Plan Review Details - Permit 09090649
Plan Review Stops For Permit 09090649
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2010-03-24 Cont ID  
Sent By jgomez Date 2010-03-24 Time 11:03 Rev Time 0.00
Received By jgomez Date 2010-03-24 Time 08:50 Sent To  
Notes
2010-03-24 11:04:06REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-03-09 Cont ID  
Sent By jgomez Date 2010-03-09 Time 15:05 Rev Time 0.00
Received By jgomez Date 2010-03-09 Time 15:04 Sent To  
Notes
2010-03-09 15:05:39ENGINEERED TRUSS REPAIR DRAWING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-12-15 Cont ID  
Sent By jgomez Date 2009-12-15 Time 13:07 Rev Time 0.00
Received By jgomez Date 2009-12-15 Time 13:07 Sent To  
Notes
2009-12-15 13:16:25BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE INFORMATION SHOWING COMPLIANCE WITH THE ROOF
 VENTILATION AS REQUIRED BY SEC. R806.1 OF 2007 FLORIDA
 RESIDENTIAL CODE. REVISE CALCULATIONS SHOWN ON SHEET
 A1. NEED TO INCLUDE THE OVERALL ROOF AREA NOT JUST THE
 A/C AREA. ALSO, SIZE OF GABLE VENTS TO PROVIDE THE
 REQUIRED VENTILATION. PROVIDE CALCULATIONS SHOWING THE
 ACTUAL CLEAR AREA OF THE SPECIFIED VENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-10-19 Cont ID  
Sent By jgomez Date 2009-10-19 Time 15:54 Rev Time 0.00
Received By jgomez Date 2009-10-19 Time 15:35 Sent To  
Notes
2009-10-19 16:14:42NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- SHEET A2: SPECIFY ALL LIVE AND DEAD LOADS INCLUDING
 THE ATTIC LIVE LOAD AS REQUIRED BY SEC. R301.1 AND
 TABLE R301.5 OF 2007 FLORIDA RESIDENTIAL CODE.
 ***NOTE: STRUCTURAL NOTE REGARDING THE ROOF LOADS IS
 INCOMPLETE AND DOESN'T SPECIFY ALL DESIGN LOADS.
 EXPLAIN WHAT IS "ALL DEAD LOADS PLUS 20PSF LIVE LOAD"
 ?.
  
 2- CLARIFY HOW IS THE ROOF VENTILATION REQUIRED BY SEC.
 R806 OF 2007 FLORIDA RESIDENTIAL CODE TAKEN CARE OF.
  
 3- SPECIFY ATTIC SIZE AND LOCATION AS REQUIRED BY SEC.
 R807. PLANS ONLY SHOW A NOTE BY THE HALLWAY STATING "
 ATTIC ACCESS". BUT, THERE IS NO SIZE AND SPECIFIC
 LOCATION SPECIFIED.
  
 4- A) PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED
 BY DCA RULE 9B-72 FOR THE HARDI BOARD TO BE INSTALLED.
  
 B) ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 PRODUCT APPROVAL PRIOR TO SUBMITTAL.
  
 5- BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.
  
 6- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 **NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 7- OWES $15.92 FOR RADON FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-12-14 Cont ID  
Sent By dpalmer Date 2009-12-14 Time 16:29 Rev Time 0.00
Received By dpalmer Date 2009-12-14 Time 16:29 Sent To  
Notes
2009-12-14 16:29:59** REDLINED PLANS.
  
  
  
 1) NOTE: PLANS INDICATE THE 2008 NEC, HOWEVER PERMIT
 APPLICATION WAS MADE BEFORE 10/31/09 WHICH PLACES
 PROJECT UNDER THE 2005 NEC.
  
 2) NOTE: AS NOTED PREVIOUSLY, ANY 15/20AMP 120
 RECEPTACLES WITHIN 6FT OF LAUNDRY SINK SHALL BE GFI/GFI
 PROTECTED. AN EXAMPLE IS THE DEDICATED CIRCUIT SUCH AS
 THE WASHING MACHINE. THIS WAS REVISED IN THE 2005 NEC.
  
