Plan Review Details - Permit 09090108
Plan Review Stops For Permit 09090108
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2010-04-15 Cont ID  
Sent By btrobaug Date 2010-04-15 Time 11:20 Rev Time 0.00
Received By btrobaug Date 2010-04-15 Time 11:20 Sent To  
Notes
2010-04-15 11:21:29OK PER DOUG./WRT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2010-02-10 Cont ID  
Sent By shill Date 2010-02-10 Time 15:08 Rev Time 0.00
Received By shill Date 2010-02-10 Time 15:08 Sent To  
Notes
2010-02-10 15:10:40****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1. THE GENERATOR INFORMATION STATES THAT THE ENCLOSURE
 MEETS WIND LOAD ANALYSIS FOR ASCE7-88, WIND VELOCITY
 150. ASCE7-88 USED FASTEST MILE, WHICH CONVERTED TO 3
 SECOND GUST WOULD BE 130MPH. THE CITY OF WEST PALM
 BEACH LIES ENTIRELY WITHIN THE 140MPH ZONE. ALSO, IT
 APPEARS THAT THIS IS LOCATED IN EXPOSURE C (LARGE BODY
 OF WATER TO THE EAST, SEE DEFINITION OF EXPOSURE C
 REVISED IN FBC2007 AND ASCE7-05).
  
 INSTALLATION - AND ENCLOSURE - IS TO RESIST WIND LOADS
 (SLIDING, OVERTURNING) FBC1609. PROVIDE INSTALLATION
 SPECIFICATION TO COMPLY WITH FBC1609, AND DECLARE WIND
 DESIGN CRITERIA PER FBC1603.1.4.
  
 2ND & 3RD REVIEWS:
  
 THE SECOND PORTION OF THE COMMENT WAS ADDRESSED WITH
 THE ENGINEERING FROM PAUL KING, PE.
  
 THE FIRST PORTION OF THE COMMENT HAS NOT BEEN
 ADDRESSED. THE ENGINEERING PROVIDED CALCULATIONS FOR
 THE ATTACHMENT OF THE GENERATOR TO THE SLAB, BUT THE
 COMMENT IS THAT THE ENCLOSURE IS TO MEET WIND DESIGN
 CRITERIA AND THE GENERATOR DOCUMENTATION DOES NOT SHOW
 COMPLIANCE WITH THAT REQUIREMENT.
  
 PLEASE SHOW HOW THE GENERATOR ENCLOSURE IS DESIGNED TO
 RESIST WIND LOADS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-12-16 Cont ID  
Sent By shill Date 2009-12-16 Time 11:15 Rev Time 0.00
Received By shill Date 2009-12-16 Time 10:03 Sent To  
Notes
2009-12-16 11:18:25****CORRECTIONS****
 ****WILL PASS WITH PROVISO UPON REQUEST***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1. THE GENERATOR INFORMATION STATES THAT THE ENCLOSURE
 MEETS WIND LOAD ANALYSIS FOR ASCE7-88, WIND VELOCITY
 150. ASCE7-88 USED FASTEST MILE, WHICH CONVERTED TO 3
 SECOND GUST WOULD BE 130MPH. THE CITY OF WEST PALM
 BEACH LIES ENTIRELY WITHIN THE 140MPH ZONE. ALSO, IT
 APPEARS THAT THIS IS LOCATED IN EXPOSURE C (LARGE BODY
 OF WATER TO THE EAST, SEE DEFINITION OF EXPOSURE C
 REVISED IN FBC2007 AND ASCE7-05).
  
 INSTALLATION IS TO RESIST WIND LOADS (SLIDING,
 OVERTURNING) FBC1609. PROVIDE INSTALLATION
 SPECIFICATION TO COMPLY WITH FBC1609, AND DECLARE WIND
 DESIGN CRITERIA PER FBC1603.1.4.
  
 2ND REVIEW:
  
 THE SECOND PORTION OF THE COMMENT WAS ADDRESSED WITH
 THE ENGINEERING FROM PAUL KING, PE.
  
 THE FIRST PORTION OF THE COMMENT HAS NOT BEEN
 ADDRESSED. THE ENGINEERING PROVIDED CALCULATIONS FOR
 THE ATTACHMENT OF THE GENERATOR TO THE SLAB, BUT THE
 COMMENT IS THAT THE ENCLOSURE IS TO MEET WIND DESIGN
 CRITERIA AND THE GENERATOR DOCUMENTATION DOES NOT SHOW
 COMPLIANCE WITH THAT REQUIREMENT.
  
 UPON REQUEST, THIS REVIEW CAN BE PASSED WITH PROVISO,
 REVISION REQUIRED, AT CONTRACTOR'S RISK, SHOW
 COMPLIANCE WITH 140MPH EXPOSURE C FOR GENERATOR
 ENCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-09-23 Cont ID  
Sent By shill Date 2009-09-23 Time 14:32 Rev Time 0.00
Received By shill Date 2009-09-23 Time 14:32 Sent To  
Notes
2009-09-23 14:55:04****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THE GENERATOR INFORMATION STATES THAT THE ENCLOSURE
 MEETS WIND LOAD ANALYSIS FOR ASCE7-88, WIND VELOCITY
 150. ASCE7-88 USED FASTEST MILE, WHICH CONVERTED TO 3
 SECOND GUST WOULD BE 130MPH. THE CITY OF WEST PALM
 BEACH LIES ENTIRELY WITHIN THE 140MPH ZONE. ALSO, IT
 APPEARS THAT THIS IS LOCATED IN EXPOSURE C (LARGE BODY
 OF WATER TO THE EAST, SEE DEFINITION OF EXPOSURE C
 REVISED IN FBC2007 AND ASCE7-05).
  
 INSTALLATION IS TO RESIST WIND LOADS (SLIDING,
 OVERTURNING) FBC1609. PROVIDE INSTALLATION
 SPECIFICATION TO COMPLY WITH FBC1609, AND DECLARE WIND
 DESIGN CRITERIA PER FBC1603.1.4.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2010-04-15 Cont ID  
Sent By btrobaug Date 2010-04-15 Time 11:14 Rev Time 0.00
Received By btrobaug Date 2010-04-15 Time 11:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2010-02-01 Cont ID  
Sent By dpalmer Date 2010-02-01 Time 14:20 Rev Time 0.00
Received By dpalmer Date 2010-01-28 Time 15:41 Sent To  
Notes
2010-01-28 15:42:36ON HOLD WAITING FOR CONTRACTOR TO MAKE SETS. ONE SET
 HAS NEW SHEETS NOT IN OLD SET. OLD SET HAS SHEETS NOT
 IN NEW SETS.
 SPOKE TO CONT REP TWICE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-12-09 Cont ID  
Sent By dpalmer Date 2009-12-09 Time 08:57 Rev Time 0.00
Received By dpalmer Date 2009-12-09 Time 08:57 Sent To  
Notes
2009-12-09 08:57:24** DENIED **
  
 ** SETS OF PLANS SUBMITTED ARE NOT THE SAME.
 ONE SET HAD ALL COMPLETE ELECTRICAL PAGES WHICH WERE
 NOT REQUESTED ON PREVIOUS REVIEW.
 ONE SET HAS PLUMBING SHEETS WHICH ARE NOT IN THE SECOND
 SET??
  
  
 2ND REQUEST
 1) NOTE: PLEASE PROVIDE INFORMATION ON THE TYPE OF BACK
 UP SYSTEM OF THIS GENERATOR. PLEASE SEE DEFINITIONS IN
 NEC/ NFPA-70 2008, 700,701, AND 702.
 PLEASE ALSO SEE 2005 NFPA-110.
 THE BASE BUILDING PLANS WERE ALSO SUBMITTED HOWEVER NOT
 ALL EMERGENCY LIGHTS ON THE FIXTURE LEGEND INDICATE
 BATTERY BACK UP. ALL REQUIRED EMERGENCY BACK UP POWER
 MUST BE FED FROM 700 OR 701 SYSTEMS. IF BATTERY BACK UP
 POWER IS PROVIDED FOR ALL LIFE SAFETY AND LEGALLY
 REQUIRED THEN THIS SYSTEM WOULD BE OPTION STAND-BY.
 IF THIS IS A 700 OR 701 SYSTEM IT MAY NOT RELY ON
 NATURAL GAS AS THE PRIMARY SOURCE FOR THE PRIME MOVER.
 700.12B3, 701.11B3.
 PLEASE REDESIGN SYSTEM IF INDEED FALLING UNDER NFPA-70,
 700,701 OR NFPA-110
  
