Plan Review Details - Permit 09100528
Plan Review Stops For Permit 09100528
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-12-21 Cont ID  
Sent By jwitmer Date 2009-12-17 Time 10:14 Rev Time 1.00
Received By jwitmer Date 2009-12-17 Time 10:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-11-05 Cont ID  
Sent By jwitmer Date 2009-11-05 Time 10:19 Rev Time 0.00
Received By jwitmer Date 2009-11-05 Time 10:00 Sent To  
Notes
2009-11-05 11:47:56BUILDING PLAN REVIEW
 PERMIT: 09100528
 ADD: 101 NORTHPOINT PARKWAY # 105
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) THE DESCRIPTION OF WORK IS A BIT CONFUSING AND MAY
 CREATE A PROBLEM FOR ONE OF THE TENANTS IN THE FUTURE.
 THE PLANS APPEAR TO BE CREATING TWO TENANCIES, POSSIBLY
 THREE. SHEET A3.0 INDICATES WHAT APPEARS TO BE NEW
 TENANT SEPERATION WALL LABELED WALL TYPE "B" TO THE
 DECK BETWEEN THE TWO TENANTS WHERE TTHE MAJOR PORTION
 OF THE WORK IS TO BE COMPLETED. AT THE LEFT HAND SIDE
 OF THE SHEET DOOR# 18 IS ALSO BEING CUT INTO A 1 HR
 FIRE RATED WALL, THE MECHANICAL PLANS ALSO
 INDICATE THIS WALL AS FIRE RATED WITH DAMPERS IN THE
 SUPPLY AND FIRE DAMPERS WITHIN THE RATED WALL FOR TTHE
 RETURN PLENUN. WITHOUT PERMIT ACTIVITY ATTACHED TO A
 NEW SUITE NUMBER THIS MAY BE AN ISSUE WHEN THE OCCUPANT
 GOES TO APPLY FOR A OCCUPATIONAL LICENSE AND NO
 ACTIVITY IS ASSOCATED WITH THIS TENANT SPACE OR SPACES.
 SHEET A2.0 DOES NOT ACTUALLY INDICATE WHAT SPACE IS
 SUITE 105. 106.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) SHEET A3.0 THE TENANT SEPERATION OR FIRE PARTITION
 BETWEEN THE TWO TENANCIES BUT THE M SHEETS ARE MISSING
 FIRE DAMPERS FOR THE TRUNK LINE AND THE PLANS DO NOT
 INDICATE ANY OPENINGS WITHIN THE WALL WITH FIRE DAMPERS
 FOR THE RETURN AIR SINCE THIS IS A PLENUN RETURN. SEE
 SECTION 716 OF THE FBC.
  
 3) PLEASE PROVIDE INFORMATION AS TO PENETRATION OF
 FIRRE RATED WALLS WILL BE COMPLIED WITH, SEE 712.3 &
 712.3.1.2.
  
 4) SHEET A3.0 INDICATES FUTURE WINDOW, IF WORK TO BE
 CONSIDERED UNDER THIS PERMIT, PLEASE PROVIDE
 ENGINEERING FOR COLUMNS AND LINTEL OR BEAM FOR WALL
 REINFORCEMENT, WILL ALSO NEED WIND DESIGN INFORMATION
 AS WELL AS BUCK DETAILS, IF USED, AND PRODUCT APPROVAL
 WITH GLAZING TYPE HIGHLIGHTED.
 1609.1.4/ RULE 9B-74(31)(B).
  
 5) SHEET A3.0 DOOR NUMBER 5 & 6 PLEASE SEE SECTION
 11-4.13.6. MANEUVERING CLEARENCES AT DOORS. MINIMUM 18"
 ON TTHE PULL SIDE OF DOOR.
  
 6) A3.0 NEW RAMP IN FRONT OF LOBBY 111, THERE ARE TWO
 ISSUES:
 6A) BOTTOM LANDING: 11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM
 OF EACH RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE.
  
 6B) 11.4.8.5. HANDRAILS: IF A RAMP HAS A RISE GREATER
 THAN 6" OR A HORIZONTAL PROJECTION GREATER THAN 72",
 THEN IT SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 7) SHEET A3.0 ROOM 109 IF THIS IS A TRUE "IT" ROOM IT
 WILL NEED TO MEET THE REQUIEMENTS OF NEC 645.4 PLEASE
 NOTE SECTION 5 REQUIRES A 1 HR RATING OF WALLS AND
 CEILING.
  
 8) SHEET A3.0 FINISH SCHEDULE INDICATES APAINT FINISH
 IN THE RESTROOM PLEASE SEE SECTION 1210.2 WALLS. WALLS
 WITHIN 2 FEET (610 MM) OF URINALS AND WATER CLOSETS
 SHALL HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A
 HEIGHT OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT
 FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH
 WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED
 BY MOISTURE.
  
 9) NEW OFFICE SPACE SINCE THIS IS A CHANGE IN OCCUPANCY
 PLANS WILL NEED TO BE SUBMITTED TO PALM BEACH COUNTY
 IMPACT FEE OFFICE FOR REVIEW.THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-12-22 Cont ID  
Sent By btrobaug Date 2009-12-22 Time 16:56 Rev Time 0.00
Received By btrobaug Date 2009-12-22 Time 16:38 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-11-23 Cont ID  
Sent By btrobaug Date 2009-11-23 Time 10:30 Rev Time 0.00
Received By btrobaug Date 2009-11-19 Time 16:08 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-12-21 Cont ID  
Sent By mawillia Date 2009-12-21 Time 14:28 Rev Time 0.00
Received By mawillia Date 2009-12-21 Time 13:58 Sent To  
Notes
2009-12-21 14:17:15*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED: PLAN SHEETS A3.0, A4.0, E1, E2, FS1, AND FS2
 WERE STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-11-19 Cont ID  
Sent By mawillia Date 2009-11-19 Time 09:51 Rev Time 0.00
Received By mawillia Date 2009-11-19 Time 08:52 Sent To  
Notes
2009-11-19 09:51:35*****DENIED*****
  
  
 1. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED, NOT THE 2003 EDITION AS STATED ON A1.0
 SHEET.
  
 2. THE PERMIT APPLICATION INDICATES THAT THE SCOPE OF
 WORK IS FOR SUITE 105, HOWEVER THE FOOR PLAN (SHEET
 A3.0) APPEARS TO INDICATE TWO SEPARATE TENAT SPACES.
 PLEASE EXPLAIN.
  
 3. IN COMPARING SHEETS A3.0, A4.0, AND E2, IT APPEARS
 THAT DOOR #18 FROM OPEN AREA (105) EXITS TO ANOTHER
 TENANT SPACE IN THE BUILDING. PLEASE EXPLAIN.
  
 4. IT IS STATED ON SHEET A1.0 THA THE BUILDING DOES NOT
 CONTAIN A FIRE ALARM SYSTEM. BASED UPON PREVIOUS FIELD
 INSPECTIONS CONDUCTED BY WEST PALM BEACH FIRE
 PREVENTION BUREAU, THIS BUILDING DOES HAVE A FIRE ALARM
 SYSTEM. PLEASE VERIFY AND IF THERE IS INDEED A FIRE
 ALARM SYSTEM IN THE BUILDING, PLEASE SHOW THE FIRE
 ALARM DEVICES IN THE SCOPE OF WORK LOCATION.
  
 5. SPECIFY THE INTERIOR FINISH MATERIAL FOR THE WALL
 AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-09 Cont ID  
Sent By rmcdouga Date 2009-12-09 Time 11:12 Rev Time 0.00
Received By rmcdouga Date 2009-12-09 Time 11:12 Sent To  
Notes
2009-12-09 11:16:33TO B-11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-11-23 Cont ID  
Sent By btrobaug Date 2009-11-23 Time 10:31 Rev Time 0.00
Received By btrobaug Date 2009-10-27 Time 13:45 Sent To PC
Notes
2009-10-28 13:46:39B12

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-12-21 Cont ID  
Sent By rregueir Date 2009-12-21 Time 09:34 Rev Time 0.00
Received By rregueir Date 2009-12-21 Time 09:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-11-06 Cont ID  
Sent By rregueir Date 2009-11-06 Time 10:53 Rev Time 0.00
Received By rregueir Date 2009-11-06 Time 10:41 Sent To  
Notes
2009-11-06 10:53:43REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M1 SHOWS SUPPLY AND EXHAUST DUCTS PENETRATING
 1-HOUR RATED WALL. SEE WALL TYPE "B" AS SHOWN ON PAGE
 A3.0. SHOW HOW THESE PENETRATIONS ARE TO BE PROTECTED
 IN ACCORDANCE WITH FBC-M 607.5 AND 607.8.
  
