Plan Review Details - Permit 09090594
Plan Review Stops For Permit 09090594
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-11-09 Cont ID  
Sent By jwitmer Date 2009-11-09 Time 16:57 Rev Time 1.00
Received By jwitmer Date 2009-11-09 Time 15:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-10-08 Cont ID  
Sent By jwitmer Date 2009-10-08 Time 12:00 Rev Time 4.00
Received By jwitmer Date 2009-10-08 Time 08:00 Sent To  
Notes
2009-10-08 11:27:36BUILDING PLAN REVIEW
 PERMIT: 09090594
 ADD: 525 OKEECHOBEE BLVD SUITE# 1600
 CONT: TO BE DETERMINED
 TEL: (561)650-0900
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1) BOTH SHEETS LS-1 AND A-1.0 INDICATE THE CORRIDORS
 WITH 1 HR TENANT SEPERATION WALLS WITH THE EXCEPTION OF
 DOOR 1606 AND GLASS ENCLOSURE SURROUND.
 PLEASE PROVIDE ANALYSIS AS WHY THIS SECTION WOULD NOT
 BE REQUIRED TO MEET THE SAME TENANT SEPERATION 708.1(7)
 & 715.TABLE 715.4 & 715,4,3.2. THE BUILDING OFFICIAL
 INTERPETS THE COMMON AREA AS A SEPERATE TENANCY
 THEREFORE REQUIRING TENANT SEPERATION ON BOTH SIDES OF
 THE CORRIDOR.
  
 2) PROVISO: ACCESS CONTROLED EGRESS DOORS PLEASE
 PROVIDE COMPLIANCE WITH SECTION 1008.1.3.4. PLEASE
 PROVIDE MANUFACTURERS SPEC BY FRAMING INSPECTION.
  
 3) PROVSO: SHEET A-1.0 BOARD ROOM A & B ROOMS 1646&
 1647 IT APPEARS TO BE A OPERABLE PARTITION BUT NO
 PRODUCT INFORMATION HAS BEEN PROVIDED, THIS MAY BE
 SUPPLIED AT A LATER DATE ONCE THE PERMIT IS ISSUED BUT
 WILL BE REQUIRED BEFORE THE FRAMING INSPECTION. DETAIL
 17/ A-6.1 ADDITIONAL SHOP DRAWING WILL BE PROVIDED BY
 SKYFOLD PANEL SYSTEMS. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 4) SHEET A-1.0 ROOM 1616 INDICATES A HIGH DENSITY FILE
 SYSTEM, HAS THE FLOOR SYSTEM BEEN DESIGNED FOR THE
 HEIVER LIVE LOADS CONSIDERED FOR THIS FLOOR AREA?
 TABLE 1607.1(26). COMPLIED SEE PERMIT 09080342.
  
 6) PROVISO: SHEET A-3.1 FINISH SCHEDULE INDICATES THE
 USE OF CARPET WITHIN THE EXIT ACESS CORRIDORS, PLEASE
 PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING THAT
 THE CARPET COMPLIES WITH SECTION 804.4.1 MINIMUM
 CRITICAL RADIANT FLUX, FLOOR COVERING MATERIALS SHALL
 COMPLY WITH THE DOC FF-1 "PILL TEST" (CPSC 16 CFR, PART
 1630) CLASS II MATERIAL. THIS INFORMATION WILL BE
 REQUIRED BY THE TIME OF FRAMING INSPECTION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-11-18 Cont ID  
Sent By dpalmer Date 2009-11-18 Time 16:01 Rev Time 0.00
Received By dpalmer Date 2009-11-18 Time 16:01 Sent To  
Notes
2009-11-18 16:01:42REDLINED PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-11 Cont ID  
Sent By dpalmer Date 2009-10-11 Time 12:36 Rev Time 0.00
Received By dpalmer Date 2009-10-11 Time 12:36 Sent To  
Notes
2009-10-11 12:37:09 
  
