Plan Review Details - Permit 09080604
Plan Review Stops For Permit 09080604
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-06-15 Cont ID  
Sent By jwitmer Date 2010-06-15 Time 10:59 Rev Time 1.55
Received By jwitmer Date 2010-06-15 Time 10:59 Sent To  
Notes
2010-06-15 11:08:40BUILDING PLAN REVIEW
 PERMIT: 09080604
 ADD: 519 CLEMATIS ST.
 CONT: SEC CONSTRUCTION
 TEL: (561)797-6007
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE A
 SEPERATE REVIEW WITH ASSOCIATED FEES.
  
 1) MC LAREN ENGINEERING FOR KNOCK-DOWN ROOF CURBS WILL
 NEED TO BE UPDATED TO THE CURRENT ASCE 7-05 STANDARDS.
  
 2) THE SECOND ISSUE WITH ENGINEERING CALCULATIONS ARE
 REQUIRED TO BE SIGNED AND SEALED. FLORIDA STATUTE 471
 AND FLORIDA ADMINISTRATIVE CODE 61G-15.23.002.
  
 NOTE: DOOR PRODUCT APPROVALS FOR THTE EXTERIOR DOORS
 ARE PART OF THE SHELL PERMIT AND NEED TO BE SUBMITTED
 UNDER PERMIT # 09090658.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-01-11 Cont ID  
Sent By jwitmer Date 2010-01-11 Time 14:46 Rev Time 3.00
Received By jwitmer Date 2010-01-11 Time 11:02 Sent To  
Notes
2010-01-11 14:50:07 
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 1) PROVIDE FIRE EXTINGUISHER PLACEMENT PER SECTION
 906.1.
  
 2) PROVIDE PLACEMENT OF ACCESSIBLE TABLES PER SECTION
 11-5.1.
  
 3) PROVIDE PRODUCT APPROVAL FOR EXTERIOR FREEZER PER
 RULE 9B-72(31)(G).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-09-09 Cont ID  
Sent By jwitmer Date 2009-09-09 Time 11:57 Rev Time 4.00
Received By jwitmer Date 2009-09-09 Time 08:05 Sent To  
Notes
2009-09-09 11:45:55BUILDING PLAN REVIEW
 PERMIT: 09080604
 ADD: 519 CLEMATIS ST.
 CONT: SEC
 TEL: (561)797-6007
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 09-09-09
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) PLANS ARE DEFICIENT IN THE FOLLOWING ITEMS, 106.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS:
 106.3.5(2) OCCUPANCY GROUP AND SPECIAL OCCUPANCY
 REQUIREMENTS SHALL BE DETERMINED.
  
 (3) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
  
 (4) FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS TABLE 601
  
 (5) FIRE SUPPRESSION SYSTEMS, ARE THER FIRE SPRINKLERS?
 903
 PLANS DO NOT PROVIDE FIRE EXTINGUISHER LOCATIONS 906.1
  
 (6) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
  
 (7) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD TABLE 1004.1.1
 MEANS OF EGRESS / EXIT ACCESS 1015/ AISLE ACCESSWAYS
 1014.4.3.3
  
 (8) INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 803.1/ TABLE 803.5
 SANITATION 1210.2
  
 (9) ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 ACCESSIBLE ROUTE BOTH FOR THE INTERIOR AND PATIO DECK
 RESTROOMS
  
 3) SHEET A.02 INDICATESA STALL WITHIN THE MENS
 RESTROOM, THE NEW WORK SHEET A.03 INDICATES THE STALL
 NOW DOES NOT HAVE A TURNING RADIUS WITHIN THE STALL,
 PLEASE REVIEW 11-4.1.6 ACCESSIBLE BUILDINGS-
 ALTERATIONS (1)
 A) NO ALTERATION SHALL BE UNDERTAKEN WHICH DECREASES OR
 HAS THE EFFECT OF DECREASING ACCESSIBILITY OR USABILITY
 OF A BUILDING OR FACILITY BELOW THE REQUIREMENTS FOR
 NEW CONSTRUCTION AT THE TIME OF ALTERATION.
  
 (B) IF EXISTING ELEMENTS, SPACES, OR COMMON AREAS ARE
 ALTERED, THEN EACH SUCH ALTERED ELEMENT, SPACE,
 FEATURE, OR AREA SHALL COMPLY WITH THE APPLICABLE
 PROVISIONS OF SECTION 11-4.1.1 TO SECTION 11-4.1.3,
 MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION. IF THE
 APPLICABLE PROVISION FOR NEW CONSTRUCTION REQUIRES THAT
 AN ELEMENT, SPACE, OR COMMON AREA BE ON AN ACCESSIBLE
 ROUTE, THE ALTERED ELEMENT, SPACE, OR COMMON AREA IS
 NOT REQUIRED TO BE ON AN ACCESSIBLE ROUTE EXCEPT AS
 PROVIDED IN SECTION 11-4.1.6(2), ALTERATIONS TO AN AREA
 CONTAINING A PRIMARY FUNCTION.
  
 (C) IF ALTERATIONS OF SINGLE ELEMENTS, WHEN CONSIDERED
 TOGETHER, AMOUNT TO AN ALTERATION OF A ROOM OR SPACE IN
 A BUILDING OR FACILITY, THE ENTIRE SPACE SHALL BE MADE
 ACCESSIBLE.
  
 4) PLEASE ALSO PROVIDE A FLOOR PLAN INDICATING
 COMPLIANCE WITH :
 11-5.1 GENERAL. EXCEPT AS SPECIFIED OR MODIFIED IN THIS
 SECTION, RESTAURANTS AND CAFETERIAS SHALL COMPLY WITH
 THE REQUIREMENTS OF SECTION 11-4.1 TO SECTION 11-4.35.
 WHERE FIXED TABLES (OR DINING COUNTERS WHERE FOOD IS
 CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED, AT
 LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF THE FIXED
 TABLES (OR A PORTION OF THE DINING COUNTER) SHALL BE
 ACCESSIBLE AND SHALL COMPLY WITH SECTION 11-4.32 AS
 REQUIRED IN SECTION 11-4.1.3(18). ETWEEN THE SMOKING
 AND NONSMOKING AREAS. IN NEW CONSTRUCTION, AND WHERE
 PRACTICABLE IN ALTERATIONS, ACCESSIBLE FIXED TABLES (OR
 COUNTERS) SHALL BE DISTRIBUTED THROUGHOUT THE SPACE OR
 FACILITY.
  
 11-5.2 COUNTERS AND BARS. WHERE FOOD OR DRINK IS SERVED
 AT COUNTERS EXCEEDING 34 INCHES (865 MM) IN HEIGHT FOR
 CONSUMPTION BY CUSTOMERS SEATED ON STOOLS OR STANDING
 AT THE COUNTER, A PORTION OF THE MAIN COUNTER WHICH IS
 60 INCHES (1525 MM) IN LENGTH MINIMUM SHALL BE PROVIDED
 IN COMPLIANCE WITH SECTION 11-4.32 OR SERVICE SHALL BE
 AVAILABLE AT ACCESSIBLE TABLES WITHIN THE SAME AREA.
  
 11-5.3 ACCESS AISLES. ALL ACCESSIBLE FIXED TABLES SHALL
 BE ACCESSIBLE BY MEANS OF AN ACCESS AISLE AT LEAST 36
 INCHES (915 MM) CLEAR BETWEEN PARALLEL EDGES OF TABLES
 OR BETWEEN A WALL AND THE TABLE EDGES.
  
 11-5.4 DINING AREAS. IN NEW CONSTRUCTION, ALL DINING
 AREAS, INCLUDING RAISED OR SUNKEN DINING AREAS,
 LOGGIAS, AND OUTDOOR SEATING AREAS, SHALL BE
 ACCESSIBLE. IN ALTERATIONS, ACCESSIBILITY TO RAISED OR
 SUNKEN DINING AREAS, OR TO ALL PARTS OF OUTDOOR SEATING
 AREAS IS NOT REQUIRED PROVIDED THAT THE SAME SERVICES
 AND DECOR ARE PROVIDED IN AN ACCESSIBLE SPACE USABLE BY
 THE GENERAL PUBLIC AND ARE NOT RESTRICTED TO USE BY
 PEOPLE WITH DISABILITIES.
  
 5) DESIGN LOADS SHEET A.04 & A.05 BOTH INDICATE A
 120MPH / 3SECOND GUST, PLEASE REVIEW FIGURE 1609 THE
 CITY OF WEST PALM BEACH IS ENTIRELY LOCATED WITHIN A
 140 MPH WIND ZONE, PLEASE UPDATE PLANS.
  
 6) DESIGN LOADS SHEET A.04 & A.05 BOTH INDICATE FLOOR
 LOADS OF 40 PSF LIVE LOADS PLEASE REVIEW TABLE 1607.1
 DINING ROOMS & RESTARAUNTS OF 100 PSF, OR ASSEMBLY WITH
 MOVABLE SEATS 100 PSF.
 PLEASE PROVIDE ADDITIONAL INFORMATION ON THE TYPE OF
 FLOOR SYSTEM, PLANS APPEAR TO INDICATE A FLOOR TRUSS
 SYTEM?
  
 7) BOTH A.05 & S1 BOTH INDICATE A NEW OPENING ON THE
 SIDE OF THE BUILDING WITH A PAIR OF GLAZED OPENINGS &
 TWO SIDELIGHTS. THE PRODUCT SUBMITTED FL 10356-R1 IS
 ONLY FOR A PAIR OF DOORS NON-IMPACT. MISSING PRODUCT
 APPROVALS ARE:
 7A) FIXED OR STOREFRONT WINDOWS/ SIDELIGHTS
 7B) VERTICAL MULLION
 7C ) STORM SHUTTTERS/ PANELS
  
 8) STORM SHUTTERS PLEASE PROIDE THE FOLLOWING: FL BLD
 CODE 2004 SECTION 106.3.3, 1609.1.4, 1714.5.1 & EXIST
 BUILD CODE 507.3. PROCEDURES: 1(B) A COMPLETE
 INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY
 HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT
 STORM BAR REINFORCING REQUIREMENTS, WALL PRESSURE
 ZONES, SLAT TYPES, ETC., SHALL BE SUBMITTED AT TIME OF
 PERMIT APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 9) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2010-06-17 Cont ID  
Sent By btrobaug Date 2010-06-17 Time 08:53 Rev Time 0.00
Received By btrobaug Date 2010-06-17 Time 07:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2010-01-15 Cont ID  
Sent By dpalmer Date 2010-01-15 Time 11:38 Rev Time 0.00
Received By dpalmer Date 2010-01-15 Time 10:10 Sent To  
Notes
2010-01-15 11:38:59 
 ** DENIED *
  
 ** SOME ITEMS FROM PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED.
 THERE ARE SEVERAL NEW COMMENTS BASED ON REVISED PLANS
 SUBMITTED. THE INFORMATION ON PREVIOUS PLANS WAS NOT
 THE SAME AS THE PLANS NOW SUBMITTED. NEW COMMENTS ARE
 BASED ON CHANGES NOW ABLE TO BE REVIEWED.
  
 1) NOTE: THIS IS NOTED FOR INFORMATION. SEE COMMENTS
 FROM OTHER TRADES. SHEET A1.01 IS NOT SIGNED, DATED OR
 SEALED IN EITHER SET SUBMITTED. THIS IS REQUIRED UNDER
 FS 481.221. THE ARCHITECT OF RECORD MAY PERSONALLY
 APPEAR TO SIGN AND SEAL PLANS. A TIME SHOULD BE SET UP
 WITH STAFF. THIS SHOULD BE NOTED BY OTHER TRADES.
  
 2 ) NOTE: COVER SHEET HAS A CONFLICT IN CODES. ONE ARE
 INDICATES A 2007 NEC AND THE OTHER 2005. THIS CAN BE
 RELINED AS THERE WAS NO 2007 CODE. ALL APPLICATIONS FOR
 PERMIT BEFORE OCTOBER 1ST, 2009 AND AFTER DECEMBER 8TH,
 2006 ARE UNDER THE 2005 NEC.
 NO NFPA-101 LISTED. THIS SHOULD BE 2006 AS NOTED ON
 PREVIOUS REVIEW.
  
 3) NOTE: THE NEWLY SUBMITTED LIGHTING PERFORMANCE
 CALCULATIONS NOW SUBMITTED FOR NEW INTERIOR AND
 EXTERIOR LIGHTING. HOWEVER PLEASE SEE PLANS AS THEY
 INDICATE THE 2004 FLORIDA BUILDING CODE WITH 2006
 SUPPLEMENTS.
 AFTER MARCH 1ST 2009, THE LIGHTING PERFORMANCE
 CALCULATIONS ARE REQUIRED TO BE DONE PER 13-415.AB.5
 FOR INTERIOR AND 13-415.AB.2.2 FOR EXTERIOR UNDER THE
 2007 FBC W/ 2009 SUPPLEMENTS. THERE WERE SUBSTANTIAL
 CHANGES MADE TO CHAPTER 13, IN FACT THE ENTIRE CHAPTER
 WAS REVISED.
 A FIXTURE SCHEDULE WAS NOT SUBMITTED THEREFORE LIGHTING
 ON PLANS AND CALCULATIONS CAN NOT BE VERIFIED. PLEASE
 SUBMIT. ( IT CAN ALWAYS BE REVISED AT A LATER DATE IF
 FIXTURES CHANGE)
 ** THE LIGHTING SHOWN ON ARCHITECTURAL PLANS FOR WALLS
 IS MORE THAN THE LIGHTING SHOWN ON THE ELECTRICAL
 PLANS. ( SCONCES AS ONE EXAMPLE)
  
 4) NOTE: THE NEWLY SUBMITTED LIGHTING PLANS DOES NOT
 INDICATE LIGHTING CONTROL DETAIL. HOW WILL OCCUPANCY
 SENSORS BE USED TO MEET FBC 13-415.AB.1.1,.1.2 AND
 .1.3. LINE VOLTAGE? LOW VOLTAGE? THE SYMBOL LEGEND ONLY
 INDICATES AN OCCUPANCY SENSOR.
 THERE IS A SWITCH AT THE REAR DOOR FOR KITCHEN LIGHTING
 AND ALSO CEILING INDICATES AN OC SENSOR HOWEVER IT IS
 UNCLEAR HOW THIS WILL BE DONE. THERE ARE SEVERAL WAYS
 OF INSTALLATION HOWEVER WITHOUT DETAILS WHICH CAN BE
 TYPICAL IT IS UNCLEAR AT THIS TIME. SEVERAL LIGHTING
 MANUFACTURE CONTAIN TYPICAL WIRING DETAILS ON THEIR
 WEBSITE WHICH CAN BE USED.
 STANDARD SINGLE POLE SWITCHES ARE NOT ACCEPTABLE AS
 THERE ARE SOME SHOWN ON PLANS. PLEASE ALSO SEE .1.3 OF
 THE4 SECTION NOTED AS SEPARATE CONTROLS REQUIRED.
 EXTERIOR LIGHTING DOES INDICATE A PC FOR PHOTO-CELL.
  
 5) NOTE: A COMPLETELY NEW SERVICE RISER WAS SUBMITTED
 AND THERE ARE COMMENTS BELOW. THERE IS ITEMS INDICATED
 ON RISER WHICH ARE NOT CLEAR.
  
 A) SERVICE SIZE SHOWN FEEDING GUTTER TO PANEL *A* AND
 *B* IS SHOWN ON PLANS AS A 200AMP METER/MAIN COMBO. HOW
 IS THIS POSSIBLE WHEN THE LOAD ON THE CALCULATIONS FAR
 EXCEED THE RATING OF THIS SERVICE EQUIPMENT?
 ALL SERVICES SERVICE CONDUCTORS ARE TO BE RATED TO THE
 SIZE OF THE SERVICE PROVIDED AND THE LOAD SERVED.
 230.70,230.70,230.90,230.76,230.79 ETC.
  
 B) THE RISER INDICATES SEVERAL DIFFERENT LABELS TO
 EXISTING CONDUCTORS ETC HOWEVER IT IS UNCLEAR WHICH
 CONDUCTORS IS FOR WHICH SERVICE, RISER, AND CONDUCTOR.
 SEE RISER, JUST ABOVE THE METER MAIN COMBO THERE IS A
 NOTE FOR EXISTING CONDUCTORS FOR 3-3/0 AND 1-#6. WHAT
 IS THIS FOR? THE SERVICE EQUIPMENT JUST TO THE LEFT
 ALREADY INDICATES CONDUCTORS.
 IF THIS IS FOR RISER TO 200AMP METER/MAIN COMBO THE
 CONDUCTORS ARE NOT SUFFICIENT FOR SERVICE SIZE.
 IF THIS IS FOR RISER TO 200AMP METER/MAIN COMBO THE
 RISER INDICATES AND * EQUIPMENT GROUNDING CONDUCTOR*
 BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT
 PERMITTED. PLEASE SEE 250.6 AND 250.24 AS THIS WOULD
 PARALLEL THE NEUTRAL CREATING OBJECTIONABLE CURRENT.
  
 C) THE RISER JUST BELOW THE SERVICE METER/MAIN COMBO
 INDICATES EXISTING #2 AND EXISTING 1/0 HOWEVER THESE
 ARE GOING TO ANYTHING. WHAT ARE THESE FOR?
  
 D) THE LOAD CALCULATIONS FOR PANEL *B* INDICATES LOAD
 AT 196.4 AMPS AND NOTES THAT A 225AMP SERVICE IS
 SUFFICIENT. THIS IS NOT POSSIBLE WHEN THE MAIN FEEDING
 THIS SAME 225AMP MLO IS SHOWN ON RISER TO BE 200AMPS.
 THE SERVICE IS 200AMPS WHICH PLACES THIS LOAD OF 196
 AMP VERY CLOSE TO THE MAXIMUM RATING OF A 200AMP
 BREAKER.
 240.4, 230.76, 230.79, 230.70, 230.71, 215.5, ETC
  
 E) THE RISER DOES ALSO LIST 350MCM FOR SOMETHING
 HOWEVER EVEN IF THESE ARE THE SIZE CONDUCTORS IN
 GUTTER, THE SERVICE IS ONLY 200AMPS. THE SERVICE WILL
 BE REQUIRED TO BE UPGRADED. THE LOADS ALONE ARE 313
 PLUS AMPS AND 350MCM IS RATED FOR 310. THE CONDUCTORS
 ARE NOT SUFFICIENT.310.16, 110.14
  
 F) THE LOADS ON THE SERVICE ARE TO BE REVISED. WHERE
 ARE THE LOADS ON PANEL *A* FOR EXTERIOR LIGHTING? ALL
 CONTINUOUS LOADS INCLUDING LOADS ON EXTERIOR LIGHTING
 IS TO BE SHOWN AT 125%.
 THE LOAD FOR LIGHTING IS SHOWN AT 2VA PER SQ FT. IT IS
 NOT PERMITTED TO USE THE 2VA PER SQ FT IF THE ACTUAL
 LIGHTING LOAD IS HIGHER. THE LIGHTING FIXTURE LEGEND
 WAS SUBMITTED SO THIS CAN NOT BE CONFIRMED WHICH LOAD
 IS GREATER.
 NO TRACK LIGHTING LOADS ARE SHOWN?
 NO SHOW WINDOW LOADS ARE SHOWN? IF THERE IS WINDOW AREA
 ABOVE DOORS RECEPTACLES WILL BE REQUIRED. THE INTENT OF
 210.62 IS THAT QUITE OFTEN SIGNS ARE HUNG IN THESE
 AREAS.
 THE LOAD SHOWN FOR RECEPTACLES IS LESS THAN WHAT IS
 ACTUALLY ON PLANS. PLEASE SEE SECTIONS GIVEN FOR THE
 180VA PER RECEPTACLE. THE CALCULATIONS INDICATE 10,
 HOWEVER THERE ARE MORE CONVENIENCE OUTLETS ON PLANS.
 PLEASE SEE 220.12, 220.14, 220.42, AND 220.43. ETC
  
 6) NOTE: PLEASE SEE 210.8B2 AS ALL 15 AND 20AMP, 120V
 RECEPTACLES IN KITCHEN AREAS SHALL BE GFI/GFI
 PROTECTED. THIS IS REQUIRED WHETHER OR THESE ARE
 FEEDING COUNTER SPACE LOCATIONS.
 THERE IS NO GFI PROTECTION ON PANEL SCHEDULES OR ON
 PLANS.
 THIS INCLUDES BAR AREA RECEPTACLES. 210.8B3
  
 7) NOTE: PLEASE SEE 408.4 REVISED UNDER THE 2005 CODE.
 IT IS NOT PERMITTED TO USE *GENERAL LIGHTING OR GENERAL
 RECCEPTACLES * TO DESCRIBE CIRCUITING. THESE ARE
 REQUIRED TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH
 THEY FEED. THIS MAY BE DONE PART OF A PROVISO TO BE
 REVISED AND SUBMITTED BEFORE FINAL. SEE CODE COMMENTARY
 IN THE HANDBOOK WHICH PROVIDES INFORMATION. RECORD
 PLANS NEED TO CONTAIN SPECIFIC INFORMATION/DETAIL.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-09-18 Cont ID  
Sent By dpalmer Date 2009-09-18 Time 20:00 Rev Time 0.00
Received By dpalmer Date 2009-09-18 Time 20:00 Sent To PC
Notes
2009-09-18 20:01:00 
 ** DENIED **
  
 ** REVIEW IS BASED ON PLANS AND SUPPORTING DOCUMENTS
 SUBMITTED.
  
 1) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE FOLLOWING
 RELEVANT CODES.
 2006 NFPA-101
 2005 NFPA-70
 2007 FBC WITH 2009 REVISIONS.
  
 ** PLEASE PROVIDE MORE INFORMATION ON ELECTRICAL PLANS.
 THE FOLLOWING IS NOTED AS THERE ARE ITEMS NOT YET
 SUBMITTED.
  
 2) NOTE: PLEASE SEE 13-415.AB.1.4 FOR EXTERIOR LIGHTING
 CONTROLS.
  
 3) NOTE: PLEASE PROVIDE NEW AND EXISTING LIGHTING
 LOCATIONS. NEED TO VERIFY LIGHTING FOR EGRESS
 REQUIREMENTS OF LOCATION. NEW AREAS APPEAR TO MEET
 MINIMUM LEVELS UNDER BATTERY BACK UP PER NFPA- 101
 7.8.1.3,7.9.1.2,7.9.2.2, FBC 1006.1.2
 PLEASE PROVIDE LIGHTING NEW OR EXISTING FOR BATHROOMS.
  
 4) NOTE: PLEASE SURE TO SHOW CIRCUITING ON PLANS FOR
 NEW. PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY AND
 EXIT LIGHTS.
  
 5) NOTE: PLANS STATE NEW SIGN. PLEASE SEE 600.5 FOR
 REQUIRED DEDICATED SIGN CIRCUIT TO BE SHOWN ALONG WITH
 LOAD PER SAME SECTION. MINIMUM OF 1200VA REQUIRED.
  
 6) NOTE: PLEASE PROVIDE PANEL SCHEDULE OR NOTE NEW
 CIRCUITS. 408.4.
  
 7) NOTE: PLEASE PROVIDE THE LATEST ELECTRICAL RISER FOR
 RECENT SERVICE CHANGE DONE ON PLANS.
 215.5,230.2, 240.4,310.16, 230.70.
  
 ** SOME OF THE ABOVE ITEMS COULD BE SET UP AS A
 PROVISO. PLEASE CALL TO GO OVER.
  
  
 ** LOW VOLTAGE SYSTEMS, INCLUDING FIRE ALARMS ARE NOT
 INCLUDED. SEPARATE PERMITS AS INDICATED ON PLANS
 REQUIRED.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-01-13 Cont ID  
Sent By mawillia Date 2010-01-13 Time 12:49 Rev Time 0.00
Received By mawillia Date 2010-01-13 Time 12:10 Sent To  
Notes
2010-01-13 12:49:41*****APPROVED*****
  
 THE COMMENTS FORM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED AND/OR ACKNOWLEDGED; PLAN SHEETS A101, A103,
 A107, E100, AND F101 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-09-03 Cont ID  
Sent By mcarsill Date 2009-09-03 Time 11:14 Rev Time 0.00
Received By mcarsill Date 2009-09-03 Time 10:30 Sent To  
Notes
2009-09-03 11:12:43519 CLEMATIS STREET
 PERMIT # 09080604
  
  
 1. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
  
 2. PLEASE DOCUMENT ON THE PLANS THE OCCUPANT LOAD FOR
 THE LOCATION.
  
 3. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 4. PLEASE INDICATE IF THE SPACE CONTAINS ANY FIRE
 SPRINKLER OR FIRE ALARM SYSTEMS.
  
 5. PLEASE INDICATE LOCATIONS OF ANY PORTABLE FIRE
 EXTINGUISHER LOCATIONS.
  
 6. THE COVER SHEET INDICATES THE 2007 LIFE SAFETY CODE.
 BE ADVISED IT SHOULD READ THE 2006 EDITION OF THE LIFE
 SAFETY CODE.
  
 7. NO DOOR SCHEDULE PROVIDED. PLEASE PROVIDE A DOOR AND
 HARDWARE SCHEDULE.
  
 8. NO FURNITURE PLAN SUBMITTED, PLEASE PROVIDE A
 FURNITURE PLAN.
  
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2010-07-01 Cont ID  
Sent By vmolina Date 2010-07-01 Time 10:49 Rev Time 0.00
Received By vmolina Date 2010-07-01 Time 10:49 Sent To  
Notes
2010-07-01 10:50:45GAVE TO HM

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-06-10 Cont ID  
Sent By lmartine Date 2010-06-10 Time 17:37 Rev Time 0.00
Received By lmartine Date 2010-06-10 Time 17:34 Sent To  
Notes
2010-06-10 17:40:24B--8
2010-06-10 17:38:12**************EXPEDITED******************
 2ND RUN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-01-07 Cont ID  
Sent By shill Date 2010-01-07 Time 16:07 Rev Time 0.00
Received By shill Date 2010-01-07 Time 16:07 Sent To  
Notes
2010-01-07 16:08:01************** EXPEDITED **************
 B10
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-09-16 Cont ID  
Sent By jwitmer Date 2009-09-16 Time 15:26 Rev Time 0.00
Received By jwitmer Date 2009-08-26 Time 16:30 Sent To  
Notes
2009-08-26 16:38:51B-17

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2010-07-07 Cont ID  
Sent By hmoser Date 2010-07-07 Time 14:31 Rev Time 0.00
Received By hmoser Date 2010-07-07 Time 14:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2010-06-18 Cont ID  
Sent By hmoser Date 2010-06-18 Time 10:22 Rev Time 0.00
Received By hmoser Date 2010-06-18 Time 10:22 Sent To  
Notes
2010-06-18 10:28:18PLAN DENIED
 1) REVIEW STOP #2 WAS NOT ANGERED FROM LAST REVIEW .
 2) PAGE M100 IS MISSING FROM THE SET OF PLANS .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-01-21 Cont ID  
Sent By rregueir Date 2010-01-21 Time 08:41 Rev Time 0.00
Received By rregueir Date 2010-01-21 Time 08:12 Sent To  
Notes
2010-01-21 08:39:56REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. FLOOR PLAN INDICATES CEILING MOUNTED EXHAUST FANS TO
 BE USED IN RESTROOMS. HOWEVER, NOTES ON FAN SCHEDULE
 CALL FOR A SOUND ATTENUATED ROOF CURB AND DETAIL ON
 PAGE M102 SHOWS A ROOF MOUNTED FAN. PLEASE COORDINATE
 FLOOR PLANS, SCHEDULE NOTES AND DETAILS TO SHOW ACTUAL
 SCOPE OF WORK IN ACCORDANCE WITH FBC-B 106.1.1.
  
 2. A/C EQUIPMENT SCHEDULE SHOWS FOUR RTU'S WHILE THE
 FLOOR PLAN SHOWS FIVE RTU'S. ALSO, SCHEDULE SHOWS SPLIT
 SYSTEM AC-1, WHILE FLOOR PLAN SHOWS AH-5. PLEASE
 COORDINATE FLOOR PLANS AND SCHEDULE TO SHOW ACTUAL
 SCOPE OF WORK IN ACCORDANCE WITH FBC-B 106.1.1.
  
 3. LOCATION OF CONDENSER FOR SPLIT A/C SYSTEM IS NOT
 SHOWN ON PLANS. SHOW THE LOCATION WITH WIND RESISTANT
 INSTALLATION DETAILS IN ACCORDANCE WITH FBC-M 301.12.
  
 4. PROVIDE MANUFACTURER'S WIND RESISTANCE DATA FOR ALL
 OUTDOOR APPLIANCES AND EQUIPMENT EXPOSED TO WIND, SUCH
 AS RTU'S, ROOF CURBS/CAPS, CONDENSERS, FANS, ETC. IN
 ACCORDANCE WITH FBC-M 301.12.
  
 5. SHOW LOCATION OF DUCT SMOKE DETECTORS ON PLANS IN
 ACCORDANCE WITH FBC-M 606.2.1.
  
 6. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN
 ACCORDANCE WITH FBC-M 307.2.1.
  
 NOTE: SEPARATE PLANS AND PERMIT APPLICATIONS SHALL BE
 SUMITTED FOR THE FOLLOWING:
 COMMERCIAL KITCHEN EXHAUST SYSTEM
 HOOD FIRE SUPPRESSION SYSTEM
 WALK-IN COOLER AND FREEZER
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2010-06-17 Cont ID  
Sent By lwagner Date 2010-06-17 Time 09:54 Rev Time 0.00
Received By lwagner Date 2010-06-16 Time 15:23 Sent To  
Notes
2010-06-17 09:55:43PLUMBING PERMIT REQUIRED
  
 NO GAS INCLUDED IN THIS REVIEW

Review Stop P PLUMBING
Rev No 2 Status F Date 2010-01-20 Cont ID  
Sent By kstevens Date 2010-01-20 Time 08:32 Rev Time 0.00
Received By kstevens Date 2010-01-20 Time 08:32 Sent To  
Notes
2010-01-20 09:07:24DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 BUILDING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
 FBC-2007 EXISTING BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. COVER SHEET INDICATES EXISTING RESTAURANT AREA. THIS
 IS NOT SHOWN ON THE PLANS. PLEASE SHOW THE EXISTING
 KITCHEN AREA, OR IF THE KITCHEN AREA IS TO BE DEMO'D
 PLEASE INDICATE. SECTION 106.1.2 (MORE INFORMATION
 REQUIRED). IF DEMOLITION OF THE KITCHEN AREA, THEN
 DEMOLITION WORK SHALL BE SHOWN ON THE PLANS OR A
 SEPARATE DEMO PERMIT WITH PLANS WILL BE REQUIRED.
 SECTION 105.1.
 ****NO RESPONSE, COMMENT NOT ADDRESSED. PLEASE SUBMIT
 AN EXISTING FLOOR PLAN TO VERIFY ALL WORK TO BE DONE ON
 THIS PROJECT.
  
 2. OK
 3. OK
  
 4. A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED FOR ALL
 NEW WORK. SECTION 106.3.5.1.3(3)(5)((10)(13).
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 5. PER TABLE 403.1 A SERVICE SINK AND A DRINKING
 FOUNTAIN ARE REQUIRED. PLEASE SHOW THE LOCATION OF EACH
 REQUIRED FIXTURE.
 ****NO RESPONSE, BUT A MOP SINK IS INDICATED ON THE
 FLOOR PLAN NEW SHEET A101. THE REQUIREMENT FOR THE
 DRINKING FOUNTAIN IS ADDRESSED WITH EXCEPTION IN
 SECTION 4101.
  
 6. A WATER HEATER IS REQUIRED PER SECTION 607.1. PLEASE
 SHOW THE LOCATION OF THE REQUIRED WATER HEATER.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 7. BECAUSE OF THE LACK OF INFORMATION ON PLANS,
 DEPENDING ON COMMENT RESPONSES, MORE COMMENTS MAY BE
 FORTHCOMING.
 ****SEE NEW COMMENTS.
  
 **********NEW COMMENTS**********
  
 1B. COVER SHEET SEATING CAPACITY TOTAL OF 184, BUT A
 COUNT OF ALL SEATS INCLUDING THOSE ON THE EXISTING
 PATIO INDICATES 210 SEATS. PLEASE CLARIFY.
  
 2B. SHT A101 IS NOT SIGNED, SEALED AND DATED AS
 REQUIRED IN SECTION 106.1 OF THE FBC ADMINISTRATION AS
 WELL AS FAC 61G1-16 & FS 481.2055.
  
 3. SHT A101 SHOWS THE WOMEN'S TOILET ROOM BEING
 ALTERED. PER SECTION 11-4.1.6(1)(B) IF EXISTING
 ELEMENTS, SPACES, OR COMMON AREAS ARE ALTERED, THEN
 EACH SUCH ALTERED ELEMENT, SPACE, FEATURE, OR AREA
 SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION
 11-4.1.1 TO SECTION 11-4.1.3. THE WOMEN'S ACCESSIBLE
 STALL SHALL COMPLY WITH FIGURE 11-30(E).
  
 4B. SHT P100 SHOWS A GREASE INTERCEPTOR. IS THIS AN
 EXISTING INTERCEPTOR. INDICATE THE SIZE OF THE
 INTERCEPTOR. SECTION 1003.1.
  
 5B. SHT P100 SANITARY/GREASE RISER DIAGRAM, WASTE THAT
 DO NOT REQUIRE SEPARATION OR TREATMENT SHALL NOT BE
 DISCHARGE INTO ANY SEPARATOR OR INTERCEPTOR. THE FLOOR
 SINKS USED FOR DRAINING THE COOLERS & RINSE SINKS IN
 THE BAR AREA SHALL BE DISCHARGED TO THE SANITARY
 SYSTEM. SECTION 1003.2.
  
 6B. SHT P100 SANITARY/GREASE RISER DIAGRAM. THE MOP
 SINK SHALL DRAIN INTO THE GREASE INTERCEPTOR. SECTION
 1003.3.3.1. (NOT SHOWN ON RISER DIAGRAM).
  
 7B. SHT P100 SANITARY/GREASE RISER DIAGRAM SHOWS A VENT
 DOWNSTREAM OF THE FLOOR SINKS AT THE BAR. PER SECTIONS
 905.3 & 905.4 THE VENT SHALL BE CONNECTED ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE AND SHALL RISE
 VERTICALLY A MINIMUM OF 6" ABOVE THE FLOOD RIM LEVEL OF
 THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
  
 8B. SHT P100 SANITARY/GREASE RISER DIAGRAM DOES NOT
 REFLECT THE CHANGES INDICATED IN THE WOMEN'S TOILET
 ROOM.
  
