Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-12-16 Cont ID  
Sent By jwitmer Date 2009-12-16 Time 14:48 Rev Time 0.50
Received By jwitmer Date 2009-12-16 Time 14:13 Sent To  
Notes
2009-12-16 14:41:53REVISION# 5 10-28-09

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-10-08 Cont ID  
Sent By jwitmer Date 2009-10-08 Time 16:46 Rev Time 0.33
Received By jwitmer Date 2009-10-08 Time 16:46 Sent To  
Notes
2009-10-08 16:58:38BUILDING PROVISO:
  
 707.14.1 ELEVATOR LOBBY
  
 2007 EXISTING BUILDING CODE FBC
 703.2.1 EXISTING VERTICAL OPENINGS.
 ALL EXISTING INTERIOR VERTICAL OPENINGS CONNECTING TWO
 OR MORE FLOORS SHALL COMPLY WITH
 THE APPROPRIATE SECTIONS OF THE FLORIDA FIRE PREVENTION
 CODE.
  
 2007 FBC W/2009 SUPPLEMENTS
 707.14.1 PROVIDE CODE COMPLIANT DETAILS TO THE A.H.J.
 BEFORE THE FRAMING INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-09-29 Cont ID  
Sent By jwitmer Date 2009-09-29 Time 14:13 Rev Time 1.00
Received By jwitmer Date 2009-09-29 Time 14:13 Sent To  
Notes
2009-09-29 14:14:15BUILDING PROVISO:
  
 707.14.1 ELEVATOR LOBBY
  
 2007 EXISTING BUILDING CODE FBC
 703.2.1 EXISTING VERTICAL OPENINGS.
 2007 FBC W/2009 SUPPLEMENTS
 707.14.1 PROVIDE CODE COMPLIANT DETAILS TO THE A.H.J.
 BEFORE THE FRAMING INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-09-23 Cont ID  
Sent By jwitmer Date 2009-09-23 Time 17:59 Rev Time 1.00
Received By jwitmer Date 2009-09-23 Time 17:00 Sent To  
Notes
2009-09-23 17:57:13BUILDING PLAN REVIEW
 PERMIT: 09090526
 ADD: 515 N FLAGLER DR SUITE1450
 CONT: FISHER CONTRACTING CORP
 TEL: (561)691-4716
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 SEPT 23/2009
  
 1) THE COVERSHEET INDICATES THIS BUILDING TO BE A TYPE
 II-B PLEASE REVISE TO A TYPE I-A SEE TABLE 503 AND CODE
 COMMENTARY FIGURE 600 CONSTRUCTION TYPE COMPARISION
 FROM THE 2001 FBC.
  
 2) SHEET D-1.0 14TH FLOOR DEMO INDICATES THE REMOVAL OF
 ELEVATOR LOBBY DOORS. UNDER THE 2007 FBC/ 2009
 SUPPLEMENTS SECTION 707.14.1 ELEVATOR LOBBIES WOULD BE
 REQUIRED IF THEY ARE ALREADY INSTALLED. THE OTHER
 OPTION IS TO SEE IF THE DESIGNER OF RECORD WOULD LIKE
 TO MEET ONE OF THE EXCEPTIONS OR LOOK INTO OTHER SMOKE
 CONTAINMENT POSSIBLIITIES UNDER SECTION 104.11
 ALTERNATE MATERIALS, DESIGN AND METHODS OF CONSTRUCTION
 AND EQUIPMENT.
  
 NOTE: A MEETING IS SET WITH KEITH SPINA FOR MONDAY SEPT
 28/ 2009 @ 1:30PM TO DISCUSS ELEVATOR LOBBIES.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-12-02 Cont ID  
Sent By dpalmer Date 2009-12-02 Time 14:53 Rev Time 0.00
Received By dpalmer Date 2009-12-02 Time 14:53 Sent To  
Notes
2009-12-02 14:54:45SHEET 5.1 NOT STAMPED AS IT WAS NOT REVISED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-10-14 Cont ID  
Sent By dpalmer Date 2009-10-14 Time 12:41 Rev Time 0.00
Received By dpalmer Date 2009-10-11 Time 11:06 Sent To PC
Notes
2009-10-11 13:00:57CONTRACTOR MADE TWO SETS ON 10/13

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-09-25 Cont ID  
Sent By dpalmer Date 2009-09-25 Time 19:18 Rev Time 0.00
Received By dpalmer Date 2009-09-25 Time 19:18 Sent To  
Notes
2009-09-25 19:18:35 
  
  
 ** DENIED PLANS **
  
 **SUITE 1450 UNDER 09090526
 ** SUITE 1500 UNDER 09090527
  
 ** TWO PERMIT APPLICATIONS SUBMITTED ALTHOUGH ONLY ONE
 SET OF PLANS WERE SUBMITTED FOR BOTH FLOORS/SUITES.
  
  
 1) NOTE: THE SUBMITTED LIGHTING CALCULATIONS FOR ABOVE
 SUITE ARE MISSING SOME SPACES/LIGHTING AND SOME
 COORDINATION IS NEEDED FOR NUMBER OF FIXTURE, TYPES OF
 FIXTURE/WATTAGE OF FIXTURES.
 A) PLEASE SEE AREAS 1401,1411, 1400 ARE MISSING.
  
 B) PLEASE SEE AREA 1412 FOR EXAMPLE WHICH INDICATES
 5-32 WATT FIXTURES AND 2-56W FIXTURES. BASED ON THE
 FIXTURE LEGEND THESE ARE NOT CORRECT.
 BASED ON THE FIXTURE LEGEND THERE WOULD BE 2-32W, 3-56W
 AND 1-14W. IT IS ACTUALLY LESS THAN SHOWN. HOWEVER
 RECORD PLANS FOR THE NUMBER AND TYPE OF FIXTURES NEED
 TO BE CORRECTED.
  
 C) PLEASE SPACE 1512 FOR EXAMPLE; CALCULATIONS STATE
 17-32 WATT FIXTURES. HOWEVER BASED ON THE PLANS AND
 FIXTURE LEGEND THERE ARE MORE THAN ONE TYPE OF FIXTURE
 IN THIS AREA. IN FACT THERE ARE THREE DIFFERENT TYPES
 OF FIXTURES. SOME FIXTURES WITH LESS WATTAGE AND SOME
 WITH MORE WATTAGE. SPECIFICALLY G FIXTURES WHICH ARE
 NOT 32 WATT AS LISTED THEY ARE 50W. ALSO FIXTURE E
 WHICH IS NOT 32 IT IS 13W.
  
 D) PLEASE SEE ROOM 1513 FOR EXAMPLE: CALCULATIONS
 INDICATE 23-32W FIXTURES. HOWEVER BASED ON PLANS AND
 FIXTURE LEGEND THERE ARE FIXTURES SUCH AS 4-G FIXTURES
 WHICH ARE 50WATT FIXTURES. THE COUNT OF THE 32W F/F1
 FIXTURES IS 22. THE ACTUAL WATTAGE IN THIS ROOM IS
 HIGHER. PLEASE ADJUST.
  
 *** KEEP IN MIND TRADE OFFS ARE ONLY PERMITTED WITHIN
 THE TENANT SPACE. IT IS NOT PERMITTED TO TRADE COMMON
 AREA HALLWAY AREAS WITH LIGHTING WITHIN THE TENANT
 SPACE.
 13-415.AB.5, 13-415.B.1. SEE APPENDIX B
  
 2) NOTE: PLEASE GO THROUGH PLANS AND COORDINATE ALL
 CIRCUITING SO THAT LOADS SHOWN ON THE NUMBER OF
 RECEPTACLES CAN BE REVIEWED FOR CODE COMPLIANCE.
  
 A) EXAMPLE: PLANS SHOW CIRCUIT JBL1-18 IN AREA 1533 AS
 A DEDICATED RECEPTACLE HOWEVER PER THE SAME PANEL
 SCHEDULE JBL1-18 STATES RECEPTACLES IN ROOM 1520.
 ROOM 1520 INDICATES CIRCUIT AS JBL1-29
  
 B) EXAMPLE: ROOM 1520 ABOVE NOTES JBL1-29 YET WHEN YOU
 REVIEW THIS CIRCUIT ON PANEL SCHEDULE IT STATES ROOM
 1505, 1506.
  
 C) EXAMPLE: ROOM 1505 AS NOTED ABOVE IS THE WOMEN'S
 BATHROOM HOWEVER BASED ON THE PLANS THERE IS NO
 ELECTRICAL RECEPTACLES IN THIS AREA. ROOM 1505 IS
 COMMON AREA WHY IS THIS BEING FED FROM TENANT
 ELECTRICAL PANEL?
 ROOM 1506 AS NOTED ON PANEL SCHEDULE IS ACTUALLY THE
 WEST STAIRWAY AS SHOWN ON E2.2??
  
 D) EXAMPLE: PANEL JBL1 IS A TENANT PANEL. PLEASE
 EXPLAIN CIRCUITS 1,3,5,7,9 ETC WHICH ARE ALL SHOWN AS
 CIRCUITS IN THE TENANT PANEL YET PER THE PLANS ALL THE
 SPACES/ROOM LISTED ARE IN THE COMMON AREAS.
  
 E) EXAMPLE: PLEASE SEE PANEL L-14 CIRCUIT 11 WHICH IS
 LISTED ON THE TENANT PANEL SCHEDULE FEEDING SPACE 1405,
 HOWEVER SPACE 1405 ON THE PLANS IS ACTUALLY COMMON AREA
 BATHROOM WHICH DOES NOT INDICATE ANY ELECTRICAL.
  
 F) EXAMPLE: L14-4 ON PLANS WHICH IS LOCATED IN ROOM
 1420 IS ACTUALLY LISTED IN ROOM 1413 ON PANEL SCHEDULE.
  
 G) EXAMPLE: L14-6 ON PLANS WHICH IS LOCATED IN ROOM
 1420 IS ACTUALLY LISTED IN ROOM 1413 ON PANEL SCHEDULE.
  
 H) EXAMPLE: L14-8 ON PLANS WHICH IS LOCATED IN ROOM
 1420 IS ACTUALLY LISTED IN ROOM 1413 ON PANEL SCHEDULE.
  
 I) EXAMPLE: PLEASE SEE PANEL JBL2 CIRCUITS 19 AND 21.
 BOTH OF THESE ARE INDICATING RECEPTACLES IN ROOM/AREA
 102, HOWEVER ROOM 1502 DOES NOT SHOW ANY ELECTRICAL
 RECEPTACLES AS THIS IS THE VESTIBULE AREA.
  
 J) EXAMPLE: L14-7 SHOWN ON PLANS IN ROOM 1422 YET PANEL
 SCHEDULE INDICATES ROOM 1404 WHICH IS COMMON AREA.
  
 K) EXAMPLE: L14-9 SHOWN ON PLANS IN ROOM 1422 YET PANEL
 SCHEDULE INDICATES ROOM 1404 WHICH IS COMMON AREA.
  
 L) EXAMPLE: L14-12 SHOWN ON PLANS IN ROOM 1422 YET
 PANEL SCHEDULE INDICATES ROOM 1404 WHICH IS COMMON
 AREA.
  
 ETC.
  
  
 ****** IMPORTANT***
 THESE ARE ONLY SOME EXAMPLES OF CIRCUITING FOR 1450 AND
 1500 WHICH DO NOT COORDINATE. PLEASE GO THROUGH ALL
 CIRCUITING AS THERE ARE NUMEROUS OTHERS.
 LOADS ON CIRCUITS, LOADS ON PANELS AND LOADS ON SERVICE
 CAN NOT BE VERIFIED.
 SIZING OF OVER CURRENT PROTECTION FOR CIRCUITS ALSO CAN
 NOT BE VERIFIED.
  
 ** TENANT SPACES SHALL BE CIRCUITED FROM THEIR PANELS
 AND COMMON AREAS SHOULD BE CIRCUITED FROM HOUSE PANELS.
  
 240.4,310.16.220.44,220.42, 240.24A, 240.24B ETC
  
 3) NOTE: PLEASE EXPLAIN RISER. RISER INDICATES THE JBH
 PANEL FED FROM GUTTER WITH TENANT METER HOWEVER THE
 FEED TO TRANSFORMER WHICH FEEDS ALL TENANT PANELS JBL1,
 2 AND 3 YET THERE IS NO METER ON RISER?
 ALSO AS NOTED ABOVE FOR CIRCUITING CIRCUITS SUCH AS
 H14-5 STATES CORRIDOR LIGHTING HOWEVER THIS IS
 HOUSE/COMMON AREA? THERE ARE ALREADY HOUSE/COMMON AREA
 PANELS SHOWN ON RISER.
 AS NOTED ABOVE WITH THE CIRCUITING ETC NOT COORDINATED
 FOR TENANTS AND COMMON AREAS, REVIEW AND CONFIRMATION
 OF LOADS SHOWN ARE UNKNOWN FOR CODE COMPLIANCE.
  