 ** DENIED **
  
 ** SUBMITTED FOR PERMIT APPLICATION BEFORE OCTOBER 1ST,
 2009 UNDER TBD ONLY. NO LICENSED CONTRACTOR HAS
 APPLIED.
  
  
 1) NOTE: PLEASE SUBMIT MINIMUM PRESCRIPTIVE FOR COMMON
 AREA CORRIDOR. IT IS NOT PERMITTED TO TRADE OFF TENANT
 SPACE ALLOWANCES WITH THE TENANT SPACE. ONLY CORRIDORS
 LOCATED IN THE TENANT SPACES ARE TRADABLE FOR OTHER
 SPACES WITHIN TENANT. SEE 13-415.AB.5. THE PREVIOUS
 TRADE OFF SECTION OF THE CODE WAS COMPLETELY REMOVED
 WHICH STATED TRADE OFFS OF SPACES WERE OK AS LONG AS
 THE TOTAL ALLOWANCE WAS NOT EXCEEDED. THIS OFFICE HAS
 SPOKEN WITH THE STATE AS THE FLA COM PROGRAM WILL STILL
 ALLOW IT. ALSO SPOKE TO THE STATE ABOUT COMMON AREAS
 WHICH WOULD BE REQUIRED TO BE SEPARATED. THE CIRCUITS
 FOR COMMON AREAS ARE SHOWN TO PANEL L413A WHICH PER
 RISER IS A HOUSE PANEL.
 **PLEASE NOTE BELOW FOR UPDATED HOUSE PANEL SCHEDULE
 NEEDED.
 SPACE 1687 IN THE IDR IS MISSING FIXTURE M4. 3-32W
  
  
 2) NOTE: PLEASE SUBMIT REVISED PANEL SCHEDULE FOR L413A
 408.4
  
 3) NOTE: POWER PLANS CONTAIN A NOTE #8 FOR RECEPTACLES
 IN COMMON AREA WHICH STATES TO CIRCUIT TO LOCAL
 CIRCUIT. THIS IS NOT ENOUGH INFORMATION. IT IS NOT
 PERMISSIBLE TO CONNECT TO ANY EXISTING CIRCUIT IN THIS
 AREA.
 LOADS ON CIRCUITS, CIRCUITS FROM EMERGENCY SYSTEMS ARE
 NOT PERMITTED TO FEED GENERAL PURPOSE RECEPTACLES. IF
 THIS HAD BEEN THE ONLY COMMENT A PROVISO COULD BE GIVEN
 TO FIND OUT CIRCUIT BEFORE INSPECTION AND TO SUBMIT
 REVISED PLANS. HOUSE PANELS AND CIRCUITS IN THESE AREAS
 SHOULD ALREADY PROVIDE AN ESTIMATED PANEL OR CIRCUIT.
 210.20,210.21,210.24, 408.4, 220.44 ETC
  
 4) NOTE: PLEASE PLACE NOTE ON SHEETS E3.1 AND 3.2. NO
 WIRING METHODS PERMITTED PER NEC 645 PERMITTED IN ROOMS
 1674, 1672. (OR WORDS TO THAT AFFECT). THESE ARE NOT IT
 ROOMS, WALLS ARE NOT RATED, DOOR(S) ARE NOT RATED ETC.
 WIRING METHODS PERMITTED IN NEC 645 ARE LESS STRINGENT
 THAN WIRING METHODS OF OTHER CHAPTERS IN THE NEC.
 PLEASE VERIFY WITH OWNER'S IT PERSONNEL THAT THESE
 WIRING METHODS IN 645 ARE NOT GOING TO BE UTILIZED.
 IF WIRING METHODS IN NEC 645 ARE DESIRED, THEN ALL OF
 645.4 1-5 MUST BE MET ALONG WITH NFPA-75 AS ADOPTED PER
 FAC 69A-3.012.
  
 5) NOTE: PLEASE COORDINATE PANELS AND RISER. BELOW ARE
 SOME ITEMS WHICH DO NOT CORRELATE.
 A) PLEASE SEE E 5.1 AS BOTH CIRCUITS LABELED TO L14D
 AND SR14A ARE INDICATING CIRCUITING FROM A L13C PANEL.
 HOWEVER THERE IS NO PANEL L13C ON RISER OR IN PANEL
 SCHEDULES. (MISPRINT?)
  
 B) SEE RISER ON SAME SHEET AS THE CIRCUIT LABELED FROM
 PANEL H14A FEEDING TRANSFORMER IS SHOWN TO A PANEL H13A
 WHICH DOES NOT EXIST AS PART OF THIS PLAN. ( MISPRINT)
  
 C) SEE RISER ON THIS SAME SHEET WHICH INDICATES
 T13A-1L, WHEN TRANSFORMER SCHEDULE IS T14A-1L.
 (MISPRINT)
  
 D) SEE RISER TRANSFORMER IS LABELED AS T13A AND
 TRANSFORMER LEGEND IS FOR T14A. (MISPRINT)
  
 RECEPTACLE LOCATED IN HALL IN THE NORTH AND WEST
 CORRIDOR OF 1606 IS LABELED TO A CIRCUIT FOR NE
 RECEPTACLES. THIS CAN BE ADJUST NOW OR FOR FINAL PLANS.
 408.4, FBC ADMIN 106.1.1,106.5 FOR CLARITY AND
 COORDINATION OF RECORD PLANS.
  
 6) NOTE: NO ACCESS CONTROL SYSTEM PART OF THE
 ELECTRICAL REVIEW. PLANS MAY BE FOR ELECTRICAL J-BOX
 LOCATIONS ONLY. SEPARATE PLANS AND PERMIT FOR ACCESS
 CONTROL SYSTEM IS REQUIRED. NFPA-101 CHAPTER 7, 7.2 FOR
 EGRESS CONTROLS.
  
 ** LOW VOLTAGE FOR DATA, PHONE ARE UNDER SEPARATE
 PERMIT. MAY REFERENCE THESE PLANS FOR THESE SYSTEMS.
 ** LOW VOLTAGE FOR FIRE ALARM SYSTEMS UNDER SEPARATE
 PERMITS. BASE PLANS APPEAR TO SHOW COMPLIANCE WHICH IS
 UNDER ELECTRICAL REVIEW FOR ADA AND BASE SYSTEM. REVIEW
 BY FIRE MARSHALL IS STILL TO BE DONE.
  
 ** IT IS IMPORTANT TO KNOW THAT AS NO MINIMUM PLANS
 WERE SUBMITTED FOR REVIEW THE FOLLOWING REVIEW MAY
 CREATE NEW COMMENTS WHICH CAN NOT BE MADE AT THIS TIME.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-11-17 Cont ID  
Sent By mawillia Date 2009-11-17 Time 11:25 Rev Time 0.00
Received By mawillia Date 2009-11-17 Time 10:54 Sent To  
Notes
2009-11-17 11:25:27*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS LS-1.0, A-1.1, A-2.0, E2.1,
 FA0.1, FA2.1, FS0.1, AND FS2.1 WERE STAMPED, INITIALED,
 AND DATED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-10-23 Cont ID  
Sent By mawillia Date 2009-10-23 Time 12:58 Rev Time 0.00
Received By mawillia Date 2009-10-22 Time 14:49 Sent To  
Notes
2009-10-23 12:24:44*****DENIED*****
  
 1. ON SHEET S-1, A PICTORIAL DEPICTING THE 15TH LEVEL
 PARTIAL FRAMING PLAN IS SHOWN. PLEASE EXPLAIN HOW THIS
 CORRESPONDS WITH 16TH FLOOR/SUITE 1600'S SCOPE OF WORK.
  
 2. NO EXIT LIGHTS AND/OR EMERGENCY LIGHTS SHOWN FOR THE
 VACANT SPACE (1603). REFERENCE LS-1.0 AND E2.1 SHEETS.
  
 3. ANY DOOR WHICH OPENS DIRECTLY INTO AN EXIT ACCESS
 CORRIDOR SHALL COMPLY WITH THE REQUIREMENTS IN
 ACCORDANCE WITH NFPA 80 AND SHALL BE WITH POSITIVE
 LATCH AND CLOSER.
  
 4. SPECIFY INTERIOR FLOOR FINISH IN EXIT ENCLOSURES IN
 TERMS OF CLASS I OR CLASS II.
  
 5. NO FIRE ALARM DEVICES SHOWN IN THE VACANT SPACE
 (1603) ON FA2.1 SHEET.
  
 6. NO SPRINKLER HEADS SHOWN IN THE VACANT SPACE (1603)
 ON FS2.1 SHEET.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE ARESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-11-03 Cont ID  
Sent By btrobaug Date 2009-11-03 Time 10:59 Rev Time 0.00
Received By btrobaug Date 2009-11-03 Time 10:59 Sent To  
Notes
2009-11-04 09:02:21SEE C--14
2009-11-03 11:31:43 
 C 15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-11-03 Cont ID  
Sent By btrobaug Date 2009-10-26 Time   Rev Time 0.00
Received By btrobaug Date 2009-09-30 Time 17:28 Sent To PC
Notes
2009-09-30 17:28:13C34
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-11-16 Cont ID  
Sent By rregueir Date 2009-11-16 Time 11:40 Rev Time 0.00
Received By rregueir Date 2009-11-16 Time 11:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-10-26 Cont ID  
Sent By rregueir Date 2009-10-26 Time 20:55 Rev Time 0.00
Received By rregueir Date 2009-10-26 Time 20:39 Sent To  
Notes
2009-10-26 20:55:41REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. MEDIUM CONFERENCE ROOM 1678 IS SHOWN WITH FULL
 HEIGHT PARTITIONS. THE LOCATION OF THESE PARTITIONS
 WOULD ISOLATE THE SMOKE CONTROL DUCT COMING FROM THE
 ADJACENT SHAFT INTO THE TENANT SPACE. THIS SMOKE
 CONTROL DUCT SERVES THE ENTIRE FLOOR AND CANNOT BE
 ISOLATED FROM THE REST OF THE FLOOR BY THESE
 PARTITIONS. SHOW HOW THIS INTERIOR DESIGN WILL NOT
 IMACT THE EXISTING SMOKE CONTROL SYSTEM.
  
 2. FLOOR PLAN SHOWS 18X12 SUPPLY DUCT PENETRATING WALL
 BETWEEN GALLERY 1687 AND LOBBY 1601. SEE BUILDING PLAN
 REVIEW COMMNETS REGARDING TENANT SEPARATION
 REQUIREMENTS. SHOW PROTECTION OF THE DUCT PENETRATION
 AT THIS LOCATION IN ACCORDANCE WITH FBC-M 607.5 AND
 FBC-M 607.8.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-10-06 Cont ID  
Sent By kstevens Date 2009-10-06 Time 09:07 Rev Time 0.00
Received By kstevens Date 2009-10-05 Time 16:59 Sent To  
Notes
2009-10-06 09:08:23 
  
 PASSED/PROVISO:
 FLOOR SINKS OR HUB DRAINS REQUIRED FOR INDIRECT WASTE.
 SECTIONS 802.3 & 802.3.2.

Review Stop Z ZONING
Rev No 1 Status N Date 2009-10-13 Cont ID  
Sent By eschneid Date 2009-10-13 Time 16:03 Rev Time 0.10
Received By eschneid Date 2009-10-13 Time 16:02 Sent To  
Notes
2009-10-13 16:03:35INTERIOR BUILD OUT - UPPER FLOOR.