Plan Review Details - Permit 09100241
Plan Review Stops For Permit 09100241
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-11-05 Cont ID  
Sent By rmcdouga Date 2009-11-05 Time 12:54 Rev Time 0.00
Received By rmcdouga Date 2009-11-05 Time 12:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-10-20 Cont ID  
Sent By rmcdouga Date 2009-10-20 Time 07:36 Rev Time 0.00
Received By rmcdouga Date 2009-10-19 Time 06:43 Sent To  
Notes
2009-10-19 07:24:352007 FBC W/2009 REVISIONS
 EXISTING BUILDING
 LEVEL 3 ALTERATION
  
  
 DENIED BY BUILDING
  
 1) THIS PROJECT IS CLASSIFIED AS A LEVEL 3 ALTERATION
 BECAUSE THE WORK AREA EXCEEDS 50 PERCENT OF THE
 AGGREGATE AREA OF THE BUILDING. SEE FBC EXISTING
 BUILDING 405.
  
 2) SHOW AND EXPLAIN HOW COMPLIANCE WITH FBC 11-5.2
 WHICH REQUIRES A SECTION OF THE COUNTER/BAR TO BE 34"
 IN HEIGHT AND 60" IN LENGTH OR SERVICE SHALL BE
 AVAILABLE AT ACCESSIBLE TABLES WITHIN THE SAME AREA.
 ALSO SEE 11-4.32.
  
 3) THE WHEELCHAIR LIFT SHOWN ON THE DRAWINGS IS NOT
 REQUIRED. ACCESS IS NOT REQUIRED TO THE BACK KITCHEN.
 IT IS CONSIDERED A WORK AREA, IS NOT OPEN TO THE PUBLIC
 AND HAS AN OCCUPANT LOAD OF NO MORE THAN 5 PERSONS. IT
 IS NOT PART OF THE PRIMARY FUNCTION AREA. FBC 11-4.1.6
 (1) (F).
  
 4) THE STAIR IN THE MEANS OF EGRESS WITH A CHANGE IN
 LEVEL OF NOT EXCEEDING 21 INCHES IS REQUIRED TO HAVE A
 MINIMUM TREAD DEPTH OF 13 INCHES AND THE PRESENCE AND
 LOCATION OF EACH STEP SHALL BE READILY APPARENT PER FBC
 1003.5.1.
  
 5) FBC 1009.10 REQUIRES THE STAIR TO HAVE HANDRAILS ON
 EACH SIDE THAT COMPLY WITH SECTION 1012 AND 11-4.9.4.
  
 NOTE: THERE ARE 2 OF THE SAME SHEETS A-5.2 IN EACH OF
 THE PLAN SETS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-11-06 Cont ID  
Sent By btrobaug Date 2009-11-06 Time 11:39 Rev Time 0.00
Received By btrobaug Date 2009-11-06 Time 10:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-10-14 Cont ID  
Sent By btrobaug Date 2009-10-14 Time 17:31 Rev Time 0.00
Received By btrobaug Date 2009-10-14 Time 12:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-11-10 Cont ID  
Sent By mawillia Date 2009-11-10 Time 10:56 Rev Time 0.00
Received By mawillia Date 2009-11-10 Time 10:36 Sent To  
Notes
2009-11-10 10:56:05*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 SATISFIED; PLAN SHEETS A2.1, A3.1, A5.1, AND E2.01 WERE
 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-10-26 Cont ID  
Sent By mawillia Date 2009-10-26 Time 15:13 Rev Time 0.00
Received By mawillia Date 2009-10-26 Time 14:38 Sent To  
Notes
2009-10-26 14:56:52*****PARTIAL APPROVAL*****
  
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 FOLLOWING HAVE BEEN SATISFIED :
  
 1. SHOW LOCATION OF THE FIRE EXTINGUISHERS ON THE FLOOR
 PLAN AND/OR OTHER APPROPIATE PLAN SHEET.
  
 2. ON SHEET A5.1, DISPLAY THE NUMERICAL ADDRESS VISIBLE
 FROM DATURA STREET ON THE APPROPIATE EXTERIOR
 ELEVATION.
  
 3. BUILDING PLAN EXAMINER'S COMMENTS HAVE BEEN
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2009-10-22 Cont ID  
Sent By kstevens Date 2009-10-22 Time 18:09 Rev Time 0.00
Received By kstevens Date 2009-10-22 Time 18:09 Sent To  
Notes
2009-10-22 18:10:22SEPARATE GAS PERMIT IS REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-11-04 Cont ID  
Sent By lmartine Date 2009-11-04 Time 16:35 Rev Time 0.00
Received By lmartine Date 2009-11-04 Time 16:35 Sent To  
Notes
2009-11-04 16:39:02C--17
 *****************EXPEDITED*********************

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-10-27 Time   Rev Time 0.00
Received By lmartine Date 2009-10-13 Time 17:35 Sent To  
Notes
2009-10-13 17:39:38********************EXPEDITED*******************
 C--3

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2009-11-05 Cont ID  
Sent By rmcdouga Date 2009-11-05 Time 12:55 Rev Time  
Received By rmcdouga Date   Time   Sent To  
Notes
2009-11-05 12:55:50NOT A CHANGE OF OCCUPANCY

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-10-27 Cont ID  
Sent By rregueir Date 2009-10-27 Time 18:58 Rev Time 0.00
Received By rregueir Date 2009-10-27 Time 18:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2010-04-21 Cont ID  
Sent By lwagner Date 2010-04-21 Time 09:13 Rev Time 0.00
Received By lwagner Date 2010-04-21 Time 09:13 Sent To  
Notes
2010-04-21 09:15:16RESTROOM LAVS APPROVED: IAPMO & ANSI

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-11-18 Cont ID  
Sent By kstevens Date 2009-11-18 Time 08:44 Rev Time 0.00
Received By kstevens Date 2009-11-18 Time 08:44 Sent To  
Notes
2009-11-19 11:09:30PASSED/PROVISO:
  
 PLANS APPROVED PENDING APPROVAL OF GREASE INTERCEPTOR
 BY UTILITY DEPT.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-10-22 Cont ID  
Sent By kstevens Date 2009-10-22 Time 17:18 Rev Time 0.00
Received By kstevens Date 2009-10-22 Time 17:18 Sent To  
Notes
2009-10-22 18:09:39DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
 MUNICIPAL CODE W.P.B.
  
 1. SHT A2.1 MEN'S TOILET ROOM. THE LAV IN THE
 ACCESSIBLE STALL APPEARS TO RESTRICT THE ACCESS TO THE
 STALL. PLEASE MOVE THE LAV SO THAT THE W/C IS JUST
 OUTSIDE THE CLEAR FLOOR SPACE REQUIRED FOR THE LAV.
 SECTION 11-4.17.3 EXCEPTION (TECHNICALLY INFEASIBLE) TO
 BRING THE STALL UP TO AS MUCH CODE REQUIREMENTS AS
 POSSIBLE.
  
 2. SHTS P1.01 & P2.01 THE GREASE INTERCEPTOR SHALL BE
 SIZED & APPROVED BY THE UTILITY DEPT. ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT HOLLY MCGRATH, LABORATORY
 SUPERVISOR. PHONE NUMBER (561) 822-2271, FAX (561)
 822-2279 OR E-MAIL [email protected]. A DETERMINATION
 FROM THE UTILITY DEPT. IS REQUIRED IN WRITING OR E-MAIL
 PRIOR TO PERMIT. ARTICLE III SECTION 90-124(7).
  
 3. SHTS P1.01 & P2.01 ALL FLOOR DRAINS & THE FLOOR SINK
 FOR THE 3 COMPARTMENT SINK IN THE FOOD PREP AREA AS
 WELL AS THE HAND SINK IN THE FOOD PREP AREA SHALL DRAIN
 THROUGH THE REQUIRED GREASE INTERCEPTOR. SECTION
 1003.3.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-11-17 Cont ID  
Sent By aaponte Date 2009-11-17 Time 15:09 Rev Time 0.00
Received By aaponte Date 2009-11-17 Time 15:09 Sent To  
Notes
2009-11-17 15:10:14SIGNS ARE NOT INCLUDED WITH THIS PERMIT

Review Stop Z ZONING
Rev No 1 Status F Date 2009-10-21 Cont ID  
Sent By aaponte Date 2009-10-21 Time 16:01 Rev Time 0.00
Received By aaponte Date 2009-10-21 Time 16:01 Sent To  
Notes
2009-10-21 16:06:02PLANTERS AND HORIAONTAL VINES ARE NOT PERMITTED ON THE
 ROW. PLEASE CONTACT ANA MARIA APONTE AT 822-1439 FOR
 FURTHER DISCUSSION.
 SIGNS SHALL NOT BE INCLUDED UNDER THIS PERMIT.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved