Plan Review Details - Permit 09090357
Plan Review Stops For Permit 09090357
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-10-19 Cont ID  
Sent By shill Date 2009-10-19 Time 11:32 Rev Time 0.00
Received By shill Date 2009-10-19 Time 11:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-09-17 Cont ID  
Sent By shill Date 2009-09-17 Time 18:50 Rev Time 0.00
Received By shill Date 2009-09-17 Time 18:50 Sent To  
Notes
2009-09-17 19:02:40****CORRECTIONS****
 ****REVISED 10/1/9****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SHEET T, EXISTING OCCUPANCY IS NOTED AS B, WASN'T
 THIS DESIGNED AS A LIVE/WORK SPACE, MIXED, B/R2? PLEASE
 REVISE AND NOTE THAT THIS IS A CHANGE OF OCCUPANCY, FBC
 CH 3, FBC EXISTING BUILDING CODE.
  
 2. FBC11-4.1.3(5), VERTICAL ACCESSIBILITY REQUIRED. IF
 AN EXCEPTION APPLIES, PLEASE SHOW COMPLIANCE WITH ALL
 RQUIREMENTS ON THE PLAN.
  
 3. FBC11-4.1.3(5), DECLARE SQUARE FOOT AREA FOR
 MEZZANINES.
  
 4. IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY,
 233-5025. PLEASE PROVIDE STAMPED PLAN AND RECEIPT.
  
 5. TOILET ROOM 204 TO BE ADAPTABLE. PLEASE SHOW BACKING
 DETAIL FOR FUTURE GRAB BARS, FBC11.4.1.3(11). (TURNING
 RADIUS NOT REQUIRED PER DW)
  
 6. THE MEZZANINE WAS REVIEWED AS RESIDENTIAL WHEN THE
 BUILDING WAS CONSTRUCTED. IT IS NOT CLEAR WHETHER THE
 CURRENT STAIRS, THEN ELIGIBLE TO BE BUILT UNDER
 RESIDENTIAL REQUIREMENTS, MEET REQUIREMENTS FOR
 BUSINESS OCCUPANCY, FBC1009, 1009.8. PROVIDE A DETAIL
 FOR THE STAIRS AND THE SPIRAL STAIRS.
  
 7. SHOW MANEUVERING CLEARANCE, PULL SIDE, PER FBC
 FIGURE 11-25 FOR DOORS AT TOILET 105, CORRIDOR 119 (BY
 CL122).
  
 8. FBC1008.1.2, DOOR C MUST BE SIDESWINGING OR MUST
 COMPLY WITH FBC1008.1.3.3.
  
 9. FBC505.4, OPENNESS FOR MEZZANINES, AND FBC505.2,
 AREA LIMITATION, EITHER REVISE PLAN TO COMPLY OR SHOW
 EXCEPTION ON THE PLAN.
  
 10. MR BOARD SHOWN ON WALL DETAILS ON A4; SEE
 FBC2509.3, LIMITATIONS, NOT CLEAR WHERE MR BOARD IS
 PROPOSED.
  
 11. ENERGY CALCS, INCLUDE THE NAME OF ARCHITECT AND
 LICENSE NUMBER AS THE PERSON WHO IS CERTIFYING THAT
 PORTION OF THE ENERGY CALC, FBC13-103.1.1.1.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-09-17 Cont ID  
Sent By dpalmer Date 2009-09-17 Time 20:21 Rev Time 0.00
Received By dpalmer Date 2009-09-17 Time 20:21 Sent To  
Notes
2009-09-17 20:21:54 
 ** NOTED ON REVIEW**
  
 1) NOTE: THERE ARE NO *GROSS ERRORS* ON THE SUBMITTED
 FLA COM LIGHTING PERFORMANCE CALCULATIONS.
 ** THERE IS NO CONFERENCE ROOM INDICATED ON PLANS
 ALTHOUGH AREA AND LOCATION SHOWN COULD BE USED FOR
 SUCH.
  
 2) NOTE: THIS IS A SINGLE TENANT SPACE BEING FED FROM
 THREE METERS AND MAINS ON METER-CENTER. EACH MAIN FOR
 TENANT SHALL BE LABELED ACCORDINGLY. TENANT/SUITE 105,
 MAIN 1 OF 3, 2 OF 3 ETC. ( OR WORDS TO THAT AFFECT.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-10-20 Cont ID  
Sent By mawillia Date 2009-10-20 Time 11:09 Rev Time 0.00
Received By mawillia Date 2009-10-20 Time 10:50 Sent To  
Notes
2009-10-20 11:02:08*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A-5, A-6, E-1 & E-2 WERE
 STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805--6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-09-28 Cont ID  
Sent By mawillia Date 2009-09-28 Time 13:15 Rev Time 0.00
Received By mawillia Date 2009-09-28 Time 12:40 Sent To  
Notes
2009-09-28 13:15:30*****DENIED*****
  
 THE APPROROPIATE PLAN SHEETS (A-5, E-1 & E-2) TO BE
 FIRE-STAMPED WHEN THE FOLLOWING HAVE BEEN ADDRESSED:
  
 1. ON SHEET A-5, THE CORRIDORS (104, 112, 119) LEAD TO
 A REAR DOOR. WHERE DO THESE DOORS LEAD TO AND ARE THEY
 CONSIDERED EXIT DOORS?
  
 2. ON SHEET A-5, THERE APPEARS TO BE NO FIRE PROTECTION
 FOR THE CONFERENCE ROOM AND OPEN OFFICE AREAS.
  
 3. THE OTHER PLAN REVIEWERS COMMENTS HAVE BEEN
 ADDRESSED.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805--6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-10-06 Cont ID  
Sent By lmartine Date 2009-10-05 Time 13:51 Rev Time 0.00
Received By lmartine Date 2009-10-05 Time 13:51 Sent To  
Notes
2009-10-06 13:55:42B--15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2009-09-28 Time   Rev Time 0.00
Received By lmartine Date 2009-09-16 Time 17:06 Sent To  
Notes
2009-09-16 17:07:42B-14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2009-10-19 Cont ID  
Sent By shill Date 2009-10-19 Time 11:37 Rev Time 0.00
Received By shill Date 2009-10-19 Time 11:36 Sent To  
Notes
2009-10-19 11:37:23STAMPED BY COUNTY, $0 DUE (EXISTING USE CREDIT)
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2009-10-15 Cont ID  
Sent By shill Date 2009-10-15 Time 09:26 Rev Time 0.00
Received By shill Date 2009-10-15 Time 09:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-10-23 Cont ID  
Sent By rregueir Date 2009-10-23 Time 09:34 Rev Time 0.00
Received By rregueir Date 2009-10-23 Time 09:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-09-21 Cont ID  
Sent By rregueir Date 2009-09-21 Time 09:40 Rev Time 0.00
Received By rregueir Date 2009-09-21 Time 07:53 Sent To  
Notes
2009-09-21 09:40:53REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENT
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-1 SHOWS OUTSIDE AIR DUCTS ROUTED TO A RETURN
 AIR PLENUM AREA. BASED ON THE RECORD SET OF PLANS FROM
 ORIGINAL CONSTRUCTION OF THESE SPACES, THE PLENUM AREAS
 ABOVE THE CEILING CONSIST OF A SMALL DEFINED AREA
 BETWEEN THE HEAT PUMP CLOSETS AND THE EXISTING RETURN
 AIR GRILLS. THE FRESH AIR DUCTS ARE NOT SHOWN AS BEING
 ROUTED TO THESE AREAS. IS THE PLENUM SPACE FOR THESE
 AREAS BEING REDEFINED? PLEASE CLARIFY BY DEFINING THE
 AREA TO BE DESIGNATED AS THE NEW ABOVE CEILING PLENUM
 SPACE OR SHOW THE FRESH AIR DUCTS BEING ROUTED TO THE
 EXISTING PLENUM SPACES. SHOW COMPLIANCE WITH FBC-M
 601.4 FOR BALANCED RETURN, FBC-M 602.2.1 FOR MATERIALS
 EXPOSED IN A PLENUM AND FBC-M 601.5 WHICH PROHIBITS
 EXHAUST DUCTS UNDER POSITIVE PRESSURE IN PLENUM SPACES.
  
 2. PAGE M-2 SHOWS RETURN AIR TRANSFER GRILLS WHICH
 APPEAR TO UTILIZE THE ABOVE CEILING SPACE AS A NEW
 RETURN AIR PLENUM. THE FLOOR PLAN SHOWS POSITIVE
 PRESSURE EXHAUST DUCT PASSING THROUGH THIS ABOVE
 CEILING SPACE. EXHAUST DUCTS UNDER POSITIVE PRESSURE
 SHALL NOT PASS THROUGH A PLENUM IN ACCORDANCE WITH
 FBC-M 601.5. PLEASE DEFINE THIS PLENUM SPACE SHOWING
 THE EXHAUST DUCTS ISOLATED FROM THE PLENUM OR SHOW A
 TRANSFER DUCT BETWEEN RETURN GRILLS WHICH IS SIZED TO
 MEET THE REQUIREMENTS OF FBC-M 601.4 FOR BALANCED
 RETURN.
  
 3. PAGE M-1 SHOWS WHAT APPEAR TO BE TWO NEW 18X18
 EXTERIOR WALL LOUVERS. PROVIDE PRODUCT APPROVALS FOR
 THE PROPOSED LOUVERS, REVIEWED AND APPROVED IN WRITING
 BY THE DESIGNER OF RECORD FOR THIS PROJECT IN
 ACCORDANCE WITH FBC-B 106.3.3.
  
 4. NEW DUCT SMOKE DETECTORS SHALL BE CONNECTED TO THE
 BUILDING FIRE ALARM SYSTEM IN ACCORDANCE WITH FBC-M
 606.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-10-29 Cont ID  
Sent By dwise Date 2009-10-29 Time 12:23 Rev Time 0.00
Received By dwise Date 2009-10-29 Time 12:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-10-22 Cont ID  
Sent By kstevens Date 2009-10-22 Time 09:38 Rev Time 0.00
Received By kstevens Date 2009-10-21 Time 17:58 Sent To  
Notes
2009-10-22 09:48:31DENIED
 REFERENCE:
 FBC-2007 PLUMIBNG
 FBC-2007 EXISTING BLDG
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT A-3 BATHROOM 204 SHALL BE ADAPTABLE. PLEASE SHOW
 COMPLIANCE WITH THE W/C 18" FROM THE CENTERLINE OF THE
 FIXTURE TO THE WALL. FIGURE 28. - BACKING FOR THE W/C
 AND THE SHOWER. SECTIONS 11-4.16.4 & 11-4.21.4 AS WELL
 AS FIGURES 29 & 37. SHOWER CONTROLS. SECTION 11-4.21.5
 & FIGURE 37. THE CURB. SECTION 11-4.21.7. AND THE
 TURNING AREA PER SECTION 11-4.23.3.
 ****RESPONSE NOTED, BUT SINCE UNITS WERE ORIGINALLY
 INDICATED AS R-2 OCCUPANCY AND IS NOW A B OCCUPANCY
 THIS IS A CHANGE OF OCCUPANCY. PER SECTION 906.1
 ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE, BUILDING. SEE
 SECTION 11-4.1.3(11). TO BE ADAPTABLE THE BACKING FOR
 THE GRAB BARS SHALL BE INSTALLED, THE W/C SHALL BE 18"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE, THE
 TURNING AREA SHALL BE INDICATED, THE VALVE LOCATION FOR
 THE SHOWER SHALL BE INDICATED AND THE CURB FOR THE
 SHOWER IS NOT APPROVED.
  
 2. SHT A-3 A DRINKING FOUNTAIN IS REQUIRED PER TABLE
 403.1. PLEASE SHOW THE LOCATION OF THE DRINKING
 FOUNTAIN AND SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
 ****RESPONSE NOTED, BUT NO DRINKING FOUNTAIN IS
 INDICATED IN THE COMMON AREA. SUBMIT PLANS SHOWING THE
 LOCATION OF THE EXISTING DRINKING FOUNTAIN.
  
 3. SHT P-1 NO WATER PIPING/SANITARY PIPING SHOWN FOR
 THE REQUIRED DRINKING FOUNTAIN. PLEASE SUBMIT ISOMETRIC
 RISER DIAGRAMS FOR BOTH AS WELL AS INDICATING THE
 LOCATION OF THE PIPING ON THE FLOOR PLAN. SECTION
 106.3.5.1.3(1)(3)(4)(6)(10)(13).
 ****RESPONSE NOTED, WHEN COMMENT NUMBER 2 IS ADDRESSED
 SHOWING THE CLEAR FLOOR SPACE FOR THE EXISTING DRINKING
 FOUNTAIN THEN COMMENT WILL BE ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-09-22 Cont ID  
Sent By kstevens Date 2009-09-22 Time 07:45 Rev Time 0.00
Received By kstevens Date 2009-09-22 Time 07:45 Sent To  
Notes
2009-09-22 07:59:21DENIED
 REFERENCE:
 FBC-2007 PLUMIBNG
 FBC-2007 EXISTING BLDG
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 1. SHT A-3 BATHROOM 204 SHALL BE ADAPTABLE. PLEASE SHOW
 COMPLIANCE WITH THE W/C 18" FROM THE CENTERLINE OF THE
 FIXTURE TO THE WALL. FIGURE 28. - BACKING FOR THE W/C
 AND THE SHOWER. SECTIONS 11-4.16.4 & 11-4.21.4 AS WELL
 AS FIGURES 29 & 37. SHOWER CONTROLS. SECTION 11-4.21.5
 & FIGURE 37. THE CURB. SECTION 11-4.21.7. AND THE
 TURNING AREA PER SECTION 11-4.23.3.
  
 2. SHT A-3 A DRINKING FOUNTAIN IS REQUIRED PER TABLE
 403.1. PLEASE SHOW THE LOCATION OF THE DRINKING
 FOUNTAIN AND SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 3. SHT P-1 NO WATER PIPING/SANITARY PIPING SHOWN FOR
 THE REQUIRED DRINKING FOUNTAIN. PLEASE SUBMIT ISOMETRIC
 RISER DIAGRAMS FOR BOTH AS WELL AS INDICATING THE
 LOCATION OF THE PIPING ON THE FLOOR PLAN. SECTION
 106.3.5.1.3(1)(3)(4)(6)(10)(13).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2009-09-22 Cont ID  
Sent By aaponte Date 2009-09-22 Time 10:47 Rev Time 0.00
Received By aaponte Date 2009-09-22 Time 10:47 Sent To  
Notes
2009-09-22 10:49:10PROPOSED ENCLOSURE FOR MEZZANINE COMPLIES WITH BUILDING
 CODE 505.4 EXCEPTION 1-OPENNESS.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved