Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-10-20 Cont ID  
Sent By jwitmer Date 2009-10-20 Time 16:19 Rev Time 4.00
Received By jwitmer Date 2009-10-20 Time 12:02 Sent To  
Notes
2009-10-20 12:31:42BUILDING PLAN REVIEW
 PERMIT: 09090386
 ADD: 808 19TH ST
 CONT: SCALTIC USA, CORP
 TEL: (954)553-0554
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 OCT.20/ 2009
  
 1) SHEET# 1 CODE TABULATION INDICATES THIS DESIGN WAS
 TO THE 2007 FRC OR FLORIDA RESIDENTIAL CODE, PLEASE
 NOTE THE RESIDENTIAL CODE IS FOR ONE & TWO FAMILY
 STRUCTURES, NOT A 4 UNIT BUILDING. PLANS SUBMITTED FOR
 PERMIT (FIRST TIME REVIEW) AFTER MARCH 1ST, 2009 SHALL
 BE REVIEWED TO THE 2007 FBC BUILDING WITH 2009
 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT. 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST
 ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2A) 106.1.2* ADDITIONAL INFORMATION IS REQUIRED. THE
 PERMIT APPLICATION INDICATES INTERIOR REMODEL AS PER
 PLANS, SHEET# 2 DOES NOT INDICATE WHAT IS EXISTING AND
 NEW WORK, PLEASE PROVIDE EITHER IN DRAWINGS OR
 COMENTARY WORK TO BE COVERED UNDER THIS PERMIT. THE
 VALUE OF WORK TO BE COVERED UNDER THIS PERMIT IS VALUED
 AT $21,800.00 DOLLARS, THIS MAY BE LOW ONCE THE
 DESCRIPTION OF PROJECT IS KNOWN.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2B) THE COVERSHEET INDICATES THIS TO BE A R OCCUPANCY
 PLEASE PROVIDE IF R2 TRANIENT OR NONTRANSIENT.
  
 2C) IS THIS A CHANGE OF OCCUPANCY OR SUB-CATEGORY?
  
 3) SHEET# 1, THE PLANS ARE NOT CLEAR AS TO EGRESS
 WINDOW PLACEMENT (SIZE), WINDOW # 2 & 7 A SH24 ONLY HAS
 4.57 CLEAR NET OPENING VENT SIZE.
 SEE SECTION 1026.2. THE SECOND FLOOR EGRESS WINDOWS
 (23, 4 & 26) WILL NEED A CLEAR VENT SIZE OF 5.7 FT.
 MINIMUM WINDOW SIZE IS A 245 OR 345.
  
 3A) WINDOWS WILL REQUIRE PRODUCT APPROVALS (2 COPIES)
 COMPLYING WITH 1609.1.4 PROTECTION OF OPENINGS IN
 WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT
 RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3
 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE
 BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT
 RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR
 PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996,
 OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN
 AS FOLLOWS: 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET
 (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF THE
 LARGE MISSILE TEST. 2. GLAZED OPENINGS LOCATED MORE
 THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE
 PROVISIONS OF THE SMALL MISSILE TEST.
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING OF PRODUCT
 TESTING REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 WINDOWS
 SWING GLAZED DOORS
 INSULATED METAL DOORS
 STORM SHUTTERS
 NO PRODUCT APPROVALS WERE SUBMITTED NOT ABLE TO CHECK
 PRESSURES.
  
 3B) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3C) THE PLANS ALSO DO NOT PROVIDE THE TYPE OF FRAMING
 MEMBER IS BETWEEN THE WINDOW SILL AND P/TAC UNIT.
 ADDITIONAL INFORMATION IS REQUIRED. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 3D) SHEET A4 WINDOW SCHDULE INDICATES THE USE OF STORM
 SHUTTES, PLEASE PROVIDE PRODUCT APPROVAL (2 SETS). RULE
 9B-73(31) ( E).
  
 3E) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4.
 FL BLD CODE 2004 SECTION 106.3.3, 1609.1.4, 1714.5.1 &
 EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A COMPLETE
 INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING
 SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS,
 WALL PRESSURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION TO FACILITATE
 PLAN REVIEW AND PERMIT ISSUANCE.
  
 3F) IN LEAU OF LARGE MIISSILE IMPACT RATED WINDOWS,
 STORM SHUTTERS MAY BE USED ON THE FIRST FLOOR IF:
 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE
 DEBRIS IMPACT PROTECTION.
  
 PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13
 RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES
 WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE
 SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT
 MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING IS DONE
 SUFFICIENTLY IN ADVANCE OF THE HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE
 ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST
 BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS
 FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY
 SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION
 OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 4) SHEET # 6 INDICATES WHAT APPEARS TO BE ELECTRIC
 RANGES BUT THE PANEL SCHEDULE ALSO INDICATES GAS
 RANGES, IF GAS, THE SMOKE ALARMS WILL ALSO NEED TO BE
 CARBON MONOXIDE DETECTORS ALSO FL S S 553.885
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-09-26 Cont ID  
Sent By dpalmer Date 2009-09-26 Time 12:01 Rev Time 0.00
Received By dpalmer Date 2009-09-26 Time 11:20 Sent To  
Notes
2009-09-26 12:01:27 
  
 ** DENIED **
  
 1) NOTE: PLANS NEED TO CONTAIN THE FOLLOWING ADOPTED
 RELEVANT CODES FOR DESIGN.
 2005 NFPA-70 ( NEC)
 2002 NFPA-72
  
 2) NOTE: PLANS INDICATE AN EQUIPMENT GROUNDING
 CONDUCTORS BEFORE THE FIRST MEANS OF DISCONNECT WHICH
 IS NOT PERMITTED.
 250.24, 250.6
  
 3) NOTE: PLANS DO NOT SHOW DISCONNECTING MEANS FOR THE
 CU. 440.11,440.12
  
 4) NOTE: PLANS SHOW SMOKE DETECTORS HOWEVER THESE SEEM
 THEY SHOULD BE SMOKE ALARMS. SMOKE DETECTORS ARE
 DEVICES WHICH ONLY DETECT AND DO NOT SOUND AN ALARM. IF
 THESE ARE ACTUALLY SMOKE DETECTORS THEN PLEASE SHOW
 LOCATIONS OF SOUNDING DEVICES/ALARMS. IF THESE ARE
 INDEED SMOKE ALARMS PLEASE ADJUST PLANS.
 NFPA-72 11.5.1, 11.8.3, R313.2.1
 ** SEE DEVICES LOCATED WITHIN 20FT OF COOKING
 APPLIANCES.
  
 5) NOTE: STAIR SWITCHES SHOULD BE INDICATED AS 3-WAY
 TYPE DEVICES. ALSO REAR STAIRS NEED TO HAVE A CONTROL
 AT BOTTOM OF STAIRS.
 210.70
  
 6) NOTE: PLEASE SEE 250.66 AS THE GROUNDING ELECTRODE
 CONDUCTOR IS SHOWN AS A #2 CONDUCTOR WHEN PER 250.66 IT
 IS REQUIRED TO BE LARGER. THIS GOES WITH COMMENT #2
 ABOVE.
 ** PLEASE CALL TO GO OVER.
  
 7) NOTE: THE RISER SEEMS TO INDICATE A 400AMP MAIN
 BEFORE METER BANK HOWEVER THIS IS NOT CLEAR. PLEASE
 VERIFY WITH FPL THE DISCONNECTING MEANS AHEAD OF
 METERING DEVICES.
 RISER SHOWS METERS AFTER SERVICE DISCONNECTING MEANS
 HOWEVER NO CT AHEAD OF MAIN.
 SEE 2009 FPL SERVICE STANDARDS.
  
