Review Stop G GAS REVIEW
Rev No 1 Status P Date 2009-11-02 Cont ID  
Sent By kstevens Date 2009-11-02 Time 15:26 Rev Time 0.00
Received By kstevens Date 2009-11-02 Time 15:26 Sent To  
Notes
2009-11-02 15:29:36PER SECTION G2407.5.1, 50 CU FT REQUIRED FOR EACH 1,000
 BTU, 7,000 CU FT MINIMUM. COMBUSTION AIR IF LESS &
 REQUIRED PER SECTIONS G2407.5 OR G2407.6.