Plan Review Details - Permit 09110126
Plan Review Stops For Permit 09110126 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2009-11-16 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2009-11-16 |
Time |
11:34 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2009-11-16 |
Time |
11:34 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2009-11-06 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2009-11-06 |
Time |
06:38 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2009-11-06 |
Time |
06:02 |
Sent To |
|
|
Notes |
2009-11-06 06:39:17 | TO LUIS DESSK FOR HAND ROUTING./WRT |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2009-11-16 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-11-16 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-11-16 |
Time |
15:06 |
Sent To |
|
|
Notes |
2009-11-16 15:16:17 | *****APPROVED***** | | | | | | THE FIRE ALARM PLAN (FA 0.1 & FA 1.0) FIRE-STAMPED | | ACCORDINGLY; READY FOR PERMIT ISSUANCE. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2009-11-09 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-11-09 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-11-09 |
Time |
09:37 |
Sent To |
|
|
Notes |
2009-11-09 10:36:46 | *****DENIED***** | | | | | | 1. THE SYMBOL FOR DEVICES PS 1-1-1 AND PS 1-3-1 DO NOT | | CORRELATE AS INDICATED ON FA 0.1 AND FA 1.0 SHEETS | | | | 2. ON SHEET FA 0.1, CORRELATE FIRE ALARM DEVICE COUNT | | INDICATED IN THE FIRE ALARM RISER DIAGRAM WITH THAT | | INDICATED IN THE NOTIFICATION APPLIANCE CIRCUIT | | CALCULATIONS FOR NEW REMOTE POWER SUPPLY #1 . | | | | 3. ON SHEET FA 1.0 (JUST ABOVE THE FIRE ALARM LEGEND) | | THERE ARE THREE BROKEN RECTANGULAR BOXES FROM LEFT TO | | RIGHT "C", "B", "A" ; HOWEVER THE SHELL LAYOUT FOR THE | | TENANT SPACES FROM LEFT TO RIGHT ARE SHOWN AS "A", "C", | | "B" . PLEASE CLARIFY AS TO WHAT THESE REPRESENT. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2009-11-09 |
Time |
|
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2009-11-05 |
Time |
16:40 |
Sent To |
|
|
Notes |
2009-11-05 16:41:11 | *****************EXPEDITED******************* | | GAVE TO BILL |
|
|
|