Plan Review Details - Permit 09080776
Plan Review Stops For Permit 09080776
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-10-28 Cont ID  
Sent By shill Date 2009-10-28 Time 09:57 Rev Time 0.00
Received By shill Date 2009-10-28 Time 09:57 Sent To  
Notes
2009-10-28 14:27:01****PASSED W/REDLINE****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. FROM PREVIOUS TWO COMMENT LISTS, SHEATHING NAILING
 DOES NOT COMPLY WITH FBC R803.2.3.1, SHEET 2, VARIOUS
 DETAILS. ZONE 3 REQUIRES 4" AT EDGES, PLAN SPECIFIES
 6". THIS IS PRESCRIPTIVE IN THE CODE AND CANNOT BE
 REDUCED.
  
 THE DETAILS ON SHEET 2 SPECIFY 30# FELT; THE PRODUCT
 APPROVAL SUBMITTED DOES NOT ALLOW 30#. PLEASE EITHER
 REMOVE FROM THE DETAIL OR REVISE SO THAT IT IS
 CONSISTENT WITH OTHER DETAILS.
  
 PLANS HAVE BEEN REDLINED; THE NON CODE COMPLIANT DETAIL
 HAS BEEN REMOVED. 4"/6" ROOF SHEATHING REQUIRED
  
 2. ROOF PERMIT REQUIRED. FOR A ROOF PERMIT, ENHANCED
 FASTENING CALCULATIONS REQUIRED PER NOA 08-0221.11, SEE
 GENERAL LIMITATION #7. THIS MAY BE SUBMITTED SEPARATELY
 WITH THE ROOF PERMIT APPLICATION. APPROVED ASSEMBLY
 MUST BE SELECTED AND ENHANCED FASTENING PATTERN
 SUBMITTED PRIOR TO ROOF PERMIT ISSUANCE.
  
 REGARDING THE ROOF DOCUMENTS SUBMITTED:
  
 A. ENGINEERING SPECIFIES EXPOSURE B.
 B. THE NOA SUBMITTED IS FOR "RECOVER DECKS." THIS IS
 FOR RECOVER APPLICATION, NOT NEW CONSTRUCTION. SUBMIT
 THE APPROPRIATE NOA.
 C. AN APPROVED ASSEMBLY MUST BE SELECTED. IT IS NOT
 CLEAR HOW THE ENGINEER HAS DETERMINED ROOF FASTENER
 SPACING, MUST DO CALCULATIONS IN ACCORDANCE WITH
 RAS117. IT APPEARS THAT HE HAS ROUNDED UP, FROM 5.9" TO
 6", BUT SEE RAS117 WHICH SPECIFICALLY STATES THAT
 FASTENING MUST BE ROUNDED DOWN TO THE NEAREST INCH.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-09-14 Cont ID  
Sent By shill Date 2009-10-22 Time 09:22 Rev Time 0.00
Received By shill Date 2009-09-14 Time 16:07 Sent To Z
Notes
2009-09-14 16:26:46****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THIS PROPERTY IS LOCATED IN EXPOSURE C, SEE
 ASCE7-05. EITHER REVISE EXPOSURE AND DESIGN OR PROVIDE
 RATIONALE FOR EXPOSURE B. FBC R301
  
 2. PLEASE EXPLAIN DESIGN PRESSURES; FOR INSTANCE, ROOF
 ZONE 3, 10SF, -68.1 PSF. FBC R301
  
 3. WIND DESIGN INFORMATION, REFERENCE TO 3 SECOND
 "BURST," PLEASE CLARIFY, DO YOU MEAN "GUST?" SEE
 FBC1609, FBC R301, ASCE7-05.
  
 4. SHEATHING NAILING DOES NOT COMPLY WITH FBC
 R803.2.3.1, SHEET 2, VARIOUS DETAILS.
  
 5. FLORIDA STATE OR LOCAL PRODUCT APPROVAL OR NOA
 REQUIRED FOR HARDIBOARD SIDING.
  
 6. ROOF PERMIT REQUIRED. FOR A ROOF PERMIT, ENHANCED
 FASTENING CALCULATIONS REQUIRED PER NOA 08-0221.11, SEE
 GENERAL LIMITATION #7. THIS MAY BE SUBMITTED SEPARATELY
 WITH THE ROOF PERMIT APPLICATION. APPROVED ASSEMBLY
 MUST BE SELECTED AND ENHANCED FASTENING PATTERN
 SUBMITTED PRIOR TO ROOF PERMIT ISSUANCE.
  
 7. ADDITIONAL FEES DUE (VALUATION ADJUSTMENT, ICC
 TABLE, TYPE V, UTILITY, $37.87/SF). PLEASE PAY PRIOR TO
 RESUBMITTAL (CAN BE PAID ONLINE).
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-10-19 Cont ID  
Sent By dpalmer Date 2009-10-19 Time 14:15 Rev Time 0.00
Received By shill Date 2009-10-19 Time 14:15 Sent To Z
Notes
2009-10-22 09:22:1410/22, ROUTED PLANS FROM B2 TO SMH DESK
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-09-21 Cont ID  
Sent By lmartine Date 2009-09-21 Time 15:19 Rev Time 0.00
Received By lmartine Date 2009-08-31 Time 15:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2009-10-21 Cont ID  
Sent By jroach Date 2009-10-21 Time 15:15 Rev Time 0.00
Received By jroach Date 2009-10-21 Time 15:15 Sent To B
Notes
2009-10-21 15:16:52ZONING PLAN REVIEW
  
 PERMIT NO.: 09080776
 ADDRESS: 430 LYTLE STREET
 CONTRACTOR/CONTACT: PETER SEIDLE
 TELEPHONE NO.: 561.596.2766
 SCOPE OF REVIEW: INSTALLATION OF ACCESSORY SHED.
  
 REVIEW STATUS: PASSED WITH PROVISOS
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1) PRIOR TO CERTIFICATE OF OCCUPANCY, THE EXISTING
 ABOVE-GROUND POOL SHALL BE REMOVED IN ITS ENTIRETY.
  
 2) PRIOR TO CERTIFICATE OF OCCUPANCY, THE EXISTING SHED
 SHALL BE REMOVED IN ITS ENTIRETY.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-09-21 Cont ID  
Sent By jroach Date 2009-09-21 Time 08:38 Rev Time 0.00
Received By jroach Date 2009-09-21 Time 08:38 Sent To  
Notes
2009-09-21 08:48:35ZONING PLAN REVIEW
  
 PERMIT NO.: 09080776
 ADDRESS: 430 LYTLE STREET
 CONTRACTOR/CONTACT: PETER SEIDLE
 TELEPHONE NO.: 561-533-7139
 SCOPE OF REVIEW: WOOD FRAME SHED.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) PLEASE PROVIDE THE SEPARATION DIMENSION BETWEEN THE
 PRIMARY RESIDENCE AND THE PROPOSED SHED. PURSUANT TO
 SECTION 94-304(B)(3) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS), ACCESSORY STRUCTURES
 SHALL BE LOCATED NO CLOSER THAN SIX (6) FEET TO THE
 PRIMARY STRUCTURE.
  
 2) ACCORDING TO THE SURVEY SUBMITTED, ANOTHER ACCESSORY
 STRUCTURE IS ALREADY LOCATED ON THE PROPERTY; THIS
 STRUCTURE IS NOT LOCATED ON THE SITE PLAN. PLEASE
 CLARIFY. IF THE STRUCTURE CURRENTLY EXISTS, PLEASE
 INDICATE IT ON THE SITE PLAN AND LABEL AS "EXISTING".
  
 3) IF THE STRUCTURE ON THE SURVEY DOES EXIST, PLEASE
 PROVIDE THE TOTAL SQUARE FOOTAGE OF ALL EXISTING
 ACCESSORY STRUCTURES. PURUSANT TO SECTION 94-304(B)(1)
 OF THE CITY'S ZLDRS, THE TOAL AREA OF ALL ROOFED
 ACCESSORY STRUCTURES SHALL NOT EXCEED 75 PERCENT OF THE
 GROSS FLOOR AREA OF THE PRIMARY STRUCTURE, WITH A
 MAXIMUM OF 1,000 SQUARE FEET.
  
 4) ACCORDING TO THE SURVEY SUBMITTED, THERE IS AN
 EXISTING ABOVE-GROUND POOL. PLEASE CLARIFY AS TO
 WHETHER OR NOT THIS CURRENTLY EXISTS. PURSUANT TO
 SECTION 94-304(D)(1)(B) OF THE CITY'S ZLDRS,
 ABOVE-GROUND POOLS ARE PROHIBITED. IF THE POOL
 CURRENTLY EXISTS, IT SHALL BE REMOVED PRIOR TO THE
 ISSUANCE OF THIS BUILDING PERMIT.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  