 2. THE FULL-HEIGHT FIRE RESISTANCE RATED WALL WILL
 PROHIBIT THE FLOW OF RETURN AIR THROUGH THE PLENUM
 CEILING BACK TO THE AIR HANDLING EQUIPMENT. PROVIDE
 TRANSFER AIR OPENINGS IN THE RATED WALL TO FACILITATE
 BALANCED RETURN IN ACCORDANCE WITH FBC-M 601.4. ALSO,
 SHOW HOW THESE TRANSFER OPENINGS ARE TO BE PROTECTED IN
 ACCORDANCE WITH FBC-M 607.5 AND 607.8.
  
 3. PAGE M1 SHOWS CEILING EXHAUST FANS WITH POSITIVE
 PRESSURE EXHAUST DUCTS WITHIN THE PLENUM CEILING.
 EXHAUST DUCTS UNDER POSITIVE PRESSURE SHALL NOT EXTEND
 INTO OR PASS THROUGH PLENUMS IN ACCORDANCE WITH FBC-M
 601.5.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-12-21 Cont ID  
Sent By kstevens Date 2009-12-21 Time 15:29 Rev Time 0.00
Received By kstevens Date 2009-12-21 Time 14:08 Sent To  
Notes
2009-12-21 15:30:35SEPARATE PERMIT REQUIRED FOR THE SINKS & CABINETS
 INDICATED AS NOT IN THIS CONTRACT.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-11-03 Cont ID  
Sent By kstevens Date 2009-11-03 Time 10:08 Rev Time 0.00
Received By kstevens Date 2009-11-03 Time 10:08 Sent To  
Notes
2009-11-03 10:23:51DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 1. ALL SHEETS SHALL INDICATE THE SPACE/UNIT/SUITE
 NUMBER IN THE TITLE BLOCK. SECTION 106.1.1.
  
 2. SHT A3.0 SHOW COMPLIANCE FOR THE FOLLOWING:
 ___W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.4 GRAB BARS (SHOWN AS 2'8" & 3'0")
 C. 11-4.16.5 FLUSH CONTROLS
 ___LAVS:
 A. 11-4.19.2 CLEARANCE (29")
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.5 FAUCETS
 ___TOILET ROOMS:
 A. 11-4.22.3 TURNING AREAS
 ___SINKS:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED) - CABINET DOORS PROHIBITED.
 E. 11-4.24.7 FAUCETS
 (SUBMIT ELEVATION FOR SINKS)
  
 3. A DRINKING FOUNTAIN IS REQUIRED. TABLE 403.1. SHOW
 THE LOCATION OF THE REQUIRED DRINKING FOUNTAIN AND
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15
 WITH ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-12-21 Cont ID  
Sent By eschneid Date 2009-12-21 Time 16:35 Rev Time 0.20
Received By eschneid Date 2009-12-21 Time 16:35 Sent To  
Notes
2009-12-21 16:35:57SEPARATE PARKING/SITE PERMIT REQUIRED FOR THE RAMP AND
 MODIFICATION TO THE PARKING FOR THE HC SPACE.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-10-30 Cont ID  
Sent By eschneid Date 2009-10-30 Time 17:32 Rev Time 0.15
Received By eschneid Date 2009-10-30 Time 17:31 Sent To  
Notes
2009-10-30 17:39:47FAILED
  
 1) THE NEW RAMP TO PARKING ON THE EAST SIDE OF THE
 BUILDING REQUIRES AN AMENDMENT TO THE APPROVED
 SITE/LANDSCAPE PLAN.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.