2009-10-13 09:09:15 | RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST. | | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- PRODUCT APPROVAL NOA 06-0410.06 SUBMITTED IS NO | | LONGER VALID. THIS FILE WAS CLOSED BY THE MIAMI-DADE | | PRODUCT CONTROL DIVISION. SEE MIAMI-DADE WEBSITE. | | PROVIDE COPIES OF CURRENT NOA. | | | | 2- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | LIMITATION #7 ON PAGE 41 OF SELECTED ASSEMBLY. | | | | 3- RAS 117 CALCULATIONS NEED TO BE SIGNED AND SEALED AS | | REQUIRED ON LAST PAGE OF NOA SUBMITTED. | | ***NOTE: DESIGN PROFESSIONAL WHEN DOING THE RAS 117 | | CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING | | TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 | | FLORIDA RESIDENTIAL CODE, THIS BUILDING IS LOCATED ON | | "EXPOSURE C". | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
|