Plan Review Details - Permit 09080591
Plan Review Stops For Permit 09080591
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-09-23 Cont ID  
Sent By jwitmer Date 2009-09-23 Time 10:00 Rev Time 0.25
Received By jwitmer Date 2009-09-23 Time 09:46 Sent To  
Notes
2009-09-23 09:50:17REVISON: LS-2, LS2.1 & A1 TENAT WALL RATING REVISON

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-08-26 Cont ID  
Sent By jwitmer Date 2009-08-26 Time 16:48 Rev Time 0.44
Received By jwitmer Date 2009-08-26 Time 16:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-08-31 Cont ID  
Sent By dwise Date 2009-08-31 Time 18:35 Rev Time 0.00
Received By dwise Date 2009-08-31 Time 18:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-09-03 Cont ID  
Sent By mawillia Date 2009-09-03 Time 12:14 Rev Time 0.00
Received By mawillia Date 2009-09-03 Time 11:53 Sent To  
Notes
2009-09-03 11:53:31*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS LS-2, LS-2.1, E-3, & FP-1 WERE
 STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-08-26 Cont ID  
Sent By mawillia Date 2009-08-26 Time 15:00 Rev Time 0.00
Received By mawillia Date 2009-08-26 Time 13:22 Sent To  
Notes
2009-08-26 14:59:32*****PARTIAL APPROVAL*****
  
 1. THE PROJECT SITE ADDRESS, INCLUDING THE SUITE NUMBER
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 2. BE ADVISED OF THE CURRENTLY ADOPTED CODE EDITIONS AS
 FOLLOWS: NFPA 1 -2006 EDITION, NFPA 101 - 2006 EDITION,
 NFPA 241 - 2004 EDITION .......ON SHEET LS-2.1, AMEND
 APPLICABLE CODES
  
 (PLAN SHEETS LS-2, LS-2.1, E-3, & FP-1 TO BE
 FIRE-STAMPED WHEN THE ABOVE AS WELL AS ANY OTHER PLAN
 EXAMINERS' COMMENTS HAVE BEEN ADDRESSED)
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-22 Cont ID  
Sent By lmartine Date 2009-09-22 Time 16:40 Rev Time 0.00
Received By lmartine Date 2009-09-22 Time 16:40 Sent To  
Notes
2009-09-22 16:40:57GAVE TO JIM

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-31 Cont ID  
Sent By dwise Date 2009-08-31 Time 18:35 Rev Time 0.00
Received By dwise Date 2009-08-26 Time 13:09 Sent To  
Notes
2009-08-26 13:19:28B-6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-08-31 Cont ID  
Sent By dwise Date 2009-08-31 Time 18:30 Rev Time 0.00
Received By dwise Date 2009-08-31 Time 18:29 Sent To  
Notes
2009-08-31 18:33:59APPROVED WITH PROVISO:
 1. MUST SUBMIT REVISED MECHANICAL PLAN, FOR REVIEW AND
 APPROVAL, WHICH INDICATES THE SIZE AND TYPE OF REQUIRED
 FIRE DAMPERS TO BE INSTALLED IN BOTH SUPPLY AND RETURN
 AIR DUCTS WHICH PENETRATE THE FIRE RATED WALLS
 INDICATED ON THE PLANS SUBMITