2009-09-24 07:09:20 | PROVISO - SHUTTER PERMIT ONLY |
| WINDOW PERMIT REQUIRED |
| |
| |
| |
| ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| |
| WINDOW PRODUCT APPROVALS RETURNED TO CONTRACTOR AND |
| REMOVED FROM SCOPE OF WORK |
| |
| 1. THIS PROJECT IS LOCATED IN EXPOSURE "C", SEE NEW |
| DEFINITION OF EXPOSURE CLASSIFICATIONS, FBC R 301, |
| FBC1609, ASCE7-05. THERE IS A DRAFT COMMENTARY WHICH |
| YOU MAY FIND HELPFUL POSTED ON THE AAF ORGANIZATION |
| WEBSITE. |
| 2. DUE TO THE INCREASE IN PRESSURES, IT IS NOT CLEAR |
| WHETHER THE WINDOW PRODUCT PROPOSED COMPLIES WITH THE |
| REQUIRED DESIGN PRESSURES. ALSO NOTE THAT CONTRACTOR |
| HAS HIGHLIGHTED PRESSURES FOR A 48X44 WINDOW, BUT THE |
| OPENINGS ARE 57X46. THEREFORE THE COLUMN WHICH SHOULD |
| BE IMPLEMENTED IS 63"X50.625". |
| 3. THIS IS NOT WITHIN THE SCOPE OF AN ALUMINUM |
| SPECIALTIES CONTRACTOR LICENSE. PLEASE APPLY FOR PERMIT |
| WITH THE GLAZING SPECIALTIES LICENSE. NOTE THAT IN THE |
| FUTURE YOU MAY REQUEST A SUBCONTRACTOR PERMIT WITH THE |
| APPROPRIATE LICENSE IN THE GREEN BOX AT THE BOTTOM |
| UNDER "BUILDING CONTRACTOR". THE TWO PERMITS (GLAZING |
| AND SHUTTER) WOULD THEN BE ISSUED TOGETHER. |
| |
| |