Plan Review Details - Permit 09090218
Plan Review Stops For Permit 09090218
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-05-03 Cont ID  
Sent By jwitmer Date 2010-05-03 Time 13:17 Rev Time 2.20
Received By jwitmer Date 2010-05-03 Time 13:17 Sent To  
Notes
2010-05-03 16:35:04BUILDING PLAN REVIEW
 PERMIT: 09090218
 ADD: 5011 BROADWAY AV
 CONT: TO BE DETERMINED
 TEL: (786)368-6455
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE W/ 2009
 SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 DATE MAY 03 /2010
 SHEET A-1 SITE PLAN NOTES & CODE INFORMATION:
  
 1) A-E COMPLIED.
 F) IF THIS PERMIT IS TO BE PHASED PLEASE PROVIDE TIME
 LINES FOR EACH PHASE, THE BUILDING OFFICIAL MAY REQUIRE
 SEPARATE PERMITS DEPENDING ON THE PHASED TIME LINE.
  
 2) NOTE PRODUCT APPROVALS ARE NOT REQUIRED AT TIME OF
 PERMIT ISSUANCE BUT WILL BE CONSIDERED A REVISION AND A
 SEPARATE REVIEW AND ASSOCIATED FEES
 WOULD BE REQUIRED.
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE
 AS FOLLOWS:
 A) FIXED GLASS/ STORE FRONT
 B) EXTERIOR GLAZED SWING DOORS & SIDELIGHTS
 C) SINGLE EXTERIOR HOLLOW METAL SWING DOORS
 D) PAIRS OF EXTERIOR HOLLOW METAL SWING DOORS
 E AUTOMATIC SLIDING DOORS& SIDE LIGHTS
 F) TRUSS ANCHORS
 G) WALL LOUVERS- DECORATIVE SHUTTERS
 H) EFIS WALL SYSTEMS
 I) SHUTTERS BAHAMAN STYLE- ON TOWERS
 J) ROOF ASSEMBLY???S UNDERLAYMENT, MODIFIED BITUMEN &
 ROOF TILE
  
 3A) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.
  
 3B) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
  
 4) 2ND REQUEST, FLOOR PLAN A-3 INDICATES USE OF POWER
 HORIZONTAL SLIDING DOORS. SHOW COMPLIANCE WITH:
 1008.1.3.3 HORIZONTAL SLIDING DOORS. IN OTHER THAN
 GROUP H OCCUPANCIES, HORIZONTAL SLIDING DOORS PERMITTED
 TO BE A COMPONENT OF A MEANS OF EGRESS IN
 ACCORDANCE WITH EXCEPTION 5 TO SECTION 1008.1.2 SHALL
 COMPLY WITH ALL OF THE FOLLOWING CRITERIA:
 1. THE DOORS SHALL BE POWER OPERATED AND SHALL BE
 CAPABLE OF BEING OPERATED MANUALLY IN THE EVENT OF
 POWER FAILURE.
 2. THE DOORS SHALL BE OPEN ABLE BY A SIMPLE METHOD FROM
 BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT.
 3. THE FORCE REQUIRED TO OPERATE THE DOOR SHALL NOT
 EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND
 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE
 MINIMUM REQUIRED WIDTH.
 4. THE DOOR SHALL BE OPERABLE WITH A FORCE NOT TO
 EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS
 (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT
 TO THE OPERATING DEVICE.
 5. THE DOOR ASSEMBLY SHALL COMPLY WITH THE APPLICABLE
 FIRE PROTECTION RATING AND, WHERE RATED, SHALL BE
 SELF-CLOSING OR AUTOMATIC-CLOSING BY
 SMOKE DETECTION, SHALL BE INSTALLED IN ACCORDANCE WITH
 NFPA 80 AND SHALL COMPLY WITH SECTION 715 .
 6. THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED STANDBY
 POWER SUPPLY.
 7. THE DOOR ASSEMBLY POWER SUPPLY SHALL BE ELECTRICALLY
 SUPERVISED.
  
 RESPONSE FROM THE DESIGN PROFESSIONAL WAS TO SITE THE
 CODE SECTION NOT TO PRODUCE MANUFACTURER???S SPEC OF
 DOOR INDICATING COMPLIANCE. 106.1.1* W.P.B.
 ADMINISTRATIVE CODE/2004 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS
 A SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 5A) 2ND REQUEST, THE FOLLOWING ITEMS WILL DEAL WITH
 ROOFING REPORTS BE ADVISED OF THE INFORMATION THAT WILL
 NEED TO BE HIGHLIGHTED BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT; THIS ROOF IS MISSING OR NOT IN COMPLIANCE
 WITH THE FOLLOW ITEMS:
 (FLAT ROOF)
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. ___
 CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED.
 ___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE ___
 .
 ___ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED FASTENER SPACING, PREPARED
 , SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 5B) 2ND REQUEST, ROOF TILE FOR SLOPED ROOFS, PLEASE
 INDICATE WHICH FASTENING SYSTEM SHALL BE USED.106.1.2
 ADDITIONAL INFORMATION REQUIRED. MOMENT OF OVERTURNING,
 1609.7.3 RIGID TILE.
  
 5C) 2ND REQUEST, NO INFORMATION FOR FASTENING OF HIP
 BOARD OR HIP TILE. 1507.3.8 APPLICATION. TILE SHALL BE
 APPLIED ACCORDING TO THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS OR RECOMMENDATIONS OF THE FRSA/RTI
 07320/08-05 (FOURTH EDITION).
  
 6A) COMPLIED.
  
 6B)2ND REQUEST, STRAPPING OVER THE UNIT DOES NOT
 CONSTITUTE MEETING THIS CODE SECTION. 301.13 FBC
 MECHANICAL. WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST WIND PRESSURES ON
 THE EQUIPMENT AND THE SUPPORTS AS DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
 THIS CODE SECTION IS NOT ONLY FOR THE ATTACHMENT OF THE
 UNIT TO THE STRUCTURAL MEMBERS BUT THE ACTUAL
 MECHANICAL EQUIPMENT ITSELF, THE EXTERIOR CABINETRY.
  
 7A-B) COMPLIED.
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10)2ND REQUEST, AT CONTRACTORS OWN RISK!!! SHEET S-4
 PLEASE INDICATE COMPLIANCE WITH 1802.2.1 QUESTIONABLE
 SOIL. WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 11)COMPLIED
  
 12) 2ND REQUEST, SHEET S-4 CODES AND SPECIFICATIONS ALL
 WORK SHALL BE IN ACCORDANCE WITH 2007 FBC HIGH WIND
 VELOCITY ZONE, PLEASE NOT THE HIGH VELOCITY WIND ZONE
 DESIGNATION IS ONLY TO BE USED FOR DADE AND BROWARD
 COUNTIES, THE CITY OF WEST PALM BEACH IS LOCATED IN THE
 HIGH WIND DEBRIS REGION PLEASE REVIEW FIGURE 1609. THE
 WIND DESIGN FOUND ON SHEET S-2 INDICATES 146MPH,
 EXPOSURE "C" WHICH IS A DADE AND BROWARD REQUIREMENT
 FOR THE HIGH WIND VELOCITY ZONE. IF THE DESIGNER
 WHISHES TO DESIGN TO THIS MORE STRINGENT REQUIREMENT,
 THEN THE ASSOCIATED HIGHER POSITIVE & NEGATIVE
 PRESSURES MUST BE USED IN THE WIND DESIGN.
  
 12A-C) COMPLIED.
  
 13) SEE NOTE# 4 SAME QUESTION.
  
 14) 2ND REQUEST, PROVIDE INFORMATION ON THE WALK-IN
 COOLERS AND FREEZERS. 2603.4.1.2 COOLER AND FREEZER
 WALLS. FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF
 10 INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL:
 1. HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS.
 2. HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES
 OF NOT LESS THAN 600?F AND 800?F (316?C AND 427?C),
 RESPECTIVELY.
 3.HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 MM)
 ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160
 INCH (0.4 MM) AT ANY POINT.
 4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. WHERE
 THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH THE
 COOLER OR FREEZER AND THAT PART OF THE
 BUILDING IN WHICH IT IS LOCATED SHALL BE SPRINKLED.
  