 8) NOTE: AS ROOMS/AREAS ARE NOT IDENTIFIED ON PLANS THE
 FOLLOWING WILL BE NOTED AS BEST POSSIBLE.
 PLEASE SEE 210.52 AS THERE ARE SOME RECEPTACLE
 REQUIRED. SEE LEVEL 1 MAIN ENTRANCE FOR BOTH UNITS
 WHICH REQUIRES RECEPTACLE WITHIN 6FT OF DOOR.
 ALSO WALLS WITH MORE THAN 12FT WHICH REQUIRE ADDITIONAL
 DEVICES.
 SECOND LEVEL AT REAR WALL.
  
 9) NOTE: PLEASE SEE FBC 108.3. SCOPE OF WORK NEEDS TO
 INLCUDE ALL LABOR, MATERIALS, EQUIPMENT ETC FOR ALL
 TRADES INCLUDING DESIGN FEES EVEN IF ANY OF THESE ITEMS
 ARE OWNER SUPPLIED. AS ALL SUB CONTRACTORS ARE SIGNED
 ON, VALUE FOR ALL TRADES NEED TO BE INCLUDED.
  
  
  
 IMPORTANT**
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-10-19 Cont ID  
Sent By mawillia Date 2009-10-19 Time 15:48 Rev Time 0.00
Received By mawillia Date 2009-10-19 Time 15:08 Sent To  
Notes
2009-10-19 15:48:07*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 3. SHOW THE LOCATION OF THE PORTABLE 2A:10BC RATED FIRE
 EXTINGUISHERS WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 4. SMOKE ALARMS, NOT SMOKE DETECTORS, SHALL BE
 INSTALLED. PLEASE BE ADVISED THAT SMOKE DETECTORS ARE
 TIED INTO A BUILDING'S FIRE ALARM SYSTEM, WHEREAS,
 SMOKE ALARMS SHALL SOUND ONLY WITHIN AN INDIVIDUAL
 DWELLING UNIT , SUITE OF ROOMS, OR SIMILIAR AREA.
  
 5. DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL
 HAVE NOT LESS THAN A 20-MINUTE FIRE PROTECTION RATING.
  
 6. DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL BE
 SELF CLOSING AND SELF LATCHING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE THE COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-10-20 Cont ID  
Sent By jwitmer Date 2009-10-20 Time 16:20 Rev Time 0.00
Received By jwitmer Date 2009-09-17 Time 10:54 Sent To  
Notes
2009-09-22 10:57:45B-4

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-09-29 Cont ID  
Sent By rkussner Date 2009-09-29 Time 11:32 Rev Time 0.00
Received By rkussner Date 2009-09-29 Time 11:23 Sent To  
Notes
2009-09-29 12:05:02***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. SCOPE OF WORK INDICATES THAT THIS IS AN INTERIOR
 REMODEL BUT LANDSCAPE AND IRRIGATION PLANS HAVE BEEN
 SUBMITTED. PLEASE CHANGE SCOPE OF WORK TO INCLUDE
 EXTERIOR ON PERMIT.
  
 2. PURSUANT TO SECTION 04-442 (A), LANDSCAPE PLANS
 SHALL BE PREPARED BY PERSONS AS AUTHORIZED BY FLORIDA
 STATUTES CHAPTER 481, PT. II (LANDSCAPE ARCHITECTURE).
  
 3. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE
 EVALUATION OF OCMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE
 XERISCAPE DESIGN OPTIONS. THE CALXULATONS PROVIDED ARE
 INCONSISTENT WITH CITY STANDARDS.
  
 4. SUBMIT A CERTIFIED COST ESTIMATE THAT INCLUDES THE
 TOTAL COST OF ALL LANDSCAPE MATERIALS AND LABOR, BROKEN
 DOWN INTO UNIT COST.
  
