Plan Review Details - Permit 09110014
Plan Review Stops For Permit 09110014
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-01-19 Cont ID  
Sent By jgomez Date 2010-01-19 Time 15:52 Rev Time 0.00
Received By jgomez Date 2010-01-19 Time 15:52 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-11-23 Cont ID  
Sent By jgomez Date 2009-11-23 Time 16:50 Rev Time 0.00
Received By jgomez Date 2009-11-23 Time 16:50 Sent To PC
Notes
2009-11-23 16:50:49SIGN BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- DETAILS NEED TO SPECIFY HOW ARE THE LETTERS ATTACHED
 TO THE RACEWAY TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. 1609 OF FBC 2007.
 ALSO, CLARIFY IF THE RACEWAY IS GOING TO BE IN THE
 MIDDLE OF THE LETTER AS SHOWN ON THE LETTER SECTION #2
 OR IS IT GOING TO BE INSTALLED AT THE BOTTOM OF THE
 LETTERS AS SHOWN ON THE SIGN ELEVATION. REVISE AS
 REQUIRED TO MATCH.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. NEED TO UPDATE
 VALUATION. PROVIDE COPY OF SIGNED CONTRACT.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-01-14 Cont ID  
Sent By btrobaug Date 2010-01-14 Time 09:51 Rev Time 0.00
Received By btrobaug Date 2010-01-14 Time 09:51 Sent To B
Notes
2010-01-14 09:52:49TO JULIO./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-11-03 Cont ID  
Sent By btrobaug Date 2009-11-03 Time 08:32 Rev Time 0.00
Received By btrobaug Date 2009-11-03 Time 08:11 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-23 Cont ID  
Sent By jgomez Date 2009-12-23 Time 14:35 Rev Time 0.00
Received By jgomez Date 2009-12-23 Time 14:35 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-11-23 Cont ID  
Sent By jgomez Date 2009-11-23 Time 16:50 Rev Time 0.00
Received By jgomez Date 2009-11-03 Time 08:11 Sent To  
Notes
2009-11-03 08:33:44TO ELECTRIC, BT./WRT,

Review Stop Z ZONING
Rev No 2 Status P Date 2010-01-14 Cont ID  
Sent By lfranco Date 2010-01-11 Time 10:22 Rev Time 0.00
Received By lfranco Date 2010-01-11 Time 10:22 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-11-18 Cont ID  
Sent By lfranco Date 2009-11-18 Time 19:17 Rev Time 0.00
Received By lfranco Date 2009-11-18 Time 19:17 Sent To B
Notes
2009-11-18 19:30:21PLANNING AND ZONING: *** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THIS PROPERTY IS PART OF THE METROCENTRE COMMERCIAL
 PLANNED DEVELOPMENT ("CPD"), PROVIDE ALL EXISTING
 SIGNAGE FOR THIS BUILDING. PURSUANT TO THE ZONING CODE,
 SECTION 94-408 (D)(1) - WALL-MOUNTED, A MAXIMUM OF ONE
 SIGN FOR EACH INDIVIDUAL BUSINESS OCCUPANT OF THE
 BUILDING, PLUS TWO (2) ADDITIONAL SIGNS ARE ALLOWED,
 FOR A TOTAL OF THREE (3) WALL-MOUNTED SIGNS.
  
 PROVIDE ELEVATIONS SHOWING EXISTING SIGNAGE VS.
 PROPOSED WITH TOTAL SQUARE FOOTAGE AS ALLOWED BY THE
 SECTION 94-409. IF SIGNAGE HAS NEVER BEEN APPROVED AS
 PART OF THE SITE PLAN APPROVAL FOR THE BUILDING OR A
 MINOR AMENDMENT FOR THE SIGNAGE, THEN AN APPLICATION
 FOR A MINOR AMENDMENT TO THE CPD SHOWING THE PROPOSED
 SIGNAGE WILL BE REQUIRED TO BE FILED TO THE PLANNING
 AND ZONING DEPARTMENT AND APPROVED PRIOR TO THE
 BUILDING PERMIT BEING APPROVED. SEE
 HTTP://WWW.CITYOFWPB.COM/PLAN/INDEX.PHP, UNDER
 DEVELOPMENT APPLICATION FOR REQUIREMENTS OF A MINOR PD
 AMENDMENT.
  
 THE FOLLOWING, BUT NOT LIMITED TO THE FOLLOWING ITEMS
 SHALL BE SHOWN ON THE PLANS SUBMITTED:
  
 THE TOTAL SQUARE FOOTAGE OF ALL SIGNAGE SHALL BE SHOWN
 ON A SITE DATA IN ACCORDANCE WITH THE ZONING AND LAND
 DEVELOPMENT REGULATIONS ("ZLDR"). REFER TO THE ZLDR FOR
 SIGNAGE REGULATIONS, UNDER THE GENERAL COMMERCIAL (GC)
 ZONING DISTRICT. ADDITIONALLY, AN APPROVAL LETTER FROM
 THE METROCENTRE ARCHITECTURAL REVIEW BOARD SHALL BE
 SUBMITTED ALONG WITH THE MINOR PD AMENDMENT
 APPLICATION.
  
 3. PURSUANT TO THE ORDINANCE GOVERNING THE METROCENTRE
 CPD, AN APPROVAL LETTER FROM THE METROCENTRE
 ARCHITECTURAL REVIEW BOARD SHALL BE SUBMITTED. CONTACT:
 METROCENTRE ARCHITECTURAL BOARD CONTACT:
  
 CHARLES HALLIDAY
 561-842-8324
 561-712-5100
 EMAIL: [email protected]
  
 OR
  
 FELICIA MATULA
 561-242-9066
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  