 2603.4.1.3 WALK-IN COOLERS. IN NON-SPRINKLED BUILDINGS,
 FOAM PLASTIC HAVING A THICKNESS THAT DOES NOT EXCEED 4
 INCHES (102 MM) AND A MAXIMUM
 FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK-IN
 COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR AREA
 DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE FOAM
 PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN
 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO
 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A
 THERMAL BARRIER.
  
 15) SHEET A-7 INDICATES VARIOUS SECTIONS THROUGH THE
 STRUCTURE WITH FINISHES( 106.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR COMMERCIAL BUILDINGS ;
 15A) PLANS ARE NOT COMPLETE AS TO INTERIOR FINISHES OF
 ROOMS
  
 15B) COMPLIED.
  
 15C) A V-B BUILDING TYPE WILL NOT REQUIRE FIRE RATED
 CEILINGS. THE QUESTION WAS WILL THEY BE NEEDED, NO THEY
 WOULD NOT BE REQUIRED BECAUSE OF THE AREA INCREASES
 PROVIDED BY THE NFPA 13 SPRINKLER SYSTEM..
  
 15D) COMPLIED.
  
 16) PROVISO: TRUSS PLANS WERE NOT SUBMITTED, PLANS FAIL
 TO PROVIDE LOADS TO BE RESISTED, HORIZONTAL, LATERAL
 AND GRAVITY LOADS.
  
 17) NEW COMMENT: THIS BUILDING WILL REQUIRE 2 EXITS AT
 LEAST 1/3RD THE DISTANCE APART. 1015.2.1. THE REAR
 DOORS AS IS CAN NOT BE USED AS AN EXIT SINCE THEY LEAD
 INTO A STORAGE OCCUPANCY.
  
 18) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-09-28 Cont ID  
Sent By jwitmer Date 2009-09-28 Time 12:02 Rev Time 3.75
Received By jwitmer Date 2009-09-28 Time 09:27 Sent To  
Notes
2009-09-28 14:19:37BUILDING PLAN REVIEW
 PERMIT: 09090218
 ADD: 5011 BROADWAY AV
 CONT: TO BE DETERMINED
 TEL: (786)368-6455
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE W/ 2009
 SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 SHEET A-1 SITE PLAN NOTES & CODE INFORMATION:
  
 1) WRONG ADDITION OF THE CODE. 110.2* W. P. B.
 ADMINISTRATIVE CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PERMIT WAS
 ISSUED. 2007 FBC W/ 2009 SUPPLEMENTS 2007 EFBC-LEVEL
 III SECTION 405
 B) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503,
 CHAPTER 6, TABLE 601. PLANS INDICATE BUILDING TYPE IV
 WHICH IS HEAVY TIMBER, UNDER THECURRENT CODE.PLANS
 DRAWN UNDER THE 2001 FBC THTE EQUIVALENT IV
 CLASSIFICATION TO THE 2007 FBC IS NOW A TYPE II-B.
 PLEASE NOTE THE MINIMUM STANDARD THAT THIS BUILDING
 COULD BE BUILT UNDER THE 2007 FBC PER TABLE 503 IS A
 V-B BUILDING FOR MERCANTILE WITH AREA INCREASES FOR
 FRONTAGE INCREASE AND 506.2 AND SPRINKLER INCREASE PER
 506.3
 D) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED?
 E) WEATHER A SPRINKLER SYSTEM IS REQUIRED?
 2007 EXISTING BLDG CODE 804.2.2 AUTOMATIC FIRE
 DETECTION. WHERE REQUIRED BY THE FLORIDA BUILDING CODE,
 BUILDING FOR NEW BUILDINGS, AUTOMATIC FIRE DETECTION
 SYSTEMS SHALL BE PROVIDED THROUGHOUT THE WORK AREA.
 903.2.6 GROUP M. AN AUTOMATIC SPRINKLER SYSTEM SHALL BE
 PROVIDED THROUGHOUT BUILDINGS CONTAINING A GROUP M
 OCCUPANCY WHERE ONE OF THE FOLLOWING CONDITIONS EXISTS:
 1. WHERE A GROUP M FIRE AREA EXCEEDS 12,000 SQUARE FEET
 (1115 M2).
 PLEASE PROVIDE A FIRE SPRINKLER PLAN.
 F) IF THIS PERMIT IS TO BE PHASED PLEASE PROVIDE TIME
 LINES FOR EACH PHASE, THE BUILDING OFFICIAL MAY REQUIRE
 SEPERATE PERMITS DEPENDING ON THE PHASED TIME LINE.
  
 2) NOTE PRODUCT APPROVALS ARE NOT REQUIRED AT TIME OF
 PERMIT ISSUANCE BUT WILL BE CONSIDERED A REVISION AND A
 SEPERATE REVIEW AND ASSOCIATED FEES
 WOULD BE REQUIRED.
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE
 AS FOLLOWS:
 A) FIXED GLASS/ STORE FRONT
 B) EXTERIOR GLAZED SWING DOORS & SIDELITES
 C) SINGLE EXTERIOR HOLLOW METAL SWING DOORS
 D) PAIRS OF EXTERIOR HOLLOW METAL SWING DOORS
 E AUTOMATIC SLIDING DOORS& SIDE LITES
 F) TRUSS ANCHORS
 G) WALL LOUVERS- DECRATIVE SHUTTERS
 H) EFIS WALL SYSTEMS
 I) SHUTTERS BAHAMA STYLE- ON TOWERS
 J) ROOF ASSEMBLIES UNDERLAYMENT, MODIFIED BITUMEN &
 ROOF TILE
  
 3A) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.
  
 3B) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4) FLOOR PLAN A-3 INDICATES USE OF POWER HORIZONTAL
 SLIDING DOORS. SHOW COMPLIANCE WITH:
 1008.1.3.3 HORIZONTAL SLIDING DOORS. IN OTHER THAN
 GROUP H OCCUPANCIES, HORIZONTAL SLIDING DOORS PERMITTED
 TO BE A COMPONENT OF A MEANS OF EGRESS IN
 ACCORDANCE WITH EXCEPTION 5 TO SECTION 1008.1.2 SHALL
 COMPLY WITH ALL OF THE FOLLOWING CRITERIA:
 1. THE DOORS SHALL BE POWER OPERATED AND SHALL BE
 CAPABLE OF BEING OPERATED MANUALLY IN THE EVENT OF
 POWER FAILURE.
 2. THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD FROM
 BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT.
 3. THE FORCE REQUIRED TO OPERA TE THE DOOR SHALL NOT
 EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND
 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE
 MINIMUM REQUIRED WIDTH.
 4. THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO
 EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS
 (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT
 TO THE OPERATING DEVICE.
 5. THE DOOR ASSEMBLY SHALL COMPLY WITH THE APPLICABLE
 FIRE PROTECTION RATING AND, WHERE RATED, SHALL BE
 SELF-CLOSING OR AUTOMATIC-CLOSING BY
 SMOKE DETECTION, SHALL BE INSTALLED IN ACCORDANCE WITH
 NFPA 80 AND SHALL COMPLY WITH SECTION 715 .
 6. THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED STANDBY
 POWER SUPPLY.
 7. THE DOOR ASSEMBLY POWER SUPPLY SHALL BE ELECTRICALLY
 SUPERVISED.
  
 5A) THE FOLLOWING ITEMS WILL DEAL WITH ROOFING REPORTS
 BE ADVISED OF THE INFORMATION THAT WILL NEED TO BE
 HIGHLIGHTED BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT; THIS ROOF IS MISSING OR NOT IN COMPLIANCE
 WITH THE FOLLOW ITEMS:
 (FLAT ROOF)
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. ___
 CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED.
 ___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE ___
 .
 ___ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED FASTENER SPACING, PREPARED
 , SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 5B) ROOF TILE FOR SLOPED ROOFS, PLEASE INDICATE WHICH
 FASTENING SYSTEM SHALL BE USED.106.1.2 ADDITIONAL
 INFORMATION REQUIRED. MOMENT OF OVERTURNING, 1609.7.3
 RIGID TILE.
  
 5C) NO INFORMATION FOR FASTENING OF HIP BOARD OR HIP
 TILE. 1507.3.8 APPLICATION. TILE SHALL BE APPLIED
 ACCORDING TO THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS OR RECOMMENDATIONS OF THE FRSA/RTI
 07320/08-05 (FOURTH EDITION).
  
 6A) A-7 NOR STRUCTURAL PLANS ARE MISSING THE NEW A/C
 CURBS, HOW THE WEIGHT WILL BE CARRIED ON THE WOOD
 TTRUSS SYSTEM AND BAR JOIST SYSTEM (MEZZANINE LEVEL) ,
 WHERE THE POINT LOADING WILL NEED TO BE TAKEN IN AFFECT
 AND THE PANEL POINTS REINFORCED, NEW HEADERS SHAPE AND
 SIZE OF FRAMING AND THE ACTUAL ATTACHMENT OF THE CURB
 TO THE ROOF SYSTEM. 1609.6.1.1 MAIN WINDFORCE-RESISTING
 SYSTEMS.
  
 6B) 301.13 FBC MECHANICAL. WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING. THIS CODE SECTION IS NOT ONLY FOR THE
 ATTACHMENT OF THE UNIT TO THE STRUCTURAL MEMBERS BUT
 THE ACTUAL MECHANICAL EQUIPMENT ITSELF, THE EXTERIOR
 CABINETRY.
  
 7A) A-4 INDICATES THE USE OF ROOF DRAINS AND OVERFLOW
 SCUPPERS THERE IS NO INFORMATION PROVIDED WHAT THE
 MINIMUM ROOF INSULATION WILL BE LOCATED AT THE ROOF
 DRAINS. FBC 13-404.A.B..1 MINIMUM R-VALUE OF R-10.
  
 7B) UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES,
 DESIGN AND INSTALLATION OF ROOF DRAINAGE SYSTEMS SHALL
 COMPLY WITH THE FLORIDA BUILDING CODE, PLUMBING ,
 CHAPTER 11 .
  
 8) NOTE PLANS DO NOT INDICATE COMPLIANCE WITH: 1503.6
 PROTECTION AGAINST DECAY AND TERMITES. CONDENSATE LINES
 AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT
 (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, WHETHER BY
 UNDERGROUND PIPING, TAIL EXTENSIONS, OR SPLASH BLOCKS.
 GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON ALL BUILDINGS
 WITH EAVES OF LESS THAN 6 INCHES (152 MM) HORIZONTAL
 PROJECTION EXCEPT FOR GABLE END RAKES OR ON A ROOF
 ABOVE ANOTHER ROOF.
  
 9) SHEET S-1 PLEASE INDICATE WHERE THE PROPERTY LINE IS
 LOCATED, IT APPEARS THAT THE NEW FOUNDATION SYSTEM NEXT
 TO DIXIE HWY MAY BE ENCROUCHING INTO THE RIGHTOF-WAY.
 3202.1.1. STRUCTURAL SUPPORT. A PART OF A BUILDING
 ERECTED BELOW GRADE THAT IS NECESSARY FOR STRUCTURAL
 SUPPORT OF THE BUILDING OR STRUCTURE SHALL NOT PROJECT
 BEYOND THE LOT LINES, EXCEPT THAT THE FOOTINGS OF
 STREET WALLS OR THEIR SUPPORTS WHICH ARE LOCATED AT
 LEAST 8 FEET (2438 MM) BELOW GRADE SHALL NOT PROJECT
 MORE THAN 12 INCHES (305 MM) BEYOND THE STREET LOT
 LINE.
  
 10) SHEET S-4 PLEASE INDICATE COMPLIANCE WITH 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 11) SHEET S-4 INDICATES THE USE OF A VAPOR BERRIER BUT
 NOT SECTION;1816.1 TERMITE PROTECTION. TERMITE
 PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL-APPLIED PESTICIDES,
 BAITING SYSTEMS AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION. SEE SECTION 202, REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF THE TERMITE
 PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL
 BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED
 PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING
 STATEMENT: "THE BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES.
 TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE
 AND CONSUMER SERVICES."
  
 12) SHEET S-4 CODES AND SPECIFICATIONS ALL WORK SHALL
 BE IN ACCORDANCE WITH 2007 FBC HIGH WIND VELOCITY ZONE,
 PLEASE NOT THE HIGH VELOCITY WIND ZONE DESIGNATION IS
 ONLY TO BE USED FOR DADE AND BROWARD COUNTIES, THE CITY
 OF WEST PALM BEACH IS LOCATED IN THE HIGH WIND DEBRIS
 REGIONPLEASE REVIEW FIGURE 1609. THE WIND DESIGN FOUND
 ON SHEET S-2 INDICATES 146MPH, EXPOSURE "C" WHICH IS A
 DADE AND BROWARD REQUIREMENT FOR THE HIGH WIND VELOCITY
 ZONE. IF THE DESIGNER WHICHES TO DESIGN TO THIS MORE
 STRINGENT REQUIREMENT, THEN THE ASSOCIATED HIGHER
 POSITIVE & NEGATIVE PRESSURES MUST
 BE USED IN THTE WIND DESIGN.
  
 12A) SHEET A-6 DOES INDICATE THE PRESSURES FOR THE
 WINDOWS AND DOORS PLEASE PROVIDE INTERIOR ZONES AND END
 ZONE LOCATIONS FOR TCLARIFICATION. NOTE ON THE TOWER
 PRESSURES ARE NOT INDICATED FOR ALL WINDOW
 ELEVATIONS.1609.1.1
  
 12B) SHEET A-4 ROOF PLAN DOES NOT PROVIDE THE ROOF
 PRESSURE ZONE LOCATIONS ZONE 1, 2 OR 3 FOR THE FLAT
 ROOF NOR THE HIP ROOF. 1609.1.1.
  
 12C) SHEET A-6 THE NORTH ELEVATION INDICATES DECRETIVE
 SHUTTERS, ISN'T THIS THE MEZZANINE LEVLE WHERE THE
 MECHANICAL EQUIPMENT IS LOCATED AND THESE OPENINGS ARE
 FOR FRESH AIR NOT A SOLID WALL, IF SO THEY WILL BE
 CLASSIFIED AS LOUVERS, PLEASE PROVIDE THE POSISTIVE AND
 NEGATIVE PRESSURES FOR OPENINGS.
 1609.1.1.
  
 13) SHEET A-7 DOOR D-1 IS INDICATED AS A BY PASS DOOR
 PLEASE PROVIDE COMPLIANCE WITH 1008.1.3.3 HORIZONTAL
 SLIDING DOORS.
  
  
 14) PROVIDE INFORMATION ON THE WALK-IN COOLERS AND
 FREEZERS. 2603.4.1.2 COOLER AND FREEZER WALLS. FOAM
 PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10 INCHES
 (254 MM) IN COOLER AND FREEZER WALLS SHALL:
 1. HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS.
 2. HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES
 OF NOT LESS THAN 600?F AND 800?F (316?C AND 427?C),
 RESPECTIVELY.
 3.HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 MM)
 ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160
 INCH (0.4 MM) AT ANY POINT.
 4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. WHERE
 THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH THE
 COOLER OR FREEZER AND THAT PART OF THE
 BUILDING IN WHICH IT IS LOCATED SHALL BE SPRINKLERED.
  
 2603.4.1.3 WALK-IN COOLERS. IN NONSPRINKLERED
 BUILDINGS, FOAM PLASTIC HAVING A THICKNESS THAT DOES
 NOT EXCEED 4 INCHES (102 MM) AND A MAXIMUM
 FLAME SPREAD INDEX OF 75 IS PERMITTED IN WALK-IN
 COOLERS OR FREEZER UNITS WHERE THE AGGREGATE FLOOR AREA
 DOES NOT EXCEED 400 SQUARE FEET (37 M 2 ) AND THE FOAM
 PLASTIC IS COVERED BY A METAL FACING NOT LESS THAN
 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO
 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A
 THERMAL BARRIER.
  
 15) SHEET A-7 INDICATES VARIOUS SECTIONS THROUGH THE
 STRUCTURE WITH FINISHES( 106.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR COMMERCIAL BUILDINGS ;
 15A) PLANS ARE NOT COMPLETE AS TO INTERIOR FINISHES OF
 ROOMS
  
 15B) SECTION 803/ TABLE 803.5.
  
 15C) PLANS ARE NOT COMPLETE AS TO 1HR FIRE RATING
 CEILING, TYPE OF SYSTEM TO BE INSTALLED, 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 15D) INTERIOR WALL AND DOOR SCHEDULE, 106.1.2.
  
