Plan Review Details - Permit 09090216
Plan Review Stops For Permit 09090216
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-09-15 Cont ID  
Sent By jwitmer Date 2009-09-15 Time 17:58 Rev Time 1.00
Received By jwitmer Date 2009-09-15 Time 17:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-10-15 Cont ID  
Sent By dpalmer Date 2009-10-15 Time 16:37 Rev Time 0.00
Received By dpalmer Date 2009-10-15 Time 16:37 Sent To  
Notes
2009-10-15 16:37:23LOW VOLTAGE UNDER SEPARATE PERMITS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-09-16 Cont ID  
Sent By dpalmer Date 2009-09-16 Time 19:37 Rev Time 0.00
Received By dpalmer Date 2009-09-16 Time 19:37 Sent To  
Notes
2009-09-16 19:14:21 
 ** DENIED PLANS**
  
  
 1) NOTE: THE SUBMITTED FORM B DOES NOT MEET
 13-415.AB.5, 13-415.B.1. THE FORM IS NOT COMPLETED FOR
 ANY SPACE OR TYPE OF FIXTURES. THE SPACES ARE IN FACT
 BLANK. IN EITHER CASE IF CHOOSING TO USE ALL FORM B*S
 FOR COMPLIANCE ONE FORM B IS REQUIRED FOR EACH AND
 EVERY SPACE TYPE IN ORDER TO MEET SPACE BY SPACE.
 MUST ONLY MEET PRESCRIPTIVE FOR LIGHTING PERFORMANCE
 CALCULATIONS. IT IS RECOMMENDED CALLING REVIEWER TO GO
 OVER MINIMUM COMPLIANCE.
 IF ADDING LIGHTS TO EXISTING THEN LIGHTING COMPLIANCE
 IS REQUIRED TO BE SHOWN FOR ALL.
 ** THE FIXTURE LEGEND CLEARLY STATES *ALL* FIXTURES ARE
 EXISTING HOWEVER PER THE LIGHTING PLANS THERE ARE *NEW*
 FIXTURES. HOW ARE ALL FIXTURES EXISTING AND NEW?
  
 2) NOTE: PLEASE SEE 422.30,31 FOR REQUIRED
 DISCONNECTING MEANS FOR IWH.
 PLEASE SEE CIRCUIT 701-3 WHICH IS NOTED ON PANEL
 SCHEDULE CONTAINING A LOCK OFF DEVICE. PLEASE SEE
 SECTIONS AND COMMENTARY. A DEVICE SHALL BE PERMANENT TO
 BREAKER. MUST BE AN INTEGRAL PART OF BREAKER. MAY NOT
 BE A *CLIP ON* OR *SNAP ON* TYPE DEVICE. IF THERE IS
 ANY NEED TO CLARIFICATION SEE UPDATED COMMENTARY UNDER
 THE 2008 NEC.
 THE IWH AS CIRCUITED TO 1702.14 DOE NOT CONTAIN ANY
 NOTE AS ABOVE. WHERE IS THE REQUIRED DISCONNECTING
 MEANS?
  
 3) NOTE: NO SOUND LEVELS INDICATED ON FA SHEETS MEETING
 ADA COMPLIANCE PER 11-4.28.1,.2 AND .3.
 PLEASE PROVIDE.
  
 4) NOTE: PLEASE PROVIDE MORE DETAILED INFORMATION ON
 NEW LIGHTING CONTROLS( TIME CLOCK) NOTED ON PLANS.
 13-415.AB.1.1,.1.2.
 PLEASE ALSO BE AWARE, ALL LIGHTING BEING OVER RIDDEN
 SHALL BE SEEN BY THE OCCUPANT OR MEET EXCEPTIONS. (
 PILOT LIGHTS AND INDICATION OF LIGHTING).
  
 5) NOTE: PLANS STATE THE *LATEST EDITION* OF THE
 NATIONAL ELECTRICAL CODE. HOWEVER PER FS 553.73, RULE
 9B-3.047 THE 2008 HAS NOT YET BEEN ADOPTED BY THE STATE
 OF FLORIDA. NOT UNTIL PERMIT APPLICATIONS AFTER OCT
 1ST, 2009.
 PLEASE ALSO BE AWARE THERE ARE OTHER REVISIONS TO THE
 FBC AT THAT DATE.
 PLEASE BE SURE THE PLANS INDICATE THE MINIMUM CODE AS
 FOLLOWS.
 2005 NFPA-70
 2006 NFPA-101
  
 ** PLANS STATE 2007 FBC ON G-1, HOWEVER THERE ARE 2009
 GLITCHES TO THE 2007 FBC WHICH SUBSTANTIALLY REVISED
 THE CODE.
 PLANS ALSO STATE THE 2006 FLORIDA FIRE PREVENTION CODE.
 THIS SHOULD READ 2007 PER FAC 69A-3.012. REVISED
 NFPA-101 AND NFPA-1 IS PER FAC 69A-60.003, .004.
  
  
  
  
 ** AS STATED ABOVE. PLEASE CALL TO GO OVER ANY
 COMMENTS.
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-10-20 Cont ID  
Sent By mawillia Date 2009-10-20 Time 10:39 Rev Time 0.00
Received By mawillia Date 2009-10-20 Time 10:19 Sent To B
Notes
2009-10-20 10:36:18*****APPROVED*****
  
  
 PLAN SHEETS E-2 AND FA-1 WERE STAMPED, INITIALED, AND
 DATED; SHEETS A-1, A-3, FP-1, FP-2, AND FA-1 WERE
 PREVIOUSLY FIRE-STAMPED ON 09/23/2009.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-09-23 Cont ID  
Sent By mawillia Date 2009-09-23 Time 12:51 Rev Time 0.00
Received By mawillia Date 2009-09-23 Time 12:11 Sent To  
Notes
2009-09-23 12:51:31*****PARTIAL APPROVAL*****
  
  
 PLAN SHEETS A-1, A-3, FP-1, FP-2, AND FA-1 WERE
 STAMPED, INITIALED, AND DATED; HOWEVER SHEET E-2 TO BE
 FIRE-STAMPED WHEN THE ELECTRICAL EXAMINER'S COMMENTS
 HAVE BEEN ADDRESSED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-10-28 Cont ID  
Sent By rmcdouga Date 2009-10-28 Time 10:51 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2009-10-28 10:52:44TO K STEVENS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-10-14 Cont ID  
Sent By rmcdouga Date 2009-10-14 Time 11:21 Rev Time 0.00
Received By rmcdouga Date 2009-10-13 Time 11:21 Sent To  
Notes
2009-10-14 11:23:13B-21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-09-23 Cont ID  
Sent By mawillia Date 2009-09-23 Time 12:11 Rev Time 0.00
Received By mawillia Date 2009-09-10 Time 17:52 Sent To  
Notes
2009-09-10 17:55:11B-2

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2009-09-10 Cont ID  
Sent By lmartine Date 2009-09-10 Time 17:55 Rev Time 0.00
Received By lmartine Date 2009-09-10 Time 17:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-09-17 Cont ID  
Sent By rregueir Date 2009-09-17 Time 08:07 Rev Time 0.00
Received By rregueir Date 2009-09-17 Time 08:07 Sent To  
Notes
2009-09-17 08:09:00ENERGY CODE COMPLIANCE FORM NOT REVIEWED. IT IS NOT
 REQUIRED ON THIS PROJECT TO DEMONSTRATE COMPLIANCE WITH
 THE MECHANICAL PROVISIONS OF THE FLORIDA ENERGY CODE.

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-11-02 Cont ID  
Sent By kstevens Date 2009-11-02 Time 10:55 Rev Time 0.00
Received By kstevens Date 2009-11-02 Time 10:55 Sent To  
Notes
2009-11-02 10:56:10REVISION OK -- SHTS A-1, A-2 & A-3.

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-09-16 Cont ID  
Sent By kstevens Date 2009-09-16 Time 17:49 Rev Time 0.00
Received By kstevens Date 2009-09-16 Time 17:49 Sent To  
Notes
2009-09-16 17:56:16 
  
 PASSED/PROVISO:
  
 REVISIONS REQUIRED:
  
 SHT A-1 SHOW CLEAR FLOOR SPACE FOR SINKS IN 1702 &
 1714. SECTION 11-4.24.3.
 SHT A-3 DELETE CABINET DOORS DETAILS 1/A-3 ROOM 1714 &
 3/A-3 ROOM 1702. NO DOORS IN CLEAR FLOOR SPACE.SECTION
 11-4.24.3.
 SHT A-3 SHOW SINK DEPTH IN DETAILS . 11-4.24.4.
 SHT A-3 SHOW COMPLIANCE WITH 11-4.24.5 EXPOSED PIPES &
 SURFACES.
 SHT A-3 SHOW COMPLIANCE WITH 11-4.24.6 FAUCETS.
  
  
 .
  