 3) NOTE: RISER NOW INDICATES A NEW MAIN DISCONNECT
 WHICH IS OK, HOWEVER NOW THE RISER IS MISSING THE
 EQUIPMENT GROUNDING CONDUCTOR FROM MAIN TO THE SUB MLO
 PANEL INSIDE. PLEASE SIZE PER 250.122.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-10 Cont ID  
Sent By dpalmer Date 2009-10-10 Time 07:48 Rev Time 0.00
Received By dpalmer Date 2009-10-10 Time 07:01 Sent To  
Notes
2009-10-10 07:48:55 
  
 ** DENIED **
  
 ** SOME OF THE COMMENTS BELOW WOULD TYPICALLY BE
 REDLINED HOWEVER NOT ALL. AS STATED IN ALL REVIEWS IF
 THERE ARE QUESTIONS ON ANY OF THE BELOW COMMENTS PLEASE
 DO NOT HESITATE IN CONTACTING THIS REVIEWER.
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE
 REFLECTED ON ELECTRICAL PLANS.
 2005 NFPA-70 (NEC)
 2002 NFPA-72
  
 2) NOTE: PLEASE INCLUDE AIC RATING OF MAIN/SERVICE
 EQUIPMENT. 110.9
  
 3) NOTE: PLEASE SEE 250.6, 250.24 AS AN EQUIPMENT
 GROUNDING CONDUCTOR IS SHOWN BEFORE THE FIRST MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED. AS THE
 GROUNDED/NEUTRAL CONDUCTOR IS BONDED AT THE FIRST MEANS
 OF DISCONNECT THIS WOULD PARALLEL THE NEUTRAL CREATING
 OBJECTIONABLE CURRENTS.
  
 4) NOTE: PLEASE SEE MASTER BATH. GFI RECEPTACLE SPACE
 MUST MEET 210.52D. THE LOCATION OF THE GFI IS REQUIRED
 TO BE WITHIN 3FT OF SINK EDGE WITHOUT CROSSING OVER
 ANOTHER SINK. PLEASE RELOCATE GFI OR ADD AND ADDITIONAL
 RECEPTACLE.
  
 5) NOTE: PANEL SCHEDULE DOES NOT LIST THE REQUIRED
 DEDICATED CIRCUITING FOR BATH(S) PER 210.11C3. IT IS
 PERMISSIBLE TO WIRE TWO DIFFERENT WAY HOWEVER IN ANY
 CASE THE MINIMUM CIRCUIT REQUIRED IS REQUIRED TO BE
 20AMP AND #12 AWG.
  
 6) NOTE: THE MECHANICAL PLANS INDICATE THE HEAT STRIP
 KW AT 10KW WHICH ON A HOUSE OF THIS SIZE IS ABOUT
 RIGHT. HOWEVER THE ELECTRICAL PANEL SCHEDULE STATES
 5KW.
 PLEASE COORDINATE AND ADJUST OVER CURRENT PROTECTION
 AND BRANCH CIRCUIT SIZING PER 240.4,310.16 AND MINIMUM
 125% PER 424.3B
  
 7) NOTE: ALONG WITH COMMENT #6 ABOVE, IF THE HEAT LOAD
 IS LARGE THAN THE COOLING LOAD THEN THE HEAT LOAD WOULD
 THEN BE FIGURED INTO THE LOAD CALCULATIONS. 220.60
  
 8) NOTE: PLANS INDICATES THE SERVICE AS EXISTING
 HOWEVER HOW IS THIS POSSIBLE WHEN THIS IS A NEW SFR?
 PLEASE INCLUDE THE SERVICE ENTRANCE CONDUCTORS PER
 310.15B6 OR 310.16.
  
 9) NOTE: PLEASE KITCHEN COUNTER SPACE TO THE RIGHT OF
 THE SINK LOCATION WHICH WILL REQUIRE AND ADDITIONAL GFI
 PER 210.52C1-5. 210.8A6 FOR GFI PROTECTION.
  
