Plan Review Stops For Permit 09090108 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2010-04-15 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2010-04-15 |
Time |
11:20 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2010-04-15 |
Time |
11:20 |
Sent To |
|
|
Notes |
2010-04-15 11:21:29 | OK PER DOUG./WRT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2010-02-10 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2010-02-10 |
Time |
15:08 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2010-02-10 |
Time |
15:08 |
Sent To |
|
|
Notes |
2010-02-10 15:10:40 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | FROM PREVIOUS LIST: | | | | 1. THE GENERATOR INFORMATION STATES THAT THE ENCLOSURE | | MEETS WIND LOAD ANALYSIS FOR ASCE7-88, WIND VELOCITY | | 150. ASCE7-88 USED FASTEST MILE, WHICH CONVERTED TO 3 | | SECOND GUST WOULD BE 130MPH. THE CITY OF WEST PALM | | BEACH LIES ENTIRELY WITHIN THE 140MPH ZONE. ALSO, IT | | APPEARS THAT THIS IS LOCATED IN EXPOSURE C (LARGE BODY | | OF WATER TO THE EAST, SEE DEFINITION OF EXPOSURE C | | REVISED IN FBC2007 AND ASCE7-05). | | | | INSTALLATION - AND ENCLOSURE - IS TO RESIST WIND LOADS | | (SLIDING, OVERTURNING) FBC1609. PROVIDE INSTALLATION | | SPECIFICATION TO COMPLY WITH FBC1609, AND DECLARE WIND | | DESIGN CRITERIA PER FBC1603.1.4. | | | | 2ND & 3RD REVIEWS: | | | | THE SECOND PORTION OF THE COMMENT WAS ADDRESSED WITH | | THE ENGINEERING FROM PAUL KING, PE. | | | | THE FIRST PORTION OF THE COMMENT HAS NOT BEEN | | ADDRESSED. THE ENGINEERING PROVIDED CALCULATIONS FOR | | THE ATTACHMENT OF THE GENERATOR TO THE SLAB, BUT THE | | COMMENT IS THAT THE ENCLOSURE IS TO MEET WIND DESIGN | | CRITERIA AND THE GENERATOR DOCUMENTATION DOES NOT SHOW | | COMPLIANCE WITH THAT REQUIREMENT. | | | | PLEASE SHOW HOW THE GENERATOR ENCLOSURE IS DESIGNED TO | | RESIST WIND LOADS. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2009-12-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-12-16 |
Time |
11:15 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-12-16 |
Time |
10:03 |
Sent To |
|
|
Notes |
2009-12-16 11:18:25 | ****CORRECTIONS**** | | ****WILL PASS WITH PROVISO UPON REQUEST*** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | FROM PREVIOUS LIST: | | | | 1. THE GENERATOR INFORMATION STATES THAT THE ENCLOSURE | | MEETS WIND LOAD ANALYSIS FOR ASCE7-88, WIND VELOCITY | | 150. ASCE7-88 USED FASTEST MILE, WHICH CONVERTED TO 3 | | SECOND GUST WOULD BE 130MPH. THE CITY OF WEST PALM | | BEACH LIES ENTIRELY WITHIN THE 140MPH ZONE. ALSO, IT | | APPEARS THAT THIS IS LOCATED IN EXPOSURE C (LARGE BODY | | OF WATER TO THE EAST, SEE DEFINITION OF EXPOSURE C | | REVISED IN FBC2007 AND ASCE7-05). | | | | INSTALLATION IS TO RESIST WIND LOADS (SLIDING, | | OVERTURNING) FBC1609. PROVIDE INSTALLATION | | SPECIFICATION TO COMPLY WITH FBC1609, AND DECLARE WIND | | DESIGN CRITERIA PER FBC1603.1.4. | | | | 2ND REVIEW: | | | | THE SECOND PORTION OF THE COMMENT WAS ADDRESSED WITH | | THE ENGINEERING FROM PAUL KING, PE. | | | | THE FIRST PORTION OF THE COMMENT HAS NOT BEEN | | ADDRESSED. THE ENGINEERING PROVIDED CALCULATIONS FOR | | THE ATTACHMENT OF THE GENERATOR TO THE SLAB, BUT THE | | COMMENT IS THAT THE ENCLOSURE IS TO MEET WIND DESIGN | | CRITERIA AND THE GENERATOR DOCUMENTATION DOES NOT SHOW | | COMPLIANCE WITH THAT REQUIREMENT. | | | | UPON REQUEST, THIS REVIEW CAN BE PASSED WITH PROVISO, | | REVISION REQUIRED, AT CONTRACTOR'S RISK, SHOW | | COMPLIANCE WITH 140MPH EXPOSURE C FOR GENERATOR | | ENCLOSURE. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2009-09-23 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-09-23 |
Time |
14:32 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-09-23 |
Time |
14:32 |
Sent To |
|
|
Notes |
2009-09-23 14:55:04 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. THE GENERATOR INFORMATION STATES THAT THE ENCLOSURE | | MEETS WIND LOAD ANALYSIS FOR ASCE7-88, WIND VELOCITY | | 150. ASCE7-88 USED FASTEST MILE, WHICH CONVERTED TO 3 | | SECOND GUST WOULD BE 130MPH. THE CITY OF WEST PALM | | BEACH LIES ENTIRELY WITHIN THE 140MPH ZONE. ALSO, IT | | APPEARS THAT THIS IS LOCATED IN EXPOSURE C (LARGE BODY | | OF WATER TO THE EAST, SEE DEFINITION OF EXPOSURE C | | REVISED IN FBC2007 AND ASCE7-05). | | | | INSTALLATION IS TO RESIST WIND LOADS (SLIDING, | | OVERTURNING) FBC1609. PROVIDE INSTALLATION | | SPECIFICATION TO COMPLY WITH FBC1609, AND DECLARE WIND | | DESIGN CRITERIA PER FBC1603.1.4. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2010-04-15 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2010-04-15 |
Time |
11:14 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2010-04-15 |
Time |
11:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2010-02-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2010-02-01 |
Time |
14:20 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2010-01-28 |
Time |
15:41 |
Sent To |
|
|
Notes |
2010-01-28 15:42:36 | ON HOLD WAITING FOR CONTRACTOR TO MAKE SETS. ONE SET | | HAS NEW SHEETS NOT IN OLD SET. OLD SET HAS SHEETS NOT | | IN NEW SETS. | | SPOKE TO CONT REP TWICE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2009-12-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-12-09 |
Time |
08:57 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-12-09 |
Time |
08:57 |
Sent To |
|
|
Notes |
2009-12-09 08:57:24 | ** DENIED ** | | | | ** SETS OF PLANS SUBMITTED ARE NOT THE SAME. | | ONE SET HAD ALL COMPLETE ELECTRICAL PAGES WHICH WERE | | NOT REQUESTED ON PREVIOUS REVIEW. | | ONE SET HAS PLUMBING SHEETS WHICH ARE NOT IN THE SECOND | | SET?? | | | | | | 2ND REQUEST | | 1) NOTE: PLEASE PROVIDE INFORMATION ON THE TYPE OF BACK | | UP SYSTEM OF THIS GENERATOR. PLEASE SEE DEFINITIONS IN | | NEC/ NFPA-70 2008, 700,701, AND 702. | | PLEASE ALSO SEE 2005 NFPA-110. | | THE BASE BUILDING PLANS WERE ALSO SUBMITTED HOWEVER NOT | | ALL EMERGENCY LIGHTS ON THE FIXTURE LEGEND INDICATE | | BATTERY BACK UP. ALL REQUIRED EMERGENCY BACK UP POWER | | MUST BE FED FROM 700 OR 701 SYSTEMS. IF BATTERY BACK UP | | POWER IS PROVIDED FOR ALL LIFE SAFETY AND LEGALLY | | REQUIRED THEN THIS SYSTEM WOULD BE OPTION STAND-BY. | | IF THIS IS A 700 OR 701 SYSTEM IT MAY NOT RELY ON | | NATURAL GAS AS THE PRIMARY SOURCE FOR THE PRIME MOVER. | | 700.12B3, 701.11B3. | | PLEASE REDESIGN SYSTEM IF INDEED FALLING UNDER NFPA-70, | | 700,701 OR NFPA-110 | | | | ** THERE WAS NO RESPONSE FROM THE DESIGNER OF RECORD TO | | PREVIOUS ELECTRICAL REVIEW COMMENTS. A CALL WAS PLACED | | TO THE ARCHITECT OF RECORD AS THE PHONE NUMBER LISTED | | ON TITLE BLOCK IS NO LONGER IN USE. NEW NUMBER FOR | | ENGINEER WAS OBTAINED FROM ARCHITECT AND LEFT MESSAGE | | ON 12/8 FOR A RETURN CALL. | | | | PLANS WILL REMAIN IN FAILED STATUS UNTIL INFORMATION IS | | PROVIDED OR PLANS ARE REVISED. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2009-10-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-10-13 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-10-13 |
Time |
11:16 |
Sent To |
B |
|
Notes |
2009-10-13 11:16:57 | ** DENIED ** | | | | ** ORIGINAL REVIEW WAS DONE ON 9/24 HOWEVER DID NOT GET | | INTO THE SYSTEM. NOTES ADDED 10/13 | | | | | | 1) NOTE: PLANS SUBMITTED ARE IN FACT PHOTO-COPIES OF | | SIGNED, DATED AND SEALED ENGINEERED PLANS. MUST CONTAIN | | ORIGINAL SIGNATURE, DATE AND SEAL PER FLORIDA | | ADMINISTRATIVE CODE 61G15-23.002, FS 471.025 | | | | 2) NOTE: RISER INDICATES AN INTERLOCK ENCLOSURE OF SOME | | TYPE. PLEASE PROVIDE EQUIPMENT SPECS MEETING MINIMUM | | LISTING PER UL 1081. IT ALSO INDICATES A NOTE #2, FOR | | WHAT STATES TO BE AS A NEW AUTOMATIC TRANSFER SWITCH. | | PLEASE REVISE RISER IF THIS IS INDEED GOING TO BE | | CHANGED OUT. | | | | 3) NOTE: NO PANEL SCHEDULE FOR PANEL *E* COULD BE | | LOCATED. PLEASE SUBMIT SO THAT LOADS CAN BE VERIFIED. | | IT IS NOT POSSIBLE TO REVIEW FOR MINIMUM SIZING PER | | 702.5, 220 OF THE NEC AT THIS TIME. | | | | 4) NOTE: PLEASE PROVIDE INFORMATION THAT THIS SYSTEM IS | | AN OPTIONAL STAND-BY SYSTEM AND IT DOES NOT SERVE ANY | | LEGALLY REQUIRED 701, OR EMERGENCY 700 SYSTEMS. | | ** BASE BUILD OUT PLANS WERE NOT UNDER THE REVIEW OF | | THIS REVIEWER AND LOADS ARE NOT KNOWN AT THIS TIME. | | | | 5) NOTE: PLEASE SEE 702.11. IN ORDER TO MEET EXCEPTIONS | | IN 225.31-225.39 THE DISCONNECTING MEANS AT GENERATOR | | MUST BE READILY ACCESSIBLE. PLANS APPEAR TO SHOW IT | | MEETING OTHER EXCEPTION WHICH IS IT MUST BE *WITHIN | | SITE*. SEE NEC 100. | | | | 6) NOTE: PLEASE LABEL MAINS PER 230.2 E | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2010-02-09 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2010-02-09 |
Time |
13:45 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2010-02-09 |
Time |
13:26 |
Sent To |
|
|
Notes |
2010-02-09 13:39:08 | *****APPROVED***** | | | | | | PLAN SHEET LS-1 STAMPED, INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2009-12-28 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-12-28 |
Time |
12:40 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-12-28 |
Time |
12:21 |
Sent To |
|
|
Notes |
2009-12-28 12:39:53 | *****FIRE-STAMP NEEDED***** | | | | | | THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN PLAN | | SHEETS HAVE BEEN PACKAGED TOGETHER AS ORDERLY SETS. | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2009-10-01 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2009-10-01 |
Time |
08:40 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2009-10-01 |
Time |
08:05 |
Sent To |
|
|
Notes |
2009-10-01 08:40:17 | 2007 PALM BEACH LAKES BOULEVARD | | | | 1. PLEASE INDICATE WHAT SYSTEMS OR DEVICES THE | | GENERATOR WILL SUPPLY POWER TO. | | | | 2. PLANS DO NOT INDICATE ANY DOORS OR WINDOW OPENINGS | | LOCATED NEAR THE GENERATOR. PLEASE INDICATE THAT NO | | WINDOW OR DOOR OPENINGS EXIST WITHIN 10 FEET VERTICALLY | | OR HORIZONTALLY OF THE GENERATOR. | | | | 3. THE SURVEY APPEARS TO HAVE BEEN PREPARED IN 2007 AND | | IS OVER TWO YEARS OLD. | | | | 4. NO DIMENSIONS PROVIDED WHERE THE GENERATOR IS | | PLANNED TO BE INSTALLED AND THE BUILDING. PLEASE | | PROVIDE DIMENSIONS. | | | | 5. ALL DRAWINGS IN THE SUBMITTAL PACKAGE ARE COPIES TO | | INCLUDE SIGNATURES. | | | | 6. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE | | NATIONAL ELECTRICAL CODE. PLEASE DOCUMENT THIS ON THE | | DRAWINGS. | | | | DENIED. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | WEST PALM BEACH FIRE RESCUE | | BUREAU OF FIRE PREVENTION | | 500 NORTH DIXIE HIGHWAY | | WEST PALM BEACH, FLORIDA 33401 | | (561) 804-4709 PHONE | | (561) 804-4774 FAX |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2009-09-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-09-14 |
Time |
14:27 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-09-14 |
Time |
14:27 |
Sent To |
|
|
Notes |
2009-09-14 14:28:11 | NO GAS PLANS SUBMITTED. -- SEPARATE GAS PLANS/PERMIT | | REQUIRED. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2010-04-15 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2010-04-15 |
Time |
11:21 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2010-01-19 |
Time |
10:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2009-11-18 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2009-11-18 |
Time |
17:06 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2009-11-18 |
Time |
17:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2009-10-13 |
Time |
|
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2009-09-08 |
Time |
10:53 |
Sent To |
|
|
Notes |
2009-09-08 10:57:44 | GENERATOR: 30 KW TO- C 24 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2009-09-21 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2009-09-21 |
Time |
13:39 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2009-09-21 |
Time |
13:37 |
Sent To |
|
|
Notes |
2009-09-21 13:39:24 | APPEARS TO BE LP GENERATOR. SEE GAS PLAN REVIEW | | COMMENTS. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2009-12-07 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2009-12-07 |
Time |
17:20 |
Rev Time |
0.20 |
Received By |
eschneid |
Date |
2009-12-07 |
Time |
17:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2009-09-17 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2009-09-17 |
Time |
18:19 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2009-09-17 |
Time |
18:19 |
Sent To |
|
|
Notes |
2009-09-17 18:22:42 | FAILED | | | | 1) THE PROPOSED GENERATOR LOCATION CONFLICTS WITH | | PARKING AND LANDSCAPE THAT THE PROPERTY OWNER IS | | PLANNING TO INSTALL AS SHOWN ON SITE AND LANDSCAPE | | PLANS THAT WILL BE SUBMITTED SHORTLY FOR PERMITS. | | | | 2) GENERATORS ARE REQUIRED TO BE SCREENED WITH A | | FENCE/WALL AND LANDSCAPE. PERMITS AND PLANS ARE | | REQUIRED FOR THE SCREENING PRIOR TO THE ISSUANCE OF A | | GENERATOR PERMIT. | | | | 3) PLEASE PROVIDE DETAILS AS TO THE LOCATION OF THE | | ATS. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|