 NEC 220,215, 210, 240, 310, ETC GIVEN AS GENERAL
 CHAPTERS UNTIL PLANS ARE COMPLETE WITH ITEMS ABOVE.
  
  
  
  
  
 ** IMPORTANT**
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-12-08 Cont ID  
Sent By mawillia Date 2009-12-08 Time 13:06 Rev Time 0.00
Received By mawillia Date 2009-12-08 Time 12:36 Sent To  
Notes
2009-12-08 12:43:47*****REVISION, DATED 10/28/09, APPROVED*****
  
  
 REVISED PLAN SHEETS LS-1, A-1.0, E2.1, FA0.1, AND FA2.1
 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-10-05 Cont ID  
Sent By mawillia Date 2009-10-05 Time 15:14 Rev Time 0.00
Received By mawillia Date 2009-10-05 Time 14:26 Sent To  
Notes
2009-10-05 15:09:39*****APPROVED*****
  
  
 PLAN SHEETS LS-1, A-1.0, E2.1, FA0.1, AND FA2.1 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-11-09 Cont ID  
Sent By jgomez Date 2009-11-09 Time 10:05 Rev Time 0.00
Received By jgomez Date 2009-11-09 Time 10:05 Sent To  
Notes
2009-11-09 10:05:55SENT TO BOX #C24.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-10-08 Cont ID  
Sent By kstevens Date 2009-10-08 Time 08:30 Rev Time 0.00
Received By kstevens Date 2009-10-08 Time 08:30 Sent To  
Notes
2009-10-08 08:38:54SENT TO B-7.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-10-05 Time   Rev Time 0.00
Received By lmartine Date 2009-09-23 Time 17:11 Sent To  
Notes
2009-09-23 17:16:06TRY B--7
2009-09-23 17:11:50R--7

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2009-10-14 Cont ID  
Sent By dpalmer Date 2009-10-14 Time 12:42 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-12-07 Cont ID  
Sent By rregueir Date 2009-12-07 Time 18:42 Rev Time 0.00
Received By rregueir Date 2009-12-07 Time 18:40 Sent To  
Notes
2009-12-07 18:41:54REVISED M0.1, M2.1, M2.1A, M2.2, M2.2A
 CANNOT IDENTIFY REVISIONS BY DELTA # BECAUSE THE
 REVISION HISTORY IN THE TITLE BLOCK DOES NOT MATCH THE
 REVISION CLOUDS SHOWN ON THE PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-09-24 Cont ID  
Sent By rregueir Date 2009-09-24 Time 18:11 Rev Time 0.00
Received By rregueir Date 2009-09-24 Time 18:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-11-18 Cont ID  
Sent By kstevens Date 2009-11-18 Time 15:53 Rev Time 0.00
Received By kstevens Date 2009-11-18 Time 15:53 Sent To  
Notes
2009-11-18 15:53:42REVISION OK -- SHT P.01 ADDRESSING PROVISO.

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-09-30 Cont ID  
Sent By kstevens Date 2009-09-30 Time 17:43 Rev Time 0.00
Received By kstevens Date 2009-09-30 Time 17:42 Sent To  
Notes
2009-09-30 17:45:37 
  
  
 PASSED/PROVISO:
  
 FULL OPEN VALVE REQUIRED FOR WATER HEATER. SECTION
 606.1(7).
 WATER HAMMER ARRESTOR SHALL BE LOCATED NEAR THE
 FIXTURE, NOT IN THE CEILING. PDI-WH 201.
 THE DRAINS FROM THE DISH WASHER & ICE MAKER SHALL
 CONNECT UPSTREAM OF THE TRAP. SECTION 1002.1.
  
  
  
  
 .