 10) NOTE: A CHANGE IN THE 2005 NEC WAS 210.8A7 WHICH
 REQUIRED ALL RECEPTACLES LOCATED WITHIN 6FT OF LAUNDRY
 SINKS TO BE GFI/GFI PROTECTED. THIS INCLUDES ANY
 DEDICATED CIRCUITS/RECEPTACLES SUCH AS WASHING
 MACHINES.
  
 11) NOTE: PLEASE SEE 408.4 AS ANOTHER CHANGE IN THE
 2005 NEC WAS THAT ALL PANEL SCHEDULES SHALL BE MORE
 SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. THE USE
 OF *GENERAL LIGHTING AND GENERAL RECEPTACLES* WAS NO
 LONGER ACCEPTABLE. THE RECORD SET OF PLANS WILL BE
 REQUIRED TO HAVE PANEL SCHEDULE UPDATED BEFORE FINAL.
 THIS ITEM COULD BE DONE AS A PROVISO.
 AT THAT TIME ALL ARC FAULT PROTECTED CIRCUITS ARE
 REQUIRED TO BE LISTED. PLANS ONLY CONTAIN A NOTE THAT
 MENTIONS ALL OUTLETS IN BEDROOMS TO BE PROTECTED. THIS
 PROJECT IS UNDER THE 2005 NEC AND NOT THE 2008. 210.12
  
 12) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.52 AS
 ONE OR MORE OF THE TWO MINIMUM SMALL APPLIANCE CIRCUITS
 TO BE SHOWN AND FIGURED AT 1500VA. PLEASE SEE 210.52B1
 AS DINING ROOMS, BREAKFAST AREAS AND AREAS OF THE LIKE
 ARE ALL CONSIDERED UNDER THE SMALL APPLIANCE RULES OF
 THE CODE. IF THERE IS AN ADDITIONAL DINING ROOM
 RECEPTACLE CIRCUIT OR FLORIDA/BREAKFAST ROOM RECEPTACLE
 CIRCUIT THEN EACH ONE ABOVE THE TWO MINIMUM SMALL
 APPLIANCES WOULD BE REQUIRED TO BE AN ADDITIONAL
 1500VA.
 PLEASE ADJUST AS NEEDED. AS THE PANEL SCHEDULE IS NOT
 SPECIFIC IT IS NOT POSSIBLE TO GIVE A ACCURATE REVIEW
 OF THE LOADS AND CIRCUITING FOR MINIMUMS.
  
 13) NOTE: THE LIVING ROOM NORTHEAST WALL IS OVER 12FT
 WHICH WOULD REQUIRE AT LEAST ONE ADDITIONAL RECEPTACLE
 PER 210.52.
  
 14) NOTE: PLANS INDICATE SMOKE DETECTORS. PLEASE SEE
 NFPA-72 AS SMOKE DETECTORS ARE ONLY DEVICES WHICH
 DETECT AND DO NOT SOUND AN ALARM. WILL THERE BE A FIRE
 ALARM PANEL AND SOUNDING DEVICES?
 SMOKE ALARMS ARE DEVICES THAT DETECT AND SOUND AN
 ALARM. SHOULD THESE BE SA AND SMOKE ALARMS?
 PLEASE SEE 11.5.1,11.8.3 OF NFPA AND CHAPTER 9 OF FBC
 FOR DEFINTIONS.
  
  
  
  
 **IMPORTANT**
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2009-09-29 14:20:22OK PER J PAPA NO FEE 9-29-09

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-03-22 Cont ID  
Sent By lmartine Date 2010-03-18 Time 14:46 Rev Time 0.00
Received By lmartine Date 2010-03-18 Time 14:45 Sent To  
Notes
2010-03-22 14:46:44R--10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-09 Cont ID  
Sent By rmcdouga Date 2009-12-09 Time 10:50 Rev Time 0.00
Received By rmcdouga Date 2009-12-09 Time 10:50 Sent To  
Notes
2009-12-09 10:54:42SENT TO R 10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-09 Cont ID  
Sent By rmcdouga Date 2009-12-09 Time 10:50 Rev Time 0.00
Received By rmcdouga Date 2009-09-30 Time 09:36 Sent To  
Notes
2009-09-30 09:40:05SENT TO R5