 16) TRUSS PLANS WERE NOT SUBMITTED, PLANS FAIL TO
 PROVIDE LOADS TO BE RESISTED, HORIZONTAL, LATERAL AND
 GRAVITY LOADS.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-04-19 Cont ID  
Sent By jleahy Date 2010-04-19 Time 11:26 Rev Time 0.00
Received By jleahy Date 2010-04-19 Time 11:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-07 Cont ID  
Sent By dpalmer Date 2009-10-07 Time 14:04 Rev Time 0.00
Received By dpalmer Date 2009-10-07 Time 14:04 Sent To  
Notes
2009-10-07 14:04:15 
 ** DENIED **
  
 1) NOTE: PLANS HAVE BEEN SUBMITTED UNDER PERMIT
 APPLICATION HOWEVER NO LICENSED CONTRACTOR HAS BEEN
 SIGNED ON APPLICATION. ONCE ELECTRICAL REVIEW IS FOUND
 TO PASS FOR REVIEW THE REVIEW STATUS WILL STILL REMAIN
 IN FAILED STATUS UNTIL SUCH TIME LICENSED CONTRACTOR(S)
 HAS BEEN DETERMINED ETC
  
 2) NOTE: PLANS ARE NOT SHOWING THE CORRECT ADOPTED
 CODES BY THE STATE OF FLORIDA. PLEASE KNOW THAT AS OF
 MARCH 1ST, 2009 THE STATE ADOPTED THE FOLLOWING AT A
 MINIMUM.
 2007 FBC W/2009 REVISIONS.
 AS OF DECEMBER 31ST, 2008 THE STATE ADOPTED UNDER FAC
 69A-3.012 AND 69A-60.004, .003 THE 2006 NFPA-101, 2006
 NFPA-1. ELECTRICAL PLANS INDICATE THE 2003 NFPA-101
 PLANS SUBMITTED BEFORE OCTOBER 1ST 2009 ARE UNDER THE
 2005 NATIONAL ELECTRICAL CODE. ( NFPA-70).
 PLEASE BE SURE TO LIST THE FOLLOWING MINIMUM CODES ON
 PLANS.
  
 2007 FBC W/2009 REVISIONS
 2006 NFPA-101
 2005 NFPA-70
 2002 NFPA-72 ( IF APPLICABLE FOR BUILDINGS WITH FIRE
 ALARM SYSTEMS)
  
 ** SOME CODE SECTIONS FOR EXAMPLE ON E-1 NOTE #8 IS
 ACTUALLY FROM THE 1996 NEC. THIS CODE SECTION NEEDS TO
 BE REVISED TO THE APPLICABLE SECTION FROM THE 2005 NEC.
  
 3) NOTE: PLEASE SEE FAC 61G1-60.004 FOR MISSING
 REQUIRED INFORMATION IN THE TITLE BLOCKS FOR ARCHITECT
 AND ARCHITECTURAL FIRM.
 PLEASE SEE FS 481.219 FOR REQUIRED CERTIFICATE OF
 AUTHORIZATION NUMBER.
 IF THERE ARE ANY QUESTIONS ON LICENSING REQUIRED AND
 INFORMATION REQUIRED TO BE LOCATED ON TITLE BLOCKS,
 PLEASE CONTACT THE BOARD OF ARCHITECT'S LEGAL COUNSEL.
  
 4) NOTE: LANDSCAPE ARCHITECTURAL SHEETS. PLEASE SEE FS
 481.319, 321 FOR REQUIRED LICENSING FOR FIRM,
 CORPORATION, PARTNERSHIP ETC.
 ** PLEASE KNOW ANY LANDSCAPE LIGHTING/SITE LIGHTING
 WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS PER THE
 BUILDING OFFICIAL. HOWEVER BASE PLANS FOR ENERGY CODE
 COMPLIANCE WILL BE REQUIRED TO SHOW CODE COMPLIANCE.
  
  
 5) NOTE: NO PLANS, DOCUMENTS OR INFORMATION SUBMITTED
 FOR LIGHTING PERFORMANCE CALCULATIONS UNDER FBC CHAPTER
 13 WERE SUBMITTED. PLEASE SEE 13-415.AB.5 FOR INTERIOR
 AND 13-415.AB.2.2 FOR EXTERIOR.
 ** AS NOT CALCULATIONS MEETING ENERGY CODE WERE
 SUBMITTED NO REVIEW OF THESE ITEMS COULD BE DONE.
 ** EVEN WHEN A BUILDING DOES NOT MEET THE DEFINITION OF
 A RENOVATION, THE MINIMUM PRESCRIPTIVE REQUIREMENTS OF
 THE ENERGY CODE STILL MUST BE MET.
  
 6) NOTE: PLEASE SEE 13-415.AB.1.1,.1.2, .1.3 AND .1.4
 FOR MINIMUM LIGHTING CONTROLS. BASED ON THE PLANS ITEMS
 SUCH AS SINGLE POLE SWITCHES AS SHOWN ON SYMBOL LEGEND
 AND PLANS DOES NOT MEET MINIMUM REQUIRED.
 *** IT IS IMPORTANT TO SEE SECTIONS NOTED AND TO CALL
 TO GO OVER ANY QUESTIONS.
  
 7) NOTE: PLANS INDICATE PANEL L IN THE MIDDLE OF THE
 STORAGE ROOM WALL. PLEASE RELOCATE AS STORAGE IS NOT
 PERMITTED IN THIS AREA.
 ALSO KNOW THAT PROTECTION OF ELECTRICAL EQUIPMENT IN
 ANY LOCATION WHERE CONTACT OF ROLLING EQUIPMENT/STORAGE
 UNITS COULD DAMAGE ELECTRICAL EQUIPMENT WILL BE
 REQUIRED.
 ** PLEASE VERIFY LOCATION AS THE ENLARGED ELECTRICAL
 ROOM PLANS INDICATES THE *L* PANEL ON THE MAIN
 ELECTRICAL ROOM YET THE PLANS INDICATE THIS SAME PANEL
 IN STORAGE ROOM ON WALL.??
  
 110.26, 110.27B, 408.17, 240.24 ETC.
  
 8) NOTE: THE AIC RATINGS FOR ALL EQUIPMENT, PANELS AND
 BREAKERS NEED TO BE ON PLANS AT THIS TIME. 110.9
 NOTE MENTIONS TO OBTAIN INFORMATION AND VERIFY HOWEVER
 THIS INFORMATION IS READILY AVAILABLE AT THIS TIME.
 SOME RATINGS ARE SHOWN FOR PANELS WITH SERIES RATINGS.
  
 9) NOTE: PLEASE SEE FBC 13-413.AB.2 FOR REQUIRED NOTES
 TO BE PLACED ON PLANS.
  
 10) NOTE: PLEASE SEE FBC 13-413.AB.1 FOR REQUIRED WORST
 CASE VOLTAGE DROP CALCULATIONS REQUIRED.
  
 11) NOTE: COMPLETE LOAD CALCULATIONS WERE NOT
 SUBMITTED/SHOWN PER NEC. HOW WERE LOADS DERIVED?
 PLEASE SEE 220.12,220.14,220.42,220.44, 220.43 FOR
 RECEPTACLES, LIGHTING, TRACK LIGHTING LOADS ETC.
 ** PLEASE BE SURE TO SEE 215.3,230.42 ETC FOR ALL
 CONTINUOUS LOADS TO BE SHOWN AT 125% INCLUDING LARGEST
 MOTOR LOADS.
  
 12) NOTE: IN THE MIDDLE OF E-4 THERE IS A PANEL
 SCHEDULE FOR A/C EQUIPMENT HOWEVER PANEL IS NOT
 IDENTIFIED. ACTUALLY SATES * PANE*. PLEASE ALSO
 COORDINATE THE LOCATION IN WHICH THIS PANEL IS FED
 FROM. THE *PANE* PANEL SCHEDULE STATES IT IS FED FROM
 PANEL DP, YET BASED ON THE RISER THIS IS A PANEL TAPPED
 FROM THE MAIN GUTTER AND NOT FED FROM DP.
 PLEASE ADJUST AND COORDINATE INFORMATION ON RISER.
 215,220,230,240,408 ETC GIVEN AS GENERAL CHAPTERS FOR
 COORDINATION OF ALL INFORMATION.
  
