Plan Review Details - Permit 09090068
Plan Review Stops For Permit 09090068
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-11-10 Cont ID  
Sent By jgomez Date 2009-11-10 Time 16:26 Rev Time 0.00
Received By jgomez Date 2009-11-10 Time 14:44 Sent To PC
Notes
2009-11-10 16:27:10BUILDING REVIEW APPROVED WITH PROVISO:
  
 1-PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ALL INSWING AND OUTSWING DOORS AS SHOWN ON PLANS.
 ENGINEERING SUBMITTED IS NOT A PRODUCT APPROVAL.
 B) WATER PROOF MEMBRANE OVER FOR SECOND FLOOR PORCH
 THAT IS DESIGNED TO RECEIVE THE PROPOSED FINISH FLOOR.
 C) ARCHITECT OF RECORD TO REVIEW AND APPROVE ALL
 PRODUCT APPROVALS IN WRITING PRIOR TO SUBMITTAL. SEC.
 106.3.3 CITY AMENDMENTS TO FBC.
  
 2- REVISE DESIGN PRESSURES FOR DOOR/WINDOWS SHOWN ON
 SHEET A-2. SEE DESIGN LOADS ON SHEET S-2 AND REVISE AS
 REQUIRED.
  
 3- REVISE FLOOR LOADS SHOWN ON SHEET S-1. SEE TABLE
 R301.5 OF 2007 FL. RESIDENTIAL CODE AND REVISE AS
 REQUIRED.
  
 4- SPECIFY FINISH FLOOR AT BALCONY (COORDINATE WITH
 ITEM #1B) ABOVE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-09-23 Cont ID  
Sent By jgomez Date 2009-09-22 Time 17:03 Rev Time 0.00
Received By jgomez Date 2009-09-22 Time 17:03 Sent To  
Notes
2009-09-22 17:04:40:
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2009-11-10 Cont ID  
Sent By dpalmer Date 2009-11-10 Time 14:19 Rev Time 0.00
Received By dpalmer Date 2009-11-10 Time 14:19 Sent To  
Notes
2009-11-10 14:20:08ALL ELECTRICAL REVIEWS AND PERMITS WERE REVIEWED AND
 ISSUED BY BILL TROBAUGH UNDER SEPARATE PERMITS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-09-17 Cont ID  
Sent By dpalmer Date 2009-09-17 Time 09:52 Rev Time 0.00
Received By dpalmer Date 2009-09-17 Time 09:52 Sent To  
Notes
2009-09-17 09:52:36 
 ** DENIED PLANS **
  
  
 1) NOTE: PLEASE SEE FBC R313.1. PLEASE SHOW A LAYOUT
 ALL EXISTING OR NEW SMOKE ALARMS MEETING CURRENT
 NFPA-72 11.8.3, 11.5.1. MUST BE HARDWIRED WITH BATTERY
 BACK UP. MUST BE INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 AND AT LEAST ONE ON FIRST FLOOR LEADING TO FLOOR ABOVE.
 PLEASE ALSO SEE FS 553.885 AS A CARBON MONOXIDE
 DETECTOR IS REQUIRED FOR HOME WITH THE NEW GAS
 APPLIANCES.
  
 2) NOTE: PLANS DO NOT INDICATE ANY CIRCUITS FOR NEW AND
 EXISTING REQUIRED DEDICATED CIRCUITS IN KITCHEN
 REMODEL.
 PLEASE SUBMIT A PANEL SCHEDULE SHOWING THE MINIMUM
 CIRCUITS PER 210.52B1, 210.11C1, 220.52
 PLEASE BE SURE TO INCLUDE MINIMUM CONDUCTORS AND OVER
 CURRENT PROTECTION.
 PLEASE SEE 240.4,310.16 AND 408.4 FOR CONDUCTORS,
 SIZING OF BREAKERS AND PANEL SCHEDULE.
  
 3) NOTE: PLANS STATE COMPLIANCE WITH NEC. HOWEVER THE
 EDITION OF THE PERMITTED SCOPE OF WORK IS UNDER THE
 2005 NEC. ( NFPA-70)
  
  
  
  
 ** AS STATED ABOVE. PLEASE CALL TO GO OVER ANY
 COMMENTS.
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2009-09-02 Cont ID  
Sent By swurafti Date 2009-09-02 Time 16:17 Rev Time 0.00
Received By swurafti Date 2009-09-02 Time 16:17 Sent To  
Notes
2009-09-02 16:17:41HISTORIC APPROVED BY JPAPA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-11-03 Cont ID  
Sent By btrobaug Date 2009-11-03 Time 10:43 Rev Time 0.00
Received By btrobaug Date 2009-11-03 Time 10:43 Sent To  
Notes
2009-11-03 10:44:05R 1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-09-23 Cont ID  
Sent By jgomez Date 2009-09-23 Time 09:51 Rev Time 0.00
Received By jgomez Date 2009-09-03 Time 15:01 Sent To  
Notes
2009-09-03 15:15:57SENT TO R-8.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-09-22 Cont ID  
Sent By jgomez Date 2009-09-22 Time 16:58 Rev Time 0.00
Received By jgomez Date 2009-09-22 Time 16:58 Sent To  
Notes
2009-09-22 16:59:16NO A/C WORK.

Review Stop Z ZONING
Rev No 2 Status P Date 2009-11-06 Cont ID  
Sent By eschneid Date 2009-11-06 Time 15:21 Rev Time 0.00
Received By eschneid Date 2009-11-06 Time 15:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-09-18 Cont ID  
Sent By eschneid Date 2009-09-18 Time 16:33 Rev Time 0.50
Received By eschneid Date 2009-09-18 Time 16:33 Sent To  
Notes
2009-09-18 17:02:05FAILED
  
 1) THE NEW EXTENDED SLAB AND STEPS ARE NOT SHOWN ON THE
 PROPOSED SITE PLAN. PLEASE INCLUDE THE DIMENSIONS OF
 THE SLAB AND STEPS AND THE SETBACK TO THE SOUTH AND
 EAST PROPERTY LINES.
  
 2) THE NEW ROOF IS NOT ACCURATELY SHOWN ON THE PROPOSED
 SITE PLAN.
  
 3) THE EXISTING COVERED ENTRY IS NOT SHOWN ON THE
 PROPOSED SITE PLAN. THE PROPOSED ELEVATIONS SHOW THAT
 IT IS TO REMAIN.
  
 4) THE PROPOSED SITE PLAN SHOWS THE DRIVEWAY BEING
 EXTENDED. THIS IS NOT INDICATED ON THE SCOPE OF WORK ON
 THE PERMIT.
  
 5) THE NEW COLUMNS AND THE RAILING ARE BEING SHOWN
 WITHIN THE REQUIRED 15 FOOT EAST SETBACK. THE PLANS
 SHALL BE REVISED TO MOVE THE COLUMNS AND THE RAILING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.