 9B. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT
 APPLICATION AND PLANS PRIOR TO COMMENCING GAS WORK.
 SECTION 105.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE, COMMENT NOT ADDRESSED. (NO WRITTEN
 RESPONSE SUBMITTED).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-09-10 Cont ID  
Sent By kstevens Date 2009-09-10 Time 08:38 Rev Time 0.00
Received By kstevens Date 2009-09-10 Time 08:38 Sent To  
Notes
2009-09-10 09:08:51DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 BUILDING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
 FBC-2007 EXISTING BUILDING
  
 1. COVER SHEET INDICATES EXISTING RESTAURANT AREA. THIS
 IS NOT SHOWN ON THE PLANS. PLEASE SHOW THE EXISTING
 KITCHEN AREA, OR IF THE KITCHEN AREA IS TO BE DEMO'D
 PLEASE INDICATE. SECTION 106.1.2 (MORE INFORMATION
 REQUIRED). IF DEMOLITION OF THE KITCHEN AREA, THEN
 DEMOLITION WORK SHALL BE SHOWN ON THE PLANS OR A
 SEPARATE DEMO PERMIT WITH PLANS WILL BE REQUIRED.
 SECTION 105.1.
  
 2. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER
 TABLES 1004.1.1 (BLDG) & 403.1 (PLUMBING). IF ASSEMBLY
 WITH FIXED SEATS, (SECTION 1004.7), SHOW THE FIXED
 SEATING. IF ASSEMBLY CONCENTRATED, (CHAIRS ONLY - NOT
 FIXED), SHOW THE CHAIRS. IF ASSEMBLY STANDING SPACE.
 PLEASE INDICATE. IF ASSEMBLY UNCONCENTRATED, (TABLES &
 CHAIRS), SHOW THE TABLES & CHAIRS. SECTIONS 1004 &
 403..
  
 3. SHT A.02 MEN'S TOILET ROOM SHOWS THE EXISTING STALL
 WITH A LAV, BUT SHT A.03 SHOWS THE NEW STALL WITHOUT
 THE LAV. PER SECTION 11-4.1.6(1)(A), NO ALTERATION
 SHALL BE UNDERTAKEN WHICH DECREASES OR HAS THE EFFECT
 OF DECREASING ACCESSIBILITY OR USABILITY OF A BUILDING
 OR FACILITY BELOW THE REQUIREMENT FOR NEW CONSTRUCTION
 AT THE TIME OF ALTERATION. PER SECTION 11-4.1.6(1)(B)
 IF EXISTING ELEMENTS, SPACES, OR COMMON AREAS ARE
 ALTERED, THEN EACH SUBH ALTERED ELEMENT, SPACE,
 FEATURE, OR AREA SHALL COMPLY WITH THE APPLICABLE
 PROVISIONS OF SECTION 11-4.1.1 TO SECTION 11-4.1.3.,
 MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION.
  
 4. A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED FOR ALL
 NEW WORK. SECTION 106.3.5.1.3(3)(5)((10)(13).
  
 5. PER TABLE 403.1 A SERVICE SINK AND A DRINKING
 FOUNTAIN ARE REQUIRED. PLEASE SHOW THE LOCATION OF EACH
 REQUIRED FIXTURE.
  
 6. A WATER HEATER IS REQUIRED PER SECTION 607.1. PLEASE
 SHOW THE LOCATION OF THE REQUIRED WATER HEATER.
  
 7. BECAUSE OF THE LACK OF INFORMATION ON PLANS,
 DEPENDING ON COMMENT RESPONSES, MORE COMMENTS MAY BE
 FORTHCOMING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2010-01-13 Cont ID  
Sent By aaponte Date 2010-01-13 Time 15:31 Rev Time 0.00
Received By aaponte Date 2010-01-13 Time 15:31 Sent To  
Notes
2010-01-13 15:32:26PROVISO:
 FOLDING DOORS AND DOOR CANNOT ENCROACH MORE THAN 2 FEET
 INTO THE EXISTING SIDEWALK. PROPOSED DOORS MUST BE
 SETBACK. PROVISO AMENDED BASED ON TECHNICAL HARDSHIP,
 DOORS SHALL NOT ENCROACH MORE THAN 2 FEET 6 INCHES INTO
 THE EXISTING SIDEWALK (2/10/10)

Review Stop Z ZONING
Rev No 1 Status F Date 2009-09-02 Cont ID  
Sent By aaponte Date 2009-09-02 Time 09:13 Rev Time 0.00
Received By aaponte Date 2009-09-02 Time 09:13 Sent To  
Notes
2009-09-02 09:59:301. PLEASE PROVIDE A SURVEY OF THE PROPERTY INDICATING
 THE DIMENSIONS OF THE EXISTING SIDEWALK , BUILDING AND
 THE PROPERTY LINE.
 2. PLEASE VERIFY THE EXISTING LOCATION OF STOREFRONT IS
 ACCURATELY DEPICTED BASED ON A SURVEY.
 2. DOORS ARE ENCROACHING INTO THE SIDEWALK SETBACK.


Account Summary | Usage Policy | Privacy Policy