 13) NOTE: SIGN CIRCUIT STILL REQUIRED AT FRONT ENTRANCE
 PER 600.5
  
 14) NOTE: ANY WINDOW AREAS SHALL HAVE SHOW WINDOW
 RECEPTACLES PER 210.62. PLEASE ALSO BE SURE TO ADJUST
 LOAD CALCULATIONS PER 220.43, 220.14
  
 ** AS THERE IS INFORMATION NOT YET SUBMITTED REQUIRED
 FOR MINIMUM CODE COMPLIANCE REVIEW THERE MAY VERY WELL
 BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT
 BE MADE AT THIS TIME.
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2010-05-13 Cont ID  
Sent By mgonzale Date 2010-05-13 Time 15:13 Rev Time 1.50
Received By mgonzale Date 2010-05-13 Time 15:13 Sent To  
Notes
2010-05-13 15:22:27PLANS ARE FAILED DUE TO THE FOLLOWING:
  
 PREVIOUS COMMENTS WHERE NOT ADDRESSED.
  
 NO FIRELINE CONNECTION. SUBMIT ROW PLANS AND CONNECTION
 TO MAIN.
 CONTACT CITY ENGINEERING SERVICES : MANUEL JULIAN
 GONZALEZ.
 ENGINEERING PROJECT COORDINATOR.
 ENGINEERING SERVICES DEPARTMENT.
 401 CLEMATIS STREET, 4TH FLOOR.
 WEST PALM BEACH, FL 33401.
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200.
  
 DIRECT: (561) 494-1085
  
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2009-10-07 Cont ID  
Sent By efabian Date 2009-10-07 Time 15:51 Rev Time 1.00
Received By efabian Date   Time   Sent To FIRE
Notes
2009-10-07 16:14:53FAILED
  
 PLEASE PROVIDE NEW PROPOSED WATER USAGE FLOW
 CALCULATIONS / DEMANDS:
  
 1. THE ADDITION OF SEVERAL FOOD PREPARATION, KITCHEN
 AND UTILITIY AREAS FOR PHASE 1 AND PHASE 2 MAY REQUIRE
 AN UPGRADE TO THE EXISTING WATER SERVICES.
  
 2. PLEASE PROVIDE LOCATION(S), DETAILS AND CAPACITIY OF
 EXISTING GREASE-WASTE TRAPS TO ENSURE CONFORMITY TO
 CWPB'S CONSTRUCTION STANDARDS.
  
 3. PLEASE RESPOND TO PLUMBING REVIEW STOP NO. 10,
 CONCERNING THE RPZV BACKFLOW REQUIREMENT PER MR. KEN
 STEVENS.
  
 REVIEWED BY EMERY P. FABIAN, ENGINEERING SERVICES,
 494-1078 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-05-07 Cont ID  
Sent By mcarsill Date 2010-05-07 Time 09:24 Rev Time 0.00
Received By mcarsill Date 2010-05-07 Time 09:19 Sent To  
Notes
2010-05-07 09:24:165011 BROADWAY AVENUE
 CITY MARKET
 PERMIT NUMBER 09090218
  
 1. WHEN FIRE SPRINKLER SYSTEMS ARE REQUIRED FIRE
 SPRINKLER DESIGN CRITERIA SHALL BE SUBMITTED AT TIME OF
 PERMIT APPLICATION. NO INFORMATION RELATED TO THE FIRE
 SPRINKLER SYSTEM HAS BEEN PROVIDED. PLEASE PROVIDE
 DESIGN CRITERIA AND DRAWINGS FOR THE FIRE SPRINKLER
 SYSTEM. LATER SEPARATE PLANS AND PERMITS WILL BE
 REQUIRED FOR THE DIRECT INSTALLATION OF THESE SYSTEMS.
  
 2. IT APPEARS THAT MOST OF THE PREVIOUS COMMENTS HAVE
 BEEN IDENTIFIED IN THE REVISION 1 DRAWINGS.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR THE HOOD,
 DUCT, AND FIRE SUPPRESSION SYSTEMS.
  
 4. ALL NEW FIRE DAMPERS ARE TO BE REQUIRED TO BE DROP
 TESTED AFTER INSTALLATION TO ENSURE PROPER FUNCTION.
  
 5. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 ALARM SYSTEM.
  
 6. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4709 PHONE
 (561) 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-10-14 Cont ID  
Sent By mcarsill Date 2009-10-14 Time 14:55 Rev Time 0.00
Received By mcarsill Date 2009-10-14 Time 14:44 Sent To  
Notes
2009-10-14 14:55:13CITY MARKET
 PERMIT NUMBER 09090218
  
 1. THE EXISTING BUILDING EXCEEDS 12,000 SQUARE FEET.
 DURING PHASE 1, PHASE 2, AND PHASE 3 THE ENTIRE STORE
 WILL EXCEED T12,000 SQUARE FEET. THE ENTIRE BUILDING
 WILL BE REQUIRED TO BE FIRE SPRINKLER PROTECTED IN
 ACCORDANCE WITH NFPA 13, THE STANDARD FOR AUTOMATIC
 FIRE SPRINKLERS. ALL COOLERS AND FREEZERS WILL BE
 REQUIRED TO BE FIRE SPRINKLER PROTECTED.
  
 2. SITE PLANS FAILS TO ILLUSTRATE ANY NEW OR EXISTING
 FIRE HYDRANTS.
  
 3. DEMOLITION, CONSTRUCTION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 4. THE BUILDING ADDRESS IS REQUIRED. A MINIMUM OF AT
 LEAST 6" HIGH AND AT LEAST 1" WIDE NUMBERS ARE
 REQUIRED. THEY ARE TO CONTAST TO THE BACKGROUND THEY
 WILL BE AFFIXED TO.
  
 5. A KNOX-BOX WILL BE REQUIRED.
  
 6. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE FIRE SPRINKLER, FIRE ALARM, AND
 HOOD,DUCT, AND FIRE SUPPRESSION SYSTEMS.
  
 7. PLEASE PROVIDE A LIFE SAFETY PLAN FOR REVIEW.
  
 8. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 9. ADDITIONAL EXIT SIGNS WILL BE REQUIRED IN SALES
 AREA.
  
 10. NOTE # 1 ON PAGE E-5 IS INCORRECT.
  
 11. IT DOES NOT APPEAR THAT ENOUGH FIRE ALARM SIGNALING
 APPLIANCES ARE PRESENT THROUGHOUT THE STORE.
  
 12. PLEASE INDICATE LOCATIONS OF ALL PORTABLE FIRE
 EXTINGUISHERS.
  
 13. PLEASE PROVIDE SUFFICIENT DETAILS REGADING ALL EXIT
 DOORS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 (561) 804-4709 PHONE
 (561) 804-4774 FAX
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2010-04-20 Cont ID  
Sent By lwagner Date 2010-04-20 Time 08:51 Rev Time 0.00
Received By lwagner Date 2010-04-20 Time 08:51 Sent To  
Notes
2010-04-20 08:51:48GAS REMOVED FROM PLAN.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-09-30 Cont ID  
Sent By kstevens Date 2009-09-30 Time 10:22 Rev Time 0.00
Received By kstevens Date 2009-09-30 Time 10:22 Sent To  
Notes
2009-09-30 10:27:17DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE
 REQUIRED GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU
 G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2007 FUEL
 GAS CODE SECTION 304 & RESIDENTIAL CODE SECTION G2407.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2007 FUEL GAS CODE
 SECS. 502 THRU 505 & RESIDENTIAL CODE SECS. G2426 THRU
 G2429.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2.
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-04-14 Cont ID  
Sent By rmcdouga Date 2010-04-13 Time 08:59 Rev Time 0.00
Received By rmcdouga Date 2010-04-13 Time 08:59 Sent To  
Notes
2010-04-14 09:00:49C25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-05-14 Cont ID  
Sent By hmoser Date 2010-05-14 Time 14:09 Rev Time 0.00
Received By hmoser Date 2009-09-10 Time 10:28 Sent To  
Notes
2009-09-15 10:41:41C-30

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2010-05-19 Cont ID  
Sent By rkussner Date 2010-05-19 Time 10:25 Rev Time 0.00
Received By rkussner Date 2010-05-19 Time 10:25 Sent To  
Notes
2010-05-19 10:32:44***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1, PLEASE ADDRESS ZONING COMMENTS THAT PERTAIN TO
 LANDSCAPING.
  
 2. PLEASE APPLY FOR SEPARATE IRRIGATION PERMIT. SUBMIT
 TWO COPIES OF THE IRRIGATION PLAN.
  
 3. PLEASE SUBMIT A CERTIFIED COST ESTIMATE THAT
 INCLUDES THE TOTAL COST OF ALL LANDSCAPE MATERIALS AND
 LABOR, BROKEN DOWN INTO UNIT COST. THIS AMOUNT NEEDS TO
 BE ADDED TO THE VALUATION FOR THE PROPOSED WORK, UNLESS
 IT HAS ALREADY BEEN FIGURED INTO THE TOTAL COST.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-09-22 Cont ID  
Sent By rkussner Date 2009-09-22 Time 17:08 Rev Time 0.00
Received By rkussner Date 2009-09-22 Time 17:07 Sent To  
Notes
2009-09-22 17:27:53***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 THE FOLLOWING LANDSCAPE COMMENTS ARE BASED UPON THE
 BROADWAY REGULATIONS:
  
 1. PURSUANT TO SECTION 94-219(D)(9)(B), ALL EXISTING
 SURFACE PARKING LOTS SHALL BE LANDSCAPED WITH A 36-INCH
 HIGH PERIMETER HEDGE AND SHADE TREES AT EVERY THIRD
 PARKING SPACE WITHIN 24 MONTHS OF THE BROADWAY CORRIDOR
 REZONING. THE HEDGE HEIGHT IS PROPOSED AT 24".
  
 THE FOLLOWING LANDSCAPE COMMENTS ARE BASED UPON THE
 LANDSCAPE REGULATIONS:
  
 1. PURSUANT TO SECTION 94-442(D), PRIVATE LAND AND
 PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK
 SURFACES AND REQUIRED BUFFER STRIPS AND LANDSCAPED OPEN
 SPACE AREAS SHALL BE PLANTED WITH GRASS. THIS AFFECTS
 THE ADJACENT RIGHTS-OF-WAY.
  
 2. PURSUANT TO SECTION 94-445(4)(G)(3), AUTOMATIC
 IRRIGATION SYSTEMS SHALL BE USED FOR THE CULTIVATED
 LANDSCAPE AREAS FOR ALL PROPERTIES. THIS INCLUDES THE
 RIGHT-OF-WAY AREAS.
  
 3. ALL SITE LIGHTING, UTILITIES, EASEMENTS, OVERHEAD
 LINES AND ANYTHING ELSE THAT COULD BE IN CONFLICT WITH
 PROPOSED LANDSCAPING SHALL BE SHOWN ON THE PLAN TO
 AVOID CONFLICTS.
  
 4. STAFF RECOMMENDS THAT VERTICAL LANDSCAPE ELEMENTS BE
 INSTALLED ALONG THE NORTH ELEVATION OF THE BUILDING.
  
 5. THE APPLICANT SHALL CONSIDER THE USE OF GROUND COVER
 INSTEAD OF SOD IN SMALL ISOLATED AREAS SUCH AS BETWEEN
 A HEDGE AND SIDEWALK. THIS WILL REDUCE MAINTENANCE.
  
 6. PURSUANT TO SECTION 94-443 (C)(3)(A), EACH ROW OF
 PARKING SPACES SHALL BE TERMINATED BY A LANDSCAPE
 ISLAND. AT LEAST ONE SHADE OR FLOWERING TREE OR THE
 EQUIVALENT NUMBER OF PALMS IS REQUIRED IN EACH ISLAND.
 AN ADDTITIONAL WINN PALM SHALL BE PLANTED AT THE NORTH
 END OF THE PARKING ROW ON THE SOUTH SIDE OF THE
 BUILDING (WEST PERIMETER OF SITE).
  
 7. THE SITE AND LANDSCAPE PLANS MUST BE CONSISTENT.
 THERE IS A DIFFERENCE BETWEEN THE PLANS IN THE
 LANDSCAPE STRIP BETWEEN THE ABUTTING PARKING ROWS ON
 THE SOUTH SIDE OF THE BUILDING.
  
 8. PLEASE PROVIDE A CERTIFIED COST ESTIMATE THAT
 INCLUDES THE TOTAL COST OF ALL LANDSCAPE MATERIALS AND
 LABOR, BROKEN DOWN INTO UNIT COST.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2010-05-14 Cont ID  
Sent By hmoser Date 2010-05-14 Time 13:57 Rev Time 0.00
Received By hmoser Date 2010-05-14 Time 12:21 Sent To  
Notes
2010-05-14 14:03:38PLAN DENIED
 1) PLEASE PROVIDE ON THE MECHANICAL PLANS ACCESS TO THE
 ROOF.
 2) PLEASE PROVIDE AIR CONDITIONING CONDENSATE ON
 MECHANICAL PLANS .
 PLAN REVIEW BY HAROLD MOSER 561-805-6730

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-10-06 Cont ID  
Sent By rregueir Date 2009-10-06 Time 09:27 Rev Time 0.00
Received By rregueir Date 2009-10-01 Time 10:48 Sent To E
Notes
2009-10-06 07:49:06REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ FIRST 2009 SUPPLEMENT
 FBC CHAPTER 1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M1 SHOWS CONDENSING UNIT LOCATED LESS THAN 10'
 FROM THE ROOF EDGE. GUARDS SHALL BE PROVIDED WHERE
 APPLIANCES ARE LOCATED WITHIN 10 FEET OF A ROOF EDGE IN
 ACCORDANCE WITH FBC-M 304.10. THE GUARD SHALL EXTEND
 NOT LESS THAN 30 INCHES BEYOND EACH END OF SUCH
 APPLIANCES AND THE TOP OF THE GUARD SHALL BE LOCATED
 NOT LESS THAN 42 INCHES ABOVE THE ELEVATED SURFACE
 ADJACENT TO THE GUARD. THE GUARD SHALL BE CONSTRUCTED
 SO AS TO PREVENT THE PASSAGE OF A 21-INCH-DIAMETER
 SPHERE AND SHALL COMPLY WITH THE LOADING REQUIREMENTS
 FOR GUARDS SPECIFIED IN THE FLORIDA BUILDING CODE,
 BUILDING.
  
 2. PLANS INDICATE RATED GYPSUM CEILING IN MOST, IF NOT
 ALL, AREAS. THE SPECIFIC CEILING TYPE IN THE KITCHEN IS
 NOT CLEAR. ACCESS TO AHU-1 LOCATED ABOVE THE CEILING
 SHALL BE SUFFICIENT TO ALLOW INSPECTION, SERVICE,
 REPAIR OR REPLACEMENT WITHOUT REMOVING SUCH ELEMENTS OF
 PERMANENT CONSTRUCTION OR DISABLING THE FUNCTION OF A
 REQUIRED FIRE-RESISTANCE-RATED ASSEMBLY IN ACCORDANCE
 WITH FBC-M 306.1.
  
 3. NEW MECHANICAL APPLIANCES ARE BEING INSTALLED ON THE
 ROOF. WHERE APPLIANCES REQUIRING ACCESS ARE INSTALLED
 ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT EXCEEDING,
 SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT APPROVED
 MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE FROM
 GRADE OR FLOOR LEVEL TO THE APPLIANCES' LEVEL SERVICE
 SPACE IN ACCORDANCE WITH FBC-M 306.5. SUCH ACCESS SHALL
 NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES HIGH OR WALKING ON ROOFS HAVING A SLOPE GREATER
 THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL.
  
 4. PAGE P1 SHOWS A CONDENSATE DRAIN LINE FROM THE
 CONDENSER AND NO DRAIN FROM THE AHU. CONDENSATE DRAIN
 SYSTEMS SHALL BE PROVIDED FOR APPLIANCES CONTAINING
 EVAPORATORS OR COOLING COILS IN ACCORDANCE WITH FBC-M
 307.2.
  
