Plan Review Stops For Permit 09090282 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2009-10-22 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-10-22 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-10-22 |
Time |
15:17 |
Sent To |
|
|
Notes |
2009-10-22 15:18:02 | *****APPROVED***** | | | | | | REVISED PLAN SHEET FA0.1 STAMPED, INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2009-10-21 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-10-21 |
Time |
15:42 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-10-21 |
Time |
14:45 |
Sent To |
|
|
Notes |
2009-10-21 15:15:04 | *****PROVISO***** | | | | THE FIRE ALARM PLAN (FA0.1 THRU FA1.2) WAS FIRE-STAMPED | | ACCORDINGLY; READY FOR PERMIT ISSUANCE. | | | | PLEASE BE ADVISED THAT REVISED PLANS ARE NEEDED WITH | | THE FOLLOWING CORRECTION PRIOR TO THE FIRE ALARM FINAL | | (302): | | | | 1. THE FIRE ALARM RISER ON SHEET FA0.1 INDICATES THE | | ADDITION OF TWO NEW SMOKE DETECTORS, WHEREAS THE PLANS | | SHOW THREE SUCH DEVICES. |
|
|
|