Plan Review Details - Permit 09100025
Plan Review Stops For Permit 09100025
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-10-05 Cont ID  
Sent By jwitmer Date 2009-10-05 Time 14:30 Rev Time 1.00
Received By jwitmer Date 2009-10-05 Time 13:30 Sent To  
Notes
2009-10-05 14:24:21BUILDING PLAN REVIEW
 PERMIT: 09100025
 ADD: 444 W RAILROAD AV.
 CONT: (PLAN REVIEW) PBM DEV
 TEL: (561)715-1800
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 OCT 05-2009
 1ST REVIEW
 ACTION: DENIED
  
  
 1) THE PLANS INDICATE THE MOVING OF THE ACCESSIBLE
 PARKING SPACES NEXT TO THE ENTRY AND CREATING
 ACCESSIBLE SPACES FURTHER AWAY FROM THE ENTRY AND ALSO
 CAUSING THE DISSABLED TO TRAVEL BEHIND THE OTHER PARKED
 VEHICLES.
  
 11-4.6.2 LOCATION. ACCESSIBLE PARKING SPACES SERVING A
 PARTICULAR BUILDING SHALL BE LOCATED ON THE SHORTEST
 SAFELY ACCESSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING
 TO AN ACCESSIBLE ENTRANCE.
  
 11-4.1.6 ACCESSIBLE BUILDINGS: ALTERATIONS.1) GENERAL.
 ALTERATIONS TO EXISTING BUILDINGS AND FACILITIES SHALL
 COMPLY WITH THE FOLLOWING:
  
 (A) NO ALTERATION SHALL BE UNDERTAKEN WHICH DECREASES
 OR HAS THE EFFECT OF DECREASING ACCESSIBILITY OR
 USABILITY OF A BUILDING OR FACILITY BELOW THE
 REQUIREMENTS FOR NEW CONSTRUCTION AT THE TIME OF
 ALTERATION.
  
 (B) IF EXISTING ELEMENTS, SPACES, OR COMMON AREAS ARE
 ALTERED, THEN EACH SUCH ALTERED ELEMENT, SPACE,
 FEATURE, OR AREA SHALL COMPLY WITH THE APPLICABLE
 PROVISIONS OF SECTION 11-4.1.1 TO SECTION 11-4.1.3,
 MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION.
  
  
 2) SHEET A-4 INDICATES THE INSTALATION OF A 5,000 GAL
 DESIEL FUEL DOUBLE WALL TANK. THIS IS IN EXCESS OF
 ALLOWABLE COMBUSTIBLE LIQUIDS FOR A CLASS LL COMBUSTILE
 LIQUIDS, SEE TABLE 307.7(1) WHEN OVER 240 GAL FOOTNOTE
 D & E.
  
 415.6.2 FLAMMABLE AND COMBUSTIBLE LIQUIDS. THE STORAGE,
 HANDLING, PROCESSING AND TRANSPORTING OF FLAMMABLE AND
 COMBUSTIBLE LIQUIDS SHALL BE IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, MECHANICAL AND THE FLORIDA FIRE
 PREVENTION CODE.
  
 415.6.2.1 MIXED OCCUPANCIES. WHERE THE STORAGE TANK
 AREA IS LOCATED IN A BUILDING OF TWO OR MORE
 OCCUPANCIES, AND THE QUANTITY OF LIQUID EXCEEDS THE
 MAXIMUM ALLOWABLE QUANTITY FOR ONE CONTROL AREA, THE
 USE SHALL BE COMPLETELY SEPARATED FROM ADJACENT FIRE
 AREAS IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 508.3.3. PLEASE INDICATE COMPLIANCE WITH THIS SECTION.
  
  
 3) PLEASE PROVIDE THE MANUFACTURERS CUT SHEETS FOR
 COMPLIANCE WITH:
 415.6.2.5 LEAKAGE CONTAINMENT. A LIQUID-TIGHT
 CONTAINMENT AREA COMPATIBLE WITH THE STORED LIQUID
 SHALL BE PROVIDED. THE METHOD OF SPILL CONTROL,
 DRAINAGE CONTROL AND SECONDARY CONTAINMENT SHALL BE IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
 EXCEPTION: ROOMS WHERE ONLY DOUBLE-WALL STORAGE TANKS
 CONFORMING TO SECTION 415.6.2.3 ARE USED TO STORE CLASS
 I, II AND IIIA FLAMMABLE AND COMBUSTIBLE LIQUIDS SHALL
 NOT BE REQUIRED TO HAVE A LEAKAGE CONTAINMENT AREA.
  
 4) PLEASE PROVIDE ANCHORING REQUIREMENTS FOR SLIPPAGE
 AND UPLIFT 1604.8.1.
  
 5) 1603.1.4 WIND DESIGN DATA. THE FOLLOWING INFORMATION
 RELATED TO WIND LOADS SHALL BE SHOWN, REGARDLESS OF
 WHETHER WIND LOADS GOVERN THE DESIGN OF THE
 LATERAL-FORCE-RESISTING SYSTEM OF THE BUILDING:
  
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (M/S).
  
 2. WIND IMPORTANCE FACTOR, IW , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE. WHERE MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M2) TO BE USED FOR THE SELECTION OF
 EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-26 Cont ID  
Sent By btrobaug Date 2009-10-26 Time 12:09 Rev Time 0.00
Received By btrobaug Date 2009-10-26 Time 08:13 Sent To  
Notes
2009-10-26 08:28:34 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 TRANSFER SWITCH.AND GENERATOR.
  
 2} 702.8 A SIGN SHALL BE PLACED AT THE SERVICE-ENTRANCE
 EQUIPMENT THAT INDICATES THE TYPE AND LOCATION OF
 ON-SITE OPTIONAL STANDBY POWER SOURCES.
  
 3} THE ELECTRICAL NOTES ON SHEET EO.1 INDICATE 2005
 NFPA-70 AS THE GOVERNING CODE, THE 2008 EDITION WAS
 ADOPTED 10/1/09, PLEASE CHANGE THE REFERENCE.
  
 4} THE FEEDER SCHEDULE LABLED "FH" ON SHEET E5.1
 INDICATES 3 #1/0 CONDUCTORS. FOUR CONDUCTORS (NEUTRAL
 INCLUDED) WOULD BE REQUIRED PER 250.24 (C). ALSO THE
 CONTROLLER WILL MOST LIKLUDE 120 VOLT CIRCUITS
  
 5} THE GENERATOR IS LABELED "EMERGENCY" ON E5.1, PLEASE
 NOTE THAT THE SYSTEM IS A 702 SYSTEM, NOT EMERGENCY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-10-21 Cont ID  
Sent By mcarsill Date 2009-10-21 Time 16:25 Rev Time 0.00
Received By mcarsill Date 2009-10-21 Time 16:00 Sent To  
Notes
2009-10-21 16:25:06STANDBY GENERATOR AND ABOVEGROUND STORAGE TANK (AST)
  
 1. PLEASE PROVIDE PRODUCT APPROVALS FOR THE "FIREGUARD"
 INSULATED TANK (2085) AS DESCRIBED ON THE PLANS. SOME
 INFORMATION IS SHOWN ON PAGE A-04.
  
 2. PLEASE ILLUSTRATE THE LOCATION OF ANY OPENINGS NEAR
 THE GENERATOR EXHAUST PIPE.
  
 3. PLEASE PROVIDE PRODUCT APPROVALS FOR THE GENERATOR.
  
 4. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
 5. ENTIRE INSTALLATION TO COMPLY WITH NFPA 30.
  
 6. THE GENERATOR INSTALLATION SHALL ALSO COMPLY WITH
 NFPA 37.
  
 7. SEVERAL REQUIREMENTS OF THE FLORIDA BUILDING CODE
 ARE NOT BEING MET WITH THE PROPOSED INSTALLATION.
 PLEASE SEE BUILDING REVIEWER NOTES.
  
 8. AN ELEVATION DRAWING IS NEEDED WHERE THE PROPOSED
 EQUIPMENT IS BEING SHOWN.
  
 9. BASED ON THE SIZE CAPACITY OF THE PROPOSED FUEL TANK
 A SEPARATE FIRE RATED ENCLOSURE APPEARS TO BE
 NECESSARY.
  
 10. PLEASE ILLUSTRATE ON THE PLANS THE LOCATION OF THE
 TWO HOUR WALLS THAT SEPARATE THE PARKING STRUCTURE FROM
 OTHER PORTIONS OF THE BUILDING.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 (561) 804-4709 PHONE
 (561) 804-4774 FAX
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-10-27 Cont ID  
Sent By btrobaug Date 2009-10-27 Time 12:23 Rev Time 0.00
Received By btrobaug Date 2009-10-05 Time 09:39 Sent To PC
Notes
2009-10-05 09:39:32TO B-20

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-10-23 Cont ID  
Sent By rregueir Date 2009-10-23 Time 11:35 Rev Time 0.00
Received By rregueir Date 2009-10-23 Time 11:26 Sent To  
Notes
2009-10-23 11:35:00REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE INSTALLATION OF LIQUID-FUELED STATIONARY
 INTERNAL COMBUSTION ENGINES AND GAS TURBINES, INCLUDING
 FUEL STORAGE AND PIPING, SHALL MEET THE REQUIREMENTS OF
 NFPA 37 IN ACCORDANCE WITH FBC-M 915.1.
  
 2. PLANS INDICATE THIS GENERATOR WILL SERVE ALL
 BUILDING SYSTEMS DURING POWER OUTAGES INCLUDING
 EMERGENCY SYSTEMS. GENERATORS USED FOR EMERGENCY POWER
 SUPPLIES SHALL ALSO COMPLY WITH NFPA 110, STANDARD FOR
 EMERGENCY AND STANDBY POWER SYSTEMS.
  
 3. PROVIDE GENERATOR MANUFACTURER???S SPECIFICATIONS
 INDICATING THE MINIMUM FREE-AREA OPENING REQUIRED FOR
 RADIATOR EXHAUST. THE AIR SUPPLY SHALL BE DESIGNED TO
 MEET AT LEAST THE MINIMUM REQUIREMENTS FOR COMBUSTION,
 COOLING, AND VENTILATION IN ACCORDANCE WITH NFPA 37-02
 SECTION 4.1.1.2. VENTILATION AIR SUPPLY AND DISCHARGE
 FOR RADIATOR COOLED EPS SHALL HAVE A MAXIMUM STATIC
 RESTRICTION OF 0.5 INCHES OF WATER COLUMN (125 PA) IN
 THE DISCHARGE DUCT AT THE RADIATOR OUTLET IN ACCORDANCE
 WITH NFPA 110-02 SECTION 7.7.4.1.
  
 4. WITH THE EPS RUNNING AT RATED LOAD, VENTILATION AIR
 FLOW SHALL BE PROVIDED TO LIMIT THE MAXIMUM AIR
 TEMPERATURE IN THE EPS ROOM TO THE MAXIMUM AMBIENT AIR
 TEMPERATURE REQUIRED BY THE EPS MANUFACTURER IN
 ACCORDANCE WITH NFPA 110-02 SECTION 7.7.1.
 CONSIDERATION SHALL BE GIVEN TO ALL THE HEAT REJECTED
 TO THE EPS EQUIPMENT ROOM BY THE ENERGY CONVERTER,
 UNINSULATED OR INSULATED EXHAUST PIPES, AND OTHER HEAT
 PRODUCING EQUIPMENT.
  
 5. PLANS INDICATE A 5000 GALLON FUEL TANK. FUEL TANKS
 WITHIN A STRUCTURE BUT NOT IN A ROOM BY THEMSELVES
 SHALL NOT EXCEED 660 GALLONS IN ACCORDANCE WITH NFPA
 37-02 SECTION 6.3.2.2 UNLESS ALL CONDITIONS OF THE
 EXCEPTION TO THIS SECTION ARE MET.
  
 EXCEPTION: FUEL TANKS OF ANY SIZE SHALL BE PERMITTED
 WITHIN ENGINE ROOMS OR MECHANICAL SPACES, PROVIDED THE
 ENGINE OR MECHANICAL ROOM IS DESIGNED USING RECOGNIZED
 ENGINEERING PRACTICES WITH SUITABLE FIRE DETECTION,
 FIRE SUPPRESSION, AND CONTAINMENT MEANS TO PREVENT THE
 SPREAD OF FIRE BEYOND THE ROOM OF ORIGIN.
  
 6. THE AGGREGATE CAPACITY OF ALL FUEL TANKS IN A
 STRUCTURE SHALL NOT EXCEED 5000 L (1320 GAL) UNLESS
 THAT PORTION EXCEEDING 5000 L (1320 GAL) IS ENCLOSED IN
 A ROOM IN ACCORDANCE WITH 6.3.6 PER NFPA 37-02 SECTION
 6.3.2.3.
  
 7. THE ENGINE ROOM SHALL BE PROPERLY VENTILATED IN
 ACCORDANCE WITH NFPA 37-02 SECTION 6.3.6.5.
  
 8. FUEL TANKS WITHIN STRUCTURES SHALL BE PROVIDED WITH
 SPILL CONTAINMENT CONSISTING OF EITHER A WALL, A CURB,
 OR A DIKE HAVING A CAPACITY AT LEAST EQUAL TO THAT OF
 THE LARGEST SURROUNDED TANK IN ACCORDANCE WITH NFPA
 37-02 SECTION 6.3.2.4.
  
 9. ENGINE ROOMS LOCATED WITHIN STRUCTURES SHALL HAVE
 INTERIOR WALLS, FLOORS, AND CEILINGS OF AT LEAST 1-HOUR
 FIRE RESISTANCE RATING IN ACCORDANCE WITH NFPA 37-02
 SECTION 4.1.2.3.
  
 10. ENGINE ROOMS SHALL HAVE VENTILATION THAT IS
 ADEQUATE TO PREVENT A HAZARDOUS ACCUMULATION OF
 FLAMMABLE VAPORS OR GASES, BOTH WHEN THE ENGINE IS
 OPERATING AND WHEN IT IS SHUT DOWN IN ACCORDANCE WITH
 NFPA 37-02 SECTION 4.1.2.5.
  
 11. ADDITIONAL REQUIREMENTS MAY BE APPLICABLE UPON
 DETERMINATION OF THE CLASSIFICATION OF THIS SYSTEM AS A
 LEVEL 1 OR LEVEL 2 EPSS IN ACCORDANCE WITH NFPA 110-02
 SECTION 4.4.
  
 12. ABOVE GROUND FUEL TANK INSTALLATIONS SHALL BE
 APPROVED BY PALM BEACH COUNTY DERM PRIOR TO PERMIT
 ISSUANCE. PROVIDE TWO SETS OF PLANS APPROVED BY PBC
 DERM AT TIME OF PERMIT APPLICATION.
  
 13. ALL PLANS SHALL BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL IN ACCORDANCE WITH FBC-B SECTION 106.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2009-10-22 Cont ID  
Sent By aaponte Date 2009-10-22 Time 13:20 Rev Time 0.00
Received By aaponte Date 2009-10-22 Time 13:19 Sent To  
Notes
2009-10-22 13:25:451. PLEASE PROVIDE ELEVATIONS DEPICTING THE CHANGE ON
 THE FACADE DUE TO THE FPL VAULT (EXISTING AND NEW)
 2. PROPOSED LOADING DOCK IS BLOCKING THE DRIVE AISLE.
 CURRENT CONFIGURATION IS A TWO-WAY DRIVE AISLE (24'
 MIN.)
 3. HANDICAP SPACES SHALL BE LOCATED IN THE NEAREST
 POSSIBLE SPACE TO THE ENTRANCE.