 5. PAGE P1 SHOWS CONDENSATE DISCHARGING INTO FLOOR
 DRAIN. CONDENSATE SHALL NOT DISCHARGE INTO SANITARY PER
 CITY ORDINANCE. CONDENSATE SHALL BE CONVEYED FROM THE
 DRAIN PAN OUTLET TO AN APPROVED PLACE OF DISPOSAL IN
 ACCORDANCE WITH FBC-M 307.2.1. CONDENSATE SHALL NOT
 DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS TO
 CAUSE A NUISANCE.
  
 6. DETAIL ON PAGE M3 SHOWS FLOAT SWITCH INSTALLED
 EXTERNALLY, INLINE ON THE PRIMARY DRAIN LINE. ON
 DOWN-FLOW UNITS, A WATER-LEVEL MONITORING DEVICE SHALL
 BE INSTALLED INSIDE THE PRIMARY DRAIN PAN. THIS DEVICE
 SHALL SHUT OFF THE EQUIPMENT SERVED IN THE EVENT THAT
 THE PRIMARY DRAIN BECOMES RESTRICTED. EXTERNALLY
 INSTALLED DEVICES AND DEVICES INSTALLED IN THE DRAIN
 LINE SHALL NOT BE PERMITTED IN ACCORDANCE WITH FBC-M
 307.2.3.1.
  
 7. PROVIDE PRODUCT APPROVALS FOR LOUVERS AND CONDENSER
 STAND IN ACCORDANCE WITH FBC-B 106.3.3 AND FAC RULE
 9B-72.
  
 8. AIR EXHAUST AND OPENINGS THAT TERMINATE OUTDOORS
 SHALL BE PROTECTED WITH CORROSION-RESISTANT SCREENS.
 OPENINGS SCREENS SHALL BE SIZED IN ACCORDANCE WITH
 TABLE 401.5.
  
 9. FOR RTU-1, RTU-2 AND RTU-3 PROVIDE MOTORIZED DAMPERS
 AT OUTSIDE AIR INTAKES WITH SHUTOFF DAMPER CONTROLS IN
 ACCORDANCE WITH FBC-B 13-409.AB.3.3.
  
 10. DUCT SMOKE DETECTORS AT RTUS AND AHU APPEAR TO BE
 LOCATED ABOVE A RATED GYPSUM CEILING. ACCESS SHALL BE
 PROVIDED TO SMOKE DETECTORS FOR INSPECTION AND
 MAINTENANCE IN ACCORDANCE WITH FBC-M 606.3 AND FBC-M
 306.1.
  
 11. PAGE E5 SHOWS A TOTAL OF 8 DUCT SMOKE DETECTORS
 WHILE MECHANICAL FLOOR PLAN (M1) SHOWS 4 DUCT SMOKE
 DETECTORS. PLEASE COORDINATE MECHANICAL AND FIRE ALARM
 PLANS AND SHOW COMPLIANCE WITH FBC-M 606.4.1.
  
 12. CELILNG FIRE DAMPER DETAILS ON PAGE M3 SHOW GRILL
 AND DAMPER TERMINATION AT THE RATED GYPSUM CEILING
 ASSEMBLY. DETAIL ON PAGE A6 SHOWS AREAS WITH LAY-IN
 CEILINGS BELOW THE RATED CEILING. THERE IS NO
 INSTALLATION CONFIGURATION WHICH COVERS THIS TYPE OF
 INSTALLATION. HOW WILL GRILLS AND DAMPERS TERMINATE AT
 GYPSUM CEILING WITH A LAY-IN CEILING BELOW IT? CEILING
 DAMPERS SHALL BE INSTALLED IN ACCORDANCE WITH THEIR
 LISTING AND THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS PER FBC-M 607.2.
  
 13. PAGE M1 SHOWS CEILING MOUNTED EXHAUST FANS AT
 TOILET ROOMS AND JANITOR'S CLOSET. SHOW HOW THESE
 PENETRATIONS OF THE FIRE RESISTANCE RATED CEILING ARE
 TO BE PROECTED IN ACCORDANCE WITH FBC-M 607.6.
  
 14. THE LOCATION OF EACH FIRE DAMPER SHALL BE SHOWN ON
 THE PAGE M1 FLOOR PLAN IN ACCORDANCE WITH FBC-M 607.8.
  
 15. THE PROPOSED SCOPE OF WORK CONSTITUTES A RENOVATION
 PER ENERGY CODE DEFINITIONS IN ACCORDANCE WITH FBC-B
 13-202. RENOVATED COMMERCIAL BUILDINGS SHALL COMPLY
 WITH METHOD B OF SUBCHAPTER 13-4 IN ACCORDANCE WITH
 FBC-B 13-101.1.3.
  
 16. PROVIDE MANUFACTURER'S DATA FOR OUTDOOR APPLIANCES
 SUCH AS RTUS AND CONDENSER. MECHANICAL APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES ON THE
 APPLIANCES AND THE SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FLORIDA BUILDING CODE, BUILDING PER FBC-M
 301.12. ROOF MOUNTED MECHANICAL UNITS AND SUPPORTS
 SHALL BE SECURED TO THE STRUCTURE. PROVIDE ENGINEERED
 INSTALLATION INSTRUCTIONS FOR ROOF CURBS TO THE
 BUILDING STRUCTURE AND FOR APPLIANCES TO THE ROOF
 CURBS.
  
 17. THE VALUE FOR THE PROPOSED SCOPE OF WORK AS STATED
 ON THE PERMIT APPLICATION APPEARS TO BE TOO LOW BASED
 ON ICC VALUATION TABLES FOR THE LEVEL OF ALTERATION AND
 THE TYPE OF CONSTRUCTION. PROVIDE A VALUATION MORE IN
 LINE WITH ACCEPTED VALUATION TABLES OR PRODUCE A SGNED
 CONTRACT WHICH SHOWS THE ACTUAL CONTRACT VALUE OF THE
 WORK BEING PERFORMED IN ACCORDANCE WITH FBC-B 108.3.
  
 NOTE: SPEARATE PLANS, PERMIT APPLICATIONS AND VALUES
 ARE REQUIRED FOR THE FOLLOWING AND ARE NOT PART OF THE
 SCOPE OF THIS PLAN REVIEW:
 1. WALK-IN AND REACH-IN COOLERS, FREEZERS AND OTHER
 ASSOCIATED REFRIGERATION EQUIPMENT.
 2. COMMERCIAL KITCHEN COOKING AND VANTILATION EQUIPMENT
 AND SYSTEMS.
 3. COMMERCIAL KITCHEN HOOD FIRE SUPPRESSION SYSTEMS.
  
 PLEASE RESPOND TO EACH COMMENT IN WRITING WITH
 SUFFICIENT DETAIL AND INFORMATION TO SHOW HOW EACH
 COMMNT WAS ADDRESSED AND WHERE THE RELEVANT INFORMATION
 CAN BE LOCATED. THIS WILL HELP TO FACILITATE A TIMELY
 SUBSEQUENT REVIEW.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-04-20 Cont ID  
Sent By lwagner Date 2010-04-20 Time 13:03 Rev Time 0.00
Received By lwagner Date 2010-04-19 Time 13:52 Sent To  
Notes
2010-04-20 08:50:15REVISION REQUIRED P-3 & P-4
  
 PLEASE ADD WATER COOLER TO ISO'S ON P-3 & P-4.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-09-30 Cont ID  
Sent By kstevens Date 2009-09-30 Time 09:55 Rev Time 0.00
Received By kstevens Date 2009-09-29 Time 16:54 Sent To  
Notes
2009-09-30 10:22:13DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 BUILDING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS A-4 & P-2 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. INDICATE THE TOTAL SQUARE
 FOOTAGE BEING DRAINED BY EACH ROOF DRAIN, GUTTER &
 DOWNSPOUT. CALCULATIONS SHALL SHOW 1/2 THE AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS AS WELL AS THE AREA
 OF A ROOF DRAINING ON TO THE ROOF FROM ABOVE ADDED TO
 EACH AREA. THE GUTTER AND DOWNSPOUT SIZE SHALL BE
 INDICATED. TABLES 1106.2 & 1106.6.
  
 2. ALL SHEETS WITH RUIZ - BRITO TITLE BLOCK SHALL
 INCLUDE THE FIRM LICENSE NUMBER PER FAC 61G1-16.004(2)
 AND THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT
 PER FAC 61G1-16.004(7). FS 481.219 & 481.2055.
  
 3. SHTS A-8, P-1 & P-4 INDICATE GAS HEATER &
 APPLIANCES. SEE GAS REVIEW FOR SEPARATE GAS
 PERMIT/PLANS/REQUIRMENTS.
  
 4. SHT P-1 FLOOR DRAINS IN THE MEAT CUTTING/STORAGE
 AREAS. THE MAXIMUM DISTANCE FROM THE 3" FLOOR DRAINS TO
 THE VENT IS 12 FEET PER TABLE 906.1. THE FLOOR DRAINS
 PER THE 1/8TH SCALE ARE INDICATED AS BEING 14 TO 16
 FEET FROM THE VENT.
  
 5. SHT P-1 DELI AREA NOTE STATES "8 INCH RWL 4,962 SF",
 BUT NO ROOF DRAIN IS SHOWN. PLEASE CLARIFY. SECTION
 106.1.1 & TABLE 1106.3.
  
 6. SHTS P-1 & P-3 INDICATE NEW FIXTURES DRAINING INTO
 THE EXISTING GREASE INTERCEPTOR. THE GREASE INTERCEPTOR
 SHALL BE INSPECTED FOR SIZE AND TO MAKE SURE IT IS
 OPERATING PROPERLY. ARTICLE III SECTION 90-124(7).
 PLEASE CONTACT HOLLY MCGRATH LABORATORY SUPERVISOR,
 PUBLIC UTILITIES DEPARTMENT FOR INSPECTION AND APPROVAL
 OF EXISTING GREASE INTERCEPTOR. A WRITTEN DETERMINATION
 IS REQUIRED PRIOR TO PERMIT BEING ISSUED.
  
 7. SHT P-4 WATER ISOMETRIC. AIR CHAMBERS SHOWN AT EACH
 FIXTURE ARE NOT APPROVED. PLEASE DELETE FROM ISOMETRIC.
 PDI-WH 201.
  
 8. SHT P-5 PLUMBING NOTES # 9. AIR CHAMBERS ARE NOT
 APPROVED. PLEASE DELETE FROM NOTE. PDI-WH 201.
  
 9. SHT P-5 WATER HEATER DETAIL. THERMAL EXPANSION
 CONTROL IS REQUIRED PER SECTION 607.3.2. PLEASE
 INDICATE METHOD.
  
 10. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE
 TO THE BUILDING. PLEASE INDICATE IF THERE IS AN
 EXISTING RPZV BACKFLOW OR IF A BACKFLOW WILL BE
 INSTALLED. SECTION 608.13.2.
  
 11. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE SHOW THE LOCATION OF THE REQUIRED DRINKING
 FOUNTAIN. ALSO SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 12. SUBMIT A DETAIL FOR THE TOILET ROOMS SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22
 WITH ALL SUBSECTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2010-04-20 Cont ID  
Sent By eschneid Date 2010-04-20 Time 14:21 Rev Time 1.25
Received By eschneid Date 2010-04-20 Time 14:21 Sent To  
Notes
2010-04-20 17:45:29FAILED
  
 PROVIDE RESPONSES IN WRITING.
  
 1) THE CLASS B SPECIAL USE PERMIT TO ALLOW THE
 EXPANSION OF THE GROCERY STORE TO GREATER THAN 10,000
 SQUARE FEET EXPIRED ON JANUARY 4, 2010. CONTACT THE
 ZONING DIVISION FOR THE PROCEDURE TO EXTEND THE
 DEVELOPMENT ORDER.
  
 2) REPEAT COMMENT: THE LANDSCAPE PLANS DO NOT SHOW THE
 SAME CONDITIONS AS THE SITE PLAN, SPECIFICALLY, THE
 DIMENSIONS OF THE LANDSCAPE AREA AND CURB LOCATIONS ON
 THE NORTH SIDE OF THE BUILDING.
  
 3) REPEAT COMMENT: THE PHOTOMETRIC PLAN SHALL SHOW THE
 FOOT CANDLE LEVELS AT THE WEST PROPERTY LINE - THIS
 SHALL NOT EXCEED 0.5 FOOT CANDLES.
  
 4) NEW COMMENT: THE PHOTOMETRIC PLAN(SHEET E-7) AND
 SHEET E-6 WERE NOT UPDATED TO SHOW THE LIGHT POST
 LOCATIONS AS SHOWN ON THE LANDSCAPE PLAN. THE NEW LIGHT
 POST LOCATIONS AVOID TREE CONFLICTS.
  
 5) REPEAT COMMENT: THE BMUD TYPE II REGULATIONS REQUIRE
 THAT THE FINISHED FLOOR TO FINISHED CEILING OF THE
 GROUND FLOOR BE AT LEAST 12 FEET - SHEET A-7 SHOWS THE
 CEILING HEIGHT OF 11 FEET 2 INCHES. RESPONSE STATES
 THERE ARE EXISTING STRUCTURAL CONDITIONS WHICH DO NOT
 ALLOW HIGHER CEILING. THIS NEEDS TO BE DEMONSTRATED ON
 THE PLANS. IT IS STAFF'S UNDERSTANDING THAT THE
 EXISTING CEILING HEIGHTIS HIGHER THAN 11 FEET 2 INCHES.
  
 6) NEW COMMENT: SHEET A-3 SHOWS NEW EQUIPMENT BEING
 INSTALLED ON THE EXTERIOR OF THE WESTERN BUILDING WALL.
 WHAT IS THIS? IT IS NOT SHOWN ON THE SITE OR LANDSCAPE
 PLANS. MECHANICAL EQUIPMENT SHALL BE SCREENED IN
 ACCORDANCE WITH THE BMUD REGULATIONS AND MEET ALL SET
 BACK REQUIREMENTS.
  
 7) NEW COMMENT: SHEET A-4 SHOWS NEW EQUIPMENT ON THE
 ROOF (RT-1, RT-2 AND RT-3) AND SHEET E-3 REFERENCES
 CU-1 ABOVE ROOF. PROVIDE FULL HEIGHT OF THIS EQUIPMENT
 FROM THE ROOF TOP (INC. STANDS). MECHANICAL EQUIPMENT
 SHALL BE SCREENED IN ACCORDANCE WITH THE BMUD
 REGULATIONS. THE NEW EQUIPMENT AND ANY NEW SCREENING
 SHALL BE SHOWN ON THE ELEVATIONS.
  
 8) NOTE: ANY NEW FENCES OR WALLS, EXCLUDING THE CART
 RETURN SCREEN, THE SIGNAGE, THE IRRIGATION SYSTEM AND
 THE BENCHES REQUIRE SEPARATE PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-09-22 Cont ID  
Sent By eschneid Date 2009-09-22 Time 14:30 Rev Time 1.00
Received By eschneid Date 2009-09-22 Time 14:30 Sent To  
Notes
2009-09-22 14:41:43FAILED
  
 1) THE LANDSCAPE PLANS DO NOT SHOW THE SAME CONDITIONS
 AS THE SITE PLAN, SPECIFICALLY, THE DIMENSIONS OF THE
 LANDSCAPE AREA AND CURB LOCATIONS ON THE NORTH SIDE OF
 THE BUILDING, AND THE INTERIOR PARKING AREA ON THE
 SOUTH SIDE OF THE BUILDING.
  
 2) THE PHOTOMETRIC PLAN SHALL SHOW THE FOOT CANDLE
 LEVELS AT THE WEST PROPERTY LINE - THIS SHALL NOT
 EXCEED 0.5 FOOT CANDLES.
  
 3) THE BMUD TYPE II REGULATIONS REQUIRE THAT THE
 FINISHED FLOOR TO FINISHED CEILING OF THE GROUND FLOOR
 BE AT LEAST 12 FEET - SHEET A-7 SHOWS THE CEILING
 HEIGHT OF 11 FEET 2 INCHES.
  
 4) THE LIGHT POST LOCATIONS SHALL BE SHOWN ON THE
 LANDSCAPE PLAN. PLEASE NOT THAT THERE APPEARS TO BE A
 TREE - POST CONFLICT ALONG THE WEST PROPERTY LINE.
  
 5) ANY NEW FENCES OR WALLS, EXCLUDING THE CART RETURN
 SCREEN, SIGNAGE, AND THE BENCHES REQUIRE SEPARATE
 PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.