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2009-12-15 Cont ID  
Sent By jgomez Date 2009-12-15 Time 13:06 Rev Time 0.00
Received By jgomez Date 2009-12-15 Time 13:06 Sent To  
Notes
2009-12-15 13:07:10PR# 09020996.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2009-10-19 Cont ID  
Sent By jgomez Date 2009-10-19 Time 15:34 Rev Time 0.00
Received By jgomez Date 2009-10-19 Time 15:34 Sent To  
Notes
2009-10-19 15:35:41NEED PALM BEACH COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-10-07 Cont ID  
Sent By rkussner Date 2009-10-07 Time 14:22 Rev Time 0.00
Received By rkussner Date 2009-10-07 Time 14:22 Sent To  
Notes
2009-10-07 14:24:09***LANDSCAPE REVIEW PASSED WITH PROVISO***
  
 1. PROVIDE SOD AND IRRIGATION IN RIGHT-OF-WAY.
  
 2. OPEN SPACE TOTALS 4,358 SQUARE FEET.
  
 3. SUBMIT COST ESTIMATE THAT INCLUDES THE TOTAL COST OF
 ALL LANDSCAPE MATERIRALS AND LABOR, BROKEN DOWN INTO
 UNIT COST.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-11-10 Cont ID  
Sent By hmoser Date 2009-11-10 Time 09:49 Rev Time 0.00
Received By hmoser Date 2009-11-10 Time 09:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-12-22 Cont ID  
Sent By kstevens Date 2009-12-22 Time 10:08 Rev Time 0.00
Received By kstevens Date 2009-12-22 Time 10:08 Sent To  
Notes
2009-12-22 10:08:39RESTAMP - NEW SHEET.

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-10-01 Cont ID  
Sent By kstevens Date 2009-10-01 Time 16:30 Rev Time 0.00
Received By kstevens Date 2009-10-01 Time 16:30 Sent To  
Notes
2009-10-01 16:31:24SEPARATE GAS PERMIT/PLANS REQUIRED.

Review Stop Z ZONING
Rev No 2 Status P Date 2009-12-28 Cont ID  
Sent By jroach Date 2009-12-28 Time 16:06 Rev Time 0.00
Received By jroach Date 2009-12-28 Time 16:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-10-12 Cont ID  
Sent By jroach Date 2009-10-12 Time 20:03 Rev Time 0.00
Received By jroach Date 2009-10-12 Time 20:03 Sent To  
Notes
2009-10-12 20:14:21ZONING PLAN REVIEW
  
 PERMIT NO.: 09090649
 ADDRESS: 521 33RD STREET
 CONTRACTOR/CONTACT: BOXTER TAYLOR
 TELEPHONE NO.: 561.626.2778
 SCOPE OF REVIEW: NEW SINGLE-FAMILY RESIDENCE.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) ROOF OVERHANGS SHALL NOT EXCEED THREE (3) FEET. SOME
 OVERHANGS ARE SHOWN AT SIX (6) INCHES???IS THIS THE
 CASE FOR ALL SIDES? PLEASE CLARIFY.
  
 2) ALL MECHANICAL EQUIPMENT SHALL BE LOCATED ON THE
 SITE PLAN AND SETBACKS TO ALL PROPERTY LINES SHALL BE
 PROVIDED. IT APPEARS THAT THE A/C EQUIPMENT WILL BE
 LOCATED ON THE WEST SIDE OF THE STRUCTURE???IF SO, IT
 SHALL BE NO CLOSER THAN SIX (6) FEET TO THE PROPERTY
 LINE.
  
 3) IT APPEARS ON THE SITE PLAN THAT A FENCE IS SHOWN
 ALONG ALL SIDE OF THE PROPERTY LINE. PLEASE CLARIFY. A
 SEPARATE PERMIT WILL BE REQUIRED FOR ANY AND ALL
 FENCES.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved