Plan Review Details - Permit 09110048
Plan Review Stops For Permit 09110048
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2010-02-24 Cont ID  
Sent By jgomez Date 2010-02-24 Time 10:06 Rev Time 0.00
Received By jgomez Date 2010-02-24 Time 10:06 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2010-02-04 Cont ID  
Sent By jgomez Date 2010-02-04 Time 10:31 Rev Time 0.00
Received By jgomez Date 2010-02-04 Time 10:31 Sent To PC
Notes
2010-02-04 10:42:13SIGN, BUILDING REVIEW THIRD CHECKLIST CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
  
 1- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. VALUATION TO
 INCLUDE ALL LABOR, MATERIALS AND ENGINEERING FEES.
 PROVIDE COPY OF NOTARIZED CONTRACTS SIGNED BY ALL THE
 PARTIES INVOLVED (REPEAT COMMENT. COPY OF CONTRACT
 SUBMITTED IS ONLY FOR THE INSTALLATION OF THE SIGN.
 NEED TO PROVIDE THE COST FOR THE SIGN FABRICATION
 INCLUDING THE ENGINEERING. VALUATION IS FOR THE OVERALL
 COST OF FABRICATION AND INSTALLATION OF THE SIGN).
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE. (THIS MAY BE PROVIDED AT TIME OF
 PERMIT PICK UP).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-12-30 Cont ID  
Sent By jgomez Date 2009-12-30 Time 11:07 Rev Time 0.00
Received By jgomez Date 2009-12-30 Time 11:07 Sent To PC
Notes
2009-12-30 11:10:03SIGN, BUILDING REVIEW SECOND CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. VALUATION TO
 INCLUDE ALL LABOR, MATERIALS AND ENGINEERING FEES.
 PROVIDE COPY OF NOTARIZED CONTRACTS SIGNED BY ALL THE
 PARTIES INVOLVED (REPEAT COMMENT. NOT ADDRESSED AT
 ALL).
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE. (THIS MAY BE PROVIDED AT TIME OF
 PERMIT PICK UP).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-11-24 Cont ID  
Sent By jgomez Date 2009-11-24 Time 09:34 Rev Time 0.00
Received By jgomez Date 2009-11-24 Time 09:05 Sent To PC
Notes
2009-11-24 09:46:20SIGN, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- ENGINEERING DRAWINGS ARE MISSING THE FOLLOWING:
 A) ATTACHMENT OF BRACKET TO THE 4" ALUMINUM TUBE.
 B) ATTACHMENT OF 4" ALUMINUM TUBE TO THE SIGN BOX.
 C) COMPLETE INFORMATION FOR CONSTRUCTION OF SIGN. THERE
 IS NOT INFORMATION SUBMITTED. PROVIDE COMPLETE
 SPECIFICATIONS AND DETAILS FOR SIGN CONSTRUCTION TO
 SHOW COMPLIANCE WITH THE DESIGN PRESSURES OF SECTION
 1609 FBC 2007.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. VALUATION TO
 INCLUDE ALL LABOR, MATERIALS AND ENGINEERING FEES.
 PROVIDE COPIES OF SIGNED CONTRACTS.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-12-29 Cont ID  
Sent By btrobaug Date 2009-12-29 Time 12:35 Rev Time 0.00
Received By btrobaug Date 2009-12-29 Time 12:21 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-11-19 Cont ID  
Sent By btrobaug Date 2009-11-19 Time 11:57 Rev Time 0.00
Received By btrobaug Date 2009-11-19 Time 11:43 Sent To B
Notes
2009-11-19 11:56:57 
  
  
  
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 1} A DISCONNECTING MEANS PER 600.6 FOR THE CIRCUITS
 REQUIRED BY 600.5 SHOULD BE LOCATED OR INDICATED ON THE
 PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2010-02-11 Cont ID  
Sent By kstevens Date 2010-02-11 Time 10:37 Rev Time 0.00
Received By kstevens Date 2010-02-11 Time 10:37 Sent To  
Notes
2010-02-11 10:38:06SENT TO ZONING.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-01-27 Cont ID  
Sent By lmartine Date 2010-01-26 Time 08:31 Rev Time 0.00
Received By lmartine Date 2010-01-26 Time 08:31 Sent To  
Notes
2010-01-27 08:32:50IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-23 Cont ID  
Sent By jgomez Date 2009-12-23 Time 14:42 Rev Time 0.00
Received By jgomez Date 2009-12-23 Time 14:42 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-11-24 Cont ID  
Sent By jgomez Date 2009-11-24 Time 09:46 Rev Time 0.00
Received By jgomez Date 2009-11-17 Time 14:38 Sent To  
Notes
2009-11-17 14:38:17TO ELECTRIC
  
2009-11-04 07:55:53INCOMING TO ZONING

Review Stop Z ZONING
Rev No 4 Status P Date 2010-02-19 Cont ID  
Sent By lmartine Date 2010-02-12 Time 15:17 Rev Time 0.00
Received By lmartine Date 2010-02-12 Time 15:16 Sent To  
Notes
2010-02-19 15:17:48SEE APPROVAL STAMP AND SIGNATURE ON PLANS

Review Stop Z ZONING
Rev No 3 Status F Date 2010-01-29 Cont ID  
Sent By aaponte Date 2010-01-29 Time 11:46 Rev Time 0.00
Received By aaponte Date 2010-01-29 Time 11:46 Sent To  
Notes
2010-01-29 11:51:07SIGN IS PROJECTING MORE THAN THE THREE FEET PERMITTED.

Review Stop Z ZONING
Rev No 2 Status F Date 2009-12-24 Cont ID  
Sent By aaponte Date 2009-12-24 Time 09:48 Rev Time 0.00
Received By aaponte Date 2009-12-24 Time 09:48 Sent To  
Notes
2009-12-24 10:05:03THIS PERMIT WAS ORIGINALLY SUBMITTED FOR A VERTICAL
 SIGN. SOME COMMENTS ON THE PREVIOUS REVIEW HAVE NOT
 BEEN ADDRESSED.
 PLEASE INDICATE THE TOTAL PROJECTION OF THE SIGN FROM
 THE BUILDING FACE TO THE EXTERIOR FACE OF THE SIGN.
 PLEASE INDICATE THE LOCATION OF THE SIGN ON THE
 BUILDING FACADE. SIGN SHALL BE A MINIMUM OF 2 FEET FROM
 THE END OF THE BUILDING.
 PLEASE INDICATE SIGN CONTENT.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-11-09 Cont ID  
Sent By aaponte Date 2009-11-09 Time 15:57 Rev Time 0.00
Received By aaponte Date 2009-11-09 Time 15:57 Sent To  
Notes
2009-11-09 16:03:26PLEASE INDICATE THE TOTAL DIMENSION OF THE SIGN AND
 BRAQUET PROJECTING FROM THE FACADE.
 PLEASE INDICATE THE WIDTH OF THE SIGN.
 VERTICAL SIGNS SHALL BE SET BACK A MINIMUM OF 2 FEET
 FROM THE END OF THE BUILDING.