Plan Review Details - Permit 09100423
Plan Review Stops For Permit 09100423
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-11-02 Cont ID  
Sent By mcarsill Date 2009-11-02 Time 10:51 Rev Time 0.00
Received By mawillia Date 2009-11-02 Time 10:44 Sent To  
Notes
2009-11-02 10:51:131. THE NEW FIRE ALARM SYSTEM AND FIRE SPRINKLER SYSTEM
 SHALL BE MONITORED BY A UL LISTED CENTRAL STATION
 APPROVED FOR CENTRAL STATION SERVICE.
  
 2. SMOKE DETECTORS SHALL BE A MINIMUM OF AT LEAST THREE
 FEET FROM AIR CONDITIONER DIFFUSERS.
  
 3. TAMPER SWITCHES AND A CHAIN AND LOCK ARE REQUIRED ON
 THE FIRE LINE BACKFLOW DEVICE.
  
 4. ENTIRE INSTALLATION TO COMPLY WITH NFPA 72, THE
 NATIONAL FIRE ALARM CODE.
  
 5. EQUIPMENT IN AREAS THAT ARE SUBJECT TO DAMAGE SHALL
 BE PROPERLY PROTECTED FROM MECHANICAL DAMAGE. EXAMPLES
 INCLUDE THE GYMNASIUM THAT CAN BE DAMAGED BY
 BASKETBALLS.
  
 6. ON PAGE FA-2 2B DUCT DETECTORS SHALL CAUSE AN ALARM
 AND NOT A SUPERVISORY SIGNAL.
  
 7. PLEASE INDICATE IN WRITING WHAT THE VOICE EVACUATION
 MESSAGE WILL SAY. THIS MESSAGE WILL PROVIDE THE
 EMERGENCY INSTRUCTIONS THAT WILL BE PROVIDED BY THE
 FIRE ALARM CONTROL PANEL.
  
 APPROVED PROVISO;
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 (561) 804-4709 PHONE
 (561) 804-4774 FAX
 MCARSILLO@WPB,ORG
 WEST PALM BEACH

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-11-04 Cont ID  
Sent By mawillia Date 2009-11-04 Time 14:54 Rev Time 0.00
Received By mawillia Date 2009-10-20 Time 13:50 Sent To  
Notes
2009-11-04 14:39:28*****PROCESSED*****
  
 THE FIRE ALARM PLAN (FA-1 THRU FA-3) WAS DATE STAMPED,
 INCLUDING THE PERMIT NUMBER, PRIOR TO PRINTING THE
 PERMIT CARD.
2009-10-26 13:51:21IN FIRE BOX
 ROUTED ON 10/26/09