Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-12-01 Cont ID  
Sent By rmcdouga Date 2009-12-01 Time 14:36 Rev Time 0.00
Received By rmcdouga Date 2009-12-01 Time 14:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-11-17 Cont ID  
Sent By rmcdouga Date 2009-11-17 Time 11:47 Rev Time 0.00
Received By rmcdouga Date 2009-11-17 Time 07:20 Sent To  
Notes
2009-11-17 12:05:402007 FBC W/2009 REVISIONS
 STORM PANELS
  
 DENIED
  
 1) DIRECT MOUNT IS SPECIFIED FOR SOME OF THE STORM
 PANEL CONNECTION TYPES AND THE ONLY ANCHORS THAT ARE
 SPECIFIED ARE TAPCONS. TAPCONS ARE NOT ACCEPTABLE FOR
 DIRECT MOUNT PER PRODUCT APPROVAL.
  
 2) TABLE 2 NOTE ON PAGE 6 OF THE PRODUCT APPROVAL
 SPECIFIES A MINIMUM PANEL LENGTH FOR THE VARIOUS
 MOUNTING CONDITIONS. THE TABLE STATES THAT PANEL
 LENGTHS LESS THAN THOSE NOTED IN THE TABLE REQUIRE SITE
 SPECIFIC POROSITY CALCULATIONS BY A PROFESSIONAL
 ENGINEER. SOME OF THE PANEL LENGTHS ARE LESS THAN THE
 MINIMUMS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-11-02 Cont ID  
Sent By rmcdouga Date 2009-11-02 Time 12:31 Rev Time 0.00
Received By rmcdouga Date 2009-11-02 Time 12:08 Sent To  
Notes
2009-11-02 12:30:432007 FBC W/2009 REVISIONS
 STORM PANELS
  
 DENIED BY BUILDING
  
 1) THE COMPONENT AND CLADDING PRESSURES FOR THE
 OPENINGS TO BE SHUTTERED ARE TOO LOW. PLEASE REVISE.
 FBC R301.2(2)
  
 2) THE ANCHOR SPACING FOR OPENING NUMBERS 5, 8 AND 11
 ARE INCORRECT FOR CORRECTED PRESSURES.
  
 3) THE ANCHOR TYPE ON THE SCHEDULE FOR THE ALUMINUM
 STORM PANELS IS SPECIFIED AS TAP CONS, HOWEVER ON THE
 PRODUCT APPROVAL THE ELCO PANEL MATES ARE SELECTED.
 PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-11-19 Cont ID  
Sent By kstevens Date 2009-11-19 Time 10:00 Rev Time 0.00
Received By kstevens Date 2009-11-19 Time 10:00 Sent To  
Notes
2009-11-19 10:01:05SENT TO RMCDOUGAL..

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-11-12 Cont ID  
Sent By shill Date 2009-11-12 Time 15:41 Rev Time 0.00
Received By shill Date 2009-11-12 Time 15:41 Sent To  
Notes
2009-11-12 15:41:23TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-11-02 Cont ID  
Sent By rmcdouga Date 2009-11-02 Time 12:31 Rev Time 0.00
Received By rmcdouga Date 2009-10-27 Time 10:53 Sent To  
Notes
2009-10-26 16:52:38TO BUILDING $5K & UNDER