 ** THERE WAS NO RESPONSE FROM THE DESIGNER OF RECORD TO
 PREVIOUS ELECTRICAL REVIEW COMMENTS. A CALL WAS PLACED
 TO THE ARCHITECT OF RECORD AS THE PHONE NUMBER LISTED
 ON TITLE BLOCK IS NO LONGER IN USE. NEW NUMBER FOR
 ENGINEER WAS OBTAINED FROM ARCHITECT AND LEFT MESSAGE
 ON 12/8 FOR A RETURN CALL.
  
 PLANS WILL REMAIN IN FAILED STATUS UNTIL INFORMATION IS
 PROVIDED OR PLANS ARE REVISED.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-13 Cont ID  
Sent By dpalmer Date 2009-10-13 Time 11:16 Rev Time 0.00
Received By dpalmer Date 2009-10-13 Time 11:16 Sent To B
Notes
2009-10-13 11:16:57** DENIED **
  
 ** ORIGINAL REVIEW WAS DONE ON 9/24 HOWEVER DID NOT GET
 INTO THE SYSTEM. NOTES ADDED 10/13
  
  
 1) NOTE: PLANS SUBMITTED ARE IN FACT PHOTO-COPIES OF
 SIGNED, DATED AND SEALED ENGINEERED PLANS. MUST CONTAIN
 ORIGINAL SIGNATURE, DATE AND SEAL PER FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002, FS 471.025
  
 2) NOTE: RISER INDICATES AN INTERLOCK ENCLOSURE OF SOME
 TYPE. PLEASE PROVIDE EQUIPMENT SPECS MEETING MINIMUM
 LISTING PER UL 1081. IT ALSO INDICATES A NOTE #2, FOR
 WHAT STATES TO BE AS A NEW AUTOMATIC TRANSFER SWITCH.
 PLEASE REVISE RISER IF THIS IS INDEED GOING TO BE
 CHANGED OUT.
  
 3) NOTE: NO PANEL SCHEDULE FOR PANEL *E* COULD BE
 LOCATED. PLEASE SUBMIT SO THAT LOADS CAN BE VERIFIED.
 IT IS NOT POSSIBLE TO REVIEW FOR MINIMUM SIZING PER
 702.5, 220 OF THE NEC AT THIS TIME.
  
 4) NOTE: PLEASE PROVIDE INFORMATION THAT THIS SYSTEM IS
 AN OPTIONAL STAND-BY SYSTEM AND IT DOES NOT SERVE ANY
 LEGALLY REQUIRED 701, OR EMERGENCY 700 SYSTEMS.
 ** BASE BUILD OUT PLANS WERE NOT UNDER THE REVIEW OF
 THIS REVIEWER AND LOADS ARE NOT KNOWN AT THIS TIME.
  
 5) NOTE: PLEASE SEE 702.11. IN ORDER TO MEET EXCEPTIONS
 IN 225.31-225.39 THE DISCONNECTING MEANS AT GENERATOR
 MUST BE READILY ACCESSIBLE. PLANS APPEAR TO SHOW IT
 MEETING OTHER EXCEPTION WHICH IS IT MUST BE *WITHIN
 SITE*. SEE NEC 100.
  
 6) NOTE: PLEASE LABEL MAINS PER 230.2 E
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2010-02-09 Cont ID  
Sent By mawillia Date 2010-02-09 Time 13:45 Rev Time 0.00
Received By mawillia Date 2010-02-09 Time 13:26 Sent To  
Notes
2010-02-09 13:39:08*****APPROVED*****
  
  
 PLAN SHEET LS-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-12-28 Cont ID  
Sent By mawillia Date 2009-12-28 Time 12:40 Rev Time 0.00
Received By mawillia Date 2009-12-28 Time 12:21 Sent To  
Notes
2009-12-28 12:39:53*****FIRE-STAMP NEEDED*****
  
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN PLAN
 SHEETS HAVE BEEN PACKAGED TOGETHER AS ORDERLY SETS.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-10-01 Cont ID  
Sent By mcarsill Date 2009-10-01 Time 08:40 Rev Time 0.00
Received By mcarsill Date 2009-10-01 Time 08:05 Sent To  
Notes
2009-10-01 08:40:172007 PALM BEACH LAKES BOULEVARD
  
 1. PLEASE INDICATE WHAT SYSTEMS OR DEVICES THE
 GENERATOR WILL SUPPLY POWER TO.
  
 2. PLANS DO NOT INDICATE ANY DOORS OR WINDOW OPENINGS
 LOCATED NEAR THE GENERATOR. PLEASE INDICATE THAT NO
 WINDOW OR DOOR OPENINGS EXIST WITHIN 10 FEET VERTICALLY
 OR HORIZONTALLY OF THE GENERATOR.
  
 3. THE SURVEY APPEARS TO HAVE BEEN PREPARED IN 2007 AND
 IS OVER TWO YEARS OLD.
  
 4. NO DIMENSIONS PROVIDED WHERE THE GENERATOR IS
 PLANNED TO BE INSTALLED AND THE BUILDING. PLEASE
 PROVIDE DIMENSIONS.
  
 5. ALL DRAWINGS IN THE SUBMITTAL PACKAGE ARE COPIES TO
 INCLUDE SIGNATURES.
  
 6. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE. PLEASE DOCUMENT THIS ON THE
 DRAWINGS.
  
 DENIED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 (561) 804-4709 PHONE
 (561) 804-4774 FAX

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2009-09-14 Cont ID  
Sent By kstevens Date 2009-09-14 Time 14:27 Rev Time 0.00
Received By kstevens Date 2009-09-14 Time 14:27 Sent To  
Notes
2009-09-14 14:28:11NO GAS PLANS SUBMITTED. -- SEPARATE GAS PLANS/PERMIT
 REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-04-15 Cont ID  
Sent By btrobaug Date 2010-04-15 Time 11:21 Rev Time 0.00
Received By btrobaug Date 2010-01-19 Time 10:20 Sent To  
Notes
2010-01-21 10:23:13C-27

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-11-18 Cont ID  
Sent By lmartine Date 2009-11-18 Time 17:06 Rev Time 0.00
Received By lmartine Date 2009-11-18 Time 17:06 Sent To  
Notes
2009-11-18 17:09:36C--15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-10-13 Time   Rev Time 0.00
Received By jwitmer Date 2009-09-08 Time 10:53 Sent To  
Notes
2009-09-08 10:57:44GENERATOR: 30 KW TO- C 24

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-09-21 Cont ID  
Sent By rregueir Date 2009-09-21 Time 13:39 Rev Time 0.00
Received By rregueir Date 2009-09-21 Time 13:37 Sent To  
Notes
2009-09-21 13:39:24APPEARS TO BE LP GENERATOR. SEE GAS PLAN REVIEW
 COMMENTS.

Review Stop Z ZONING
Rev No 2 Status P Date 2009-12-07 Cont ID  
Sent By eschneid Date 2009-12-07 Time 17:20 Rev Time 0.20
Received By eschneid Date 2009-12-07 Time 17:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-09-17 Cont ID  
Sent By eschneid Date 2009-09-17 Time 18:19 Rev Time 0.50
Received By eschneid Date 2009-09-17 Time 18:19 Sent To  
Notes
2009-09-17 18:22:42FAILED
  
 1) THE PROPOSED GENERATOR LOCATION CONFLICTS WITH
 PARKING AND LANDSCAPE THAT THE PROPERTY OWNER IS
 PLANNING TO INSTALL AS SHOWN ON SITE AND LANDSCAPE
 PLANS THAT WILL BE SUBMITTED SHORTLY FOR PERMITS.
  
 2) GENERATORS ARE REQUIRED TO BE SCREENED WITH A
 FENCE/WALL AND LANDSCAPE. PERMITS AND PLANS ARE
 REQUIRED FOR THE SCREENING PRIOR TO THE ISSUANCE OF A
 GENERATOR PERMIT.
  
 3) PLEASE PROVIDE DETAILS AS TO THE LOCATION OF THE
 ATS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.