Plan Review Details - Permit 09100090
Plan Review Stops For Permit 09100090 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2009-10-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-10-15 |
Time |
07:08 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-10-14 |
Time |
13:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2009-10-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-10-09 |
Time |
15:49 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-10-09 |
Time |
15:49 |
Sent To |
|
|
Notes |
2009-10-09 15:51:08 | ** PROVISO ** | | | | ** PLEASE REVISE THE FOLLOWING ITEMS | | | | 1) NOTE: PLEASE COORDINATE THE RISER, PANELS AND | | CONDUCTORS FOR THE FOLLOWING. | | A) RISER INDICATES 3-#8 AND 1-#10 FROM PANEL H TO | | TRANSFORMER HOWEVER PANEL H SCHEDULE INDICATES ALL AS | | #12 AWG. | | B) THE RISER INDICATES THE PANEL H AS BEING A 100AMP | | MLO, HOWEVER PANEL H SCHEDULE DETAILS INDICATES THIS AS | | A 100AMP MAIN CIRCUIT BREAKER PANEL. | | | | ** EITHER OF THE ABOVE FOUR SCENARIOS ARE CODE | | COMPLIANT HOWEVER PLANS NEED TO COORDINATE. PLEASE KEEP | | IN MIND #8 AWG WILL NOT FIT INTO A 20AMP BREAKER | | | | 2) NOTE: PLANS NEED TO INDICATE THE MINIMUM LEVELS FOR | | ADA COMPLIANCE FOR HORN AND STROBE DEVICES. FBC | | 11-4.28.1,.2 AND.3. | | | | ** PLANS NOTED FOR 210.4B OF THE 2008 NEC. | | ** LOW VOLTAGE PERMITS FOR PHONE/DATA/CATV, FIRE ALARM | | AND ANY ACCESS CONTROL SYSTEMS ARE UNDER SEPARATE | | PERMITS. | | THESE PLANS MAY BE REFERENCED FOR LV SYSTEMS OTHER THAN | | FA AND ACCESS CONTROLS. | | | | | | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2009-10-07 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2009-10-07 |
Time |
17:30 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2009-10-07 |
Time |
17:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2009-10-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-10-15 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-10-06 |
Time |
11:07 |
Sent To |
|
|
Notes |
2009-10-06 11:08:23 | B--5 'EXPEDITED' |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
N |
Date |
2009-10-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-10-15 |
Time |
06:51 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-10-15 |
Time |
06:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2009-10-09 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2009-10-09 |
Time |
10:12 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2009-10-09 |
Time |
10:12 |
Sent To |
|
|
Notes |
2009-10-09 10:12:52 | MECHANICAL SCOPE SHOWN ON PAGE A-1.2. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2009-10-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-10-14 |
Time |
17:19 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-10-14 |
Time |
17:19 |
Sent To |
B |
|
Notes |
2009-10-14 17:19:53 | PLUMBING PERMIT REQUIRED. FIXTURES IN SAME LOCATION. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2009-10-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-10-15 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-10-15 |
Time |
09:08 |
Sent To |
|
|
Notes |
2009-10-15 09:08:44 | OK PER A APONTE | | |
|
|
|