* INDICATE MOST OF THE EXISTING CIRCUITS AS
 *SPARE* THEN THE REVISED PANEL SCHEDULE *D* INDICATES
 MANY OF THOSE SAME CIRCUITS SHOWN AS * EXISTING SPARE*
 NOW AS *EXISTING RECEPTACLES* ETC. PLEASE SPECIFIC
 CIRCUITS REVISED PANEL D11-19 AND D8-20. HOW CAN THESE
 BE EXISTING CIRCUITS WHEN EXISTING PANEL SCHEDULE SHOWS
 ALL OF THESE SAME SPACES AS *SPARE* SPACES?
 408.4
  
 10) NOTE: PLEASE SEE SHEET E-2 SECOND FLOOR DETAIL.
 THERE ARE SQUARE/RECTANGLE BOXES ON THE WEST WALL
 OUTSIDE AREAS 1-002 AND 1-202. WHAT ARE THESE?
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
 408.4,310.16, 240.4 ETC GIVEN AS GENERAL SECTIONS FOR
 WIRING, OVERCURRENT PROTECTION AND PANEL SCHEDULES AS
 THESE ARE NOT CLEAR AT THIS TIME.
  
 11) NOTE: PLEASE VERIFY MAXIMUM OCP FOR CONDENSING
 UNITS. THIS CAN BE A PROVISO ITEM TO BE REVISED IF NOT
 KNOWN AT THIS TIME.
  
 12) NOTE: PLEASE INDICATE HORN, STROBE LEVELS FOR FIRE
 ALARM DEVICES PER FBC 11-4.28.1,.2 AND.3. PLANS SHOULD
 ALSO INDICATE MINIMUM HEIGHTS AND LOCATIONS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-01-04 Cont ID  
Sent By mawillia Date 2010-01-04 Time 14:49 Rev Time 0.00
Received By mawillia Date 2010-01-04 Time 14:14 Sent To  
Notes
2010-01-04 14:48:58*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS LS1.1, A2.1, A5.1, FP-1, FP-2,
 E-2, AND E-4 WERE STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-12-04 Cont ID  
Sent By mawillia Date 2009-12-04 Time 12:37 Rev Time 0.00
Received By mawillia Date 2009-12-04 Time 12:17 Sent To  
Notes
2009-12-04 12:37:48*****PARTIAL APPROVAL*****
  
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 OTHER TRADE REVIEWER'S COMMENTS AS WELL AS THE
 FOLLOWING FIRE COMMENTS HAVE BEEN ADDRESSED:
  
 1. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE
 BASED ON NFPA 101, LIFE SAFETY CODE, 2006 EDITION AND
 NFPA 1, UNIFORM FIRE CODE, 2006 EDITION SHALL BE
 REFERENCED. ADD TO CODE SECTION
  
 2. SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW
 ACOUSTICAL CEILING IN TERMS OF CLASS A, CLASS B, OR
 CLASS C. ADD TO THE APPROPIATE PLAN SHEET
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 L;ETTER INDICATING WHERE THE ABOVE FIRE COMMENTS WERE
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-16 Cont ID  
Sent By lmartine Date 2009-12-15 Time 19:15 Rev Time 0.00
Received By lmartine Date 2009-12-15 Time 19:14 Sent To  
Notes
2009-12-16 19:15:25C--27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-07 Cont ID  
Sent By jwitmer Date 2009-12-07 Time 11:04 Rev Time 0.00
Received By jwitmer Date 2009-11-05 Time 15:44 Sent To  
Notes
2009-11-16 15:49:56C--5
 PLAN PROCESSED ON 11/16/09

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-12-07 Cont ID  
Sent By jwitmer Date 2009-12-07 Time 11:04 Rev Time 0.00
Received By jwitmer Date 2009-12-07 Time 11:03 Sent To  
Notes
2009-12-07 11:04:24PASSED PER RON REGUEIRO'S STAMPED PLANS AND PASSED ON
 COMMERCIAL SPREAD SHEET C-5.

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-11-18 Cont ID  
Sent By kstevens Date 2009-11-18 Time 15:15 Rev Time 0.00
Received By kstevens Date 2009-11-18 Time 15:15 Sent To  
Notes
2009-11-18 15:16:17NO PLUMBING WORK/PLANS SUBMITTED OR INDICATED ON THE
 APPLICATION.

Review Stop Z ZONING
Rev No 1 Status N Date 2009-11-19 Cont ID  
Sent By kdfreema Date 2009-11-19 Time 08:45 Rev Time 0.00
Received By kdfreema Date 2009-11-19 Time 08:45 Sent To  
Notes
***NONE***