Plan Review Details - Permit 09090049
Plan Review Stops For Permit 09090049
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2009-10-26 Cont ID  
Sent By dlauderm Date 2009-10-26 Time 10:38 Rev Time 2.00
Received By dlauderm Date 2009-10-26 Time 10:35 Sent To  
Notes
2009-10-26 10:38:03DEAN LAUDERMILK, PROJECT COORDINATOR
 W-561-494-1083
 F-561-494-1116
 [email protected]
 PASSED WITH PROVISO:
 PLANS NEED TO BE SUBMITTED TO ENGINEERING SERVICES
 DEPT. FOR A SEPARATE REVIEW FOR OFF-SITE SERVICE
 CONNECTION.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2009-09-08 Cont ID  
Sent By mawillia Date 2009-09-08 Time 14:39 Rev Time 0.00
Received By mawillia Date 2009-09-08 Time 14:39 Sent To  
Notes
2009-09-08 14:42:30*****DENIED*****
  
 BASED ON MEETING CONDUCTED WITH JEFF RENAULT OF
 ENGINEERING, THE NEW POINT OF SERVICE FOR THE PROPOSED
 SPRINKLER SYSTEM SHALL BE SHOWN.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-10-27 Cont ID  
Sent By mawillia Date 2009-10-27 Time 11:24 Rev Time 0.00
Received By mawillia Date 2009-10-27 Time 10:20 Sent To  
Notes
2009-10-27 11:04:50*****APPROVED*****
  
  
 THE FIRE ALARM PLAN (FP-1 - FP-3) FIRE-STAMPED,
 ACCORDINGLY; READY FOR PERMIT ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-09-08 Cont ID  
Sent By mawillia Date 2009-09-08 Time 15:05 Rev Time 0.00
Received By mawillia Date 2009-09-08 Time 14:19 Sent To  
Notes
2009-09-08 15:03:14*****DENIED*****
  
  
 1. THE ACTUAL SITE ADDRESS SHALL BE LISTED IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET, HYDRAULIC
 CALCULATIONS, AND/OR ANY OTHER INFORMATION PERTINENT TO
 THIS PROJECT. IF NEW RESULTS ARE REQUIRED, CONTACT THE
 BUREAU OF FIRE PREVENTION AT 561-804-4724.
  
 2. THE FLOW TEST RESULTS AND HYDRAULIC CALCULATIONS
 SHALL BE BASED ON INFORMATION TAKEN NOT GREATER THAN
 ONE YEAR FROM THE DATED OF PERMIT APPLICATION.
  
 3. THE DOUBLE CHECK DETECTOR ASSEMBLY IS TO BE SECURED
 WITH A CHAIN AND LOCK IN ADDITION TO ELECTRONIC
 SUPERVISION.
  
 4. THE FIRE DEPARTMENT CONNECTION (FDC) SHALL BE
 PROVIDED WITH KNOX LOCKING DEVICES. FOR AN APPLICATION,
 CONTACT THE BUREAU OF FIRE PREVENTION AT 561-804-4724.
  
 5. PROVIDE NOTICE OF COMMENCEMENT OF WHICH THIS SCOPE
 OF WORK IS BEING CONDUCTED. IF THIS SCOPE OF WORK IS
 TIED TO THE MASTER PERMIT, INCLUDE THE MASTER PERMIT
 NUMBER.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-10-08 Cont ID  
Sent By kstevens Date 2009-10-08 Time 08:28 Rev Time 0.00
Received By kstevens Date 2009-10-08 Time 08:28 Sent To  
Notes
2009-10-08 08:29:07SENT TO FIRE.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-10-26 Cont ID  
Sent By mawillia Date 2009-09-08 Time 14:42 Rev Time 0.00
Received By mawillia Date 2009-09-03 Time 11:00 Sent To  
Notes
2009-09-03 11:00:45SENT TO FIRE.