Plan Review Details - Permit 09110081
Plan Review Stops For Permit 09110081
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-01-07 Cont ID  
Sent By dpalmer Date 2010-01-07 Time 15:37 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2010-01-07 15:38:09OK PER JW, ONLY NEEDED PBC STAMPS/REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-11-09 Cont ID  
Sent By jwitmer Date 2009-11-09 Time 15:49 Rev Time 1.50
Received By jwitmer Date 2009-11-09 Time 14:34 Sent To  
Notes
2009-11-09 16:09:52BUILDING PLAN REVIEW
 PERMIT: 09110081
 ADD: 10545 LA STRADA
 CONT: ANDREA CONSTRUCTION
 TEL: (561)358-4797
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 NOTE : WE HAVE PROVIDED (2) COPIES OF THE SLIDING GLASS
 DOOR PRODUCT APPROVAL AND STORM SHUTTER APPROVALS FROM
 THE ORIGINAL BUILDING PERMIT.
  
 1) PLEASE UPDATE THE NEW DOOR (11) SHUTTER PORTION OF
 THE STORM SHUTTER SCHEDULE. 1609.1.4/ 1714.5
  
 2) THE NEW EXTERIOR DOOR WILL ALSO NEED (2) PRODUCT
 APPROVAL, 1609.1.4. 106.3.3 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 3) PLANS CURRENTLY HAVE A WALL SECTION TYPICAL A-A,
 PLEASE SEE THIS SECTION IS FOR A MASONRY WALL NOT A
 SECTION FOR A WINDOW OR SLIDING GLASS DOOR, IN BOTH
 CASES THE GREAT ROOM AND MASTER BEDROOM HAVE A CEILING
 HEIGHT OF 10'-0" WHERE AS THE SLIDDING GLASS DOOR IS A
 8'-0" TALL UNIT, IT WOULD APPEAR THAT A LINTEL, A
 COURSE OF COMMON BLOCK AND A COURSE OF U-BLOCK WOULD BE
 REQUIRED FOR THE GREAT ROOM OPENING, IT WOULD APPEAR
 THE SAME SITUATION WILL OCCUR OVER TTHE NEW 3'X8' SWING
 DOOR.
  
 4) THE PLANS ALSO DO NOT INDICATE HOW THE NEW BLOCK
 WALL WILL TIE INTO THE TRUSS OR ROOFING SYSTEM FOR
 LATERAL LOADS. SECTION A-A INDICATES EXISTING TRUSS
 ANCHORS?
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-01-07 Cont ID  
Sent By dpalmer Date 2010-01-07 Time 15:39 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2010-01-07 15:39:48OK, PER JW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-11-09 Cont ID  
Sent By jwitmer Date 2009-11-09 Time 16:10 Rev Time 1.00
Received By jwitmer Date 2009-11-09 Time 16:10 Sent To  
Notes
2009-11-09 16:12:31ELECTRICAL PLAN REVIEW
 PERMIT: 09110081
 ADD: 10545 LA STRADA
 CONT: ANDREA CONSTRUCTION
 TEL: (561)358-4797
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 2008 NEC
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE (2) NEW OUTLETS THAT ARE BEING INSTALLED IN THE
 GREAT ROOM ADDITION WILL NEED TO BE ON THEIR OWN ARC
 FAULT PROTECTION CIRCUIT.
  
 2008 NEC- NEW ARC-FAULT PROTECTION IS NOW REQUIRED IN
 RESIDENTIAL OCCUPANCIES ON ALL 15 AND 20 AMP BRANCH
 CIRCUITS THAT ARE NOT ALREADY REQUIRED TO BE PROTECTED
 BY GROUND FAULT INTERRUPTERS CIRCUITS (GFCI) OR OVER
 120 VOLTS 2110.12(B)
  
 2008 NEC-NEW MULTI-WIRE BRANCH CIRCUITS THAT SHARE A
 COMMON GROUND CONDUCTOR (NEUTRAL) MUST SHARE A COMMON
 DISCONNECT OR THE NEUTRALS MUST BE DISCONNECTED AT THE
 SAME TIME 210.4(B).
  
 2) PLANS FAIL TO INDICATE COMPLIANCE WITH SECTION
 210.70 (2)(B) EXTERIOR LIGHT AND SWITCH LOCATIONS, THIS
 APPLIES FOR BOTH THE NEW ADDITION TO THE GREAT ROOM AS
 WELL AS THE NEW MASTER BEDROOM EXTERIOR DOORWAY.
  
 3) IN THE MASTER BEDROOM IT ALSO APPEARS TO BE A NEW
 CEILING JUNCTION BOX? 106.1.2 ADDITONAL INFORMATION
 REQUIRED.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
 SFP-100
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-09 Cont ID  
Sent By jwitmer Date 2009-12-09 Time 13:09 Rev Time 0.00
Received By jwitmer Date 2009-12-09 Time 13:09 Sent To  
Notes
2009-12-09 13:10:13SENT TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-11-30 Time   Rev Time 0.00
Received By kstevens Date 2009-11-05 Time 10:25 Sent To  
Notes
2009-11-05 10:47:45SENT TO R-23.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2010-01-07 Cont ID  
Sent By dpalmer Date 2010-01-07 Time 15:36 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2010-01-07 15:36:32NO FEE PER PBC

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-11-09 Cont ID  
Sent By jwitmer Date 2009-11-09 Time 15:41 Rev Time 0.22
Received By jwitmer Date 2009-11-09 Time 15:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-11-09 Cont ID  
Sent By jwitmer Date 2009-11-09 Time 13:53 Rev Time 0.00
Received By jwitmer Date 2009-11-09 Time 13:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2009-12-16 Cont ID  
Sent By lfranco Date 2009-12-16 Time 11:36 Rev Time 0.00
Received By lfranco Date 2009-12-16 Time 11:36 Sent To B
Notes
2009-12-16 11:36:56PLANNING AND ZONING: **** RE-STAMP SHEET NO. 1 ****

Review Stop Z ZONING
Rev No 1 Status P Date 2009-11-30 Cont ID  
Sent By lfranco Date 2009-11-30 Time 19:13 Rev Time 0.00
Received By lfranco Date 2009-11-30 Time 19:13 Sent To I
Notes
***NONE***