 5. PURSUANT TO SECTION 94-448 (D)(2), THE LANDSCAPE
 PLAN SHALL CONTAIN ALL OF THE ITEMS LISTED IN THIS
 SECTION.
  
 6. IF THERE IS A LANDSCAPED RIGHT-OF-WAY, IT SHALL BE
 SODDED AND IRRIGATED.
  
 7. IF MULCH IS GOING TO BE COUNTED IN MEETING THE
 XERISCAPE REQUIREMENTS, IT MUST BE PLACED AT A DEPTH OF
 3 INCHES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-10-17 Cont ID  
Sent By rregueir Date 2009-10-17 Time 09:47 Rev Time 0.00
Received By rregueir Date 2009-10-17 Time 09:13 Sent To  
Notes
2009-10-17 09:47:35REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE 5 SHOWS TWO FLEX DUCTS PENETRATING THE ONE HOUR
 STAIR ENCLOSURE. FLEXIBLE DUCTS SHALL NOT PASS THROUGH
 ANY FIRE-RESISTANCE-RATED ASSEMBLY IN ACCORDANCE WITH
 FBC-M 607.7. ALSO, PENETRATIONS INTO AND OPENINGS
 THROUGH AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR
 REQUIRED EXIT DOORS IN ACCORDANCE WITH FBC-B 1020.1.2.
 AN INDEPENDENT SYSTEM IS REQUIRED IF VENTILATION IS TO
 BE PROVIDED IN THE STAIR ENCLOSRE IN ACCORDANCE WITH
 FBC-B 1020.1.3.
  
 2. SHOW CFM QUANTITY FOR 1ST FLOOR BATHROOM EXHAUST
 FANS IN ACCORDANCE WITH FBC-M TABLE 403.3. SHOW MEANS
 AND LOCATION OF EXHAUST DISCHARGE IN ACCORDANCE WITH
 FBC-M 401.4 AND 401.5.
  
 3. SHOW MEANS AND LOCATION OF CONDENSATE DISCHARGE FOR
 1ST AND 2ND FLOOR AC UNITS IN ACCORDANCE WITH FBC-M
 307.2.1.
 NOTE: PVC IS A COMBUSTIBLE MATERIAL AND SHALL NOT BE
 USED IN THE 2ND FLOOR RETURN AIR PLENUM CLOSET IN
 ACCORDANCE WITH FBC-M 602.2.1.
  
 4. PROVIDE MANUFACTURER'S DATA FOR THE PTAC UNITS ON
 FIRST FLOOR SHOWING THESE APPLIANCE ARE DESIGNED FOR
 WIND RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. ALSO
 PROVIDE AN ENGINEERED WIND RESISTANT INSTALLATION
 DETAIL FOR THE PTAC SLEEVE AS WELL AS FOR THE
 ATTACHMENT OF THE UNIT WITHIN THE SLEEVE.
  
 NOTE: CODE TABULATION INDICATES THIS PROJECT IS SUBJECT
 TO THE 2007 FLORIDA BUILDING CODE, RESIDENTIAL. THIS IS
 A MULTI-FAMILY BUILDING AND IS THEREFORE BEING REVIEWED
 FOR COMPLIANCE WITH THE REQUIREMENTS OF THE 2007
 FLORIDA BUILDING CODE, MECHANICAL AS WELL AS SECTION
 13-600 OF THE FLORIDA BUILDING CODE, BUILDING AND THE
 FLORIDA BUILDING CODE, EXISTING BUILDING.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-09-22 Cont ID  
Sent By kstevens Date 2009-09-22 Time 16:35 Rev Time 0.00
Received By kstevens Date 2009-09-22 Time 16:35 Sent To  
Notes
2009-09-22 16:36:31PASSED/PROVISO:
 ALL UNITS SHALL HAVE W/M CONNECTIONS. TABLE 403.1. --
 3" STACK FOR W/M REQUIRED. SECTION 406.3.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-09-30 Cont ID  
Sent By astelly Date 2009-09-30 Time 10:30 Rev Time 0.00
Received By astelly Date 2009-09-30 Time 10:30 Sent To  
Notes
2009-09-30 10:36:06AMY STELLY
 PLANNING AND ZONING
 561.822.1442
  
 ONLY THREE (3) RESIDENTIAL UNITS ARE ALLOWED ON THIS
 PROPERTY. PLEASE AMEND THE PLANS ACCORDINGLY.
 A CURRENT SURVEY OF THE PROPERTY MUST BE SUBMITTED WITH
 THE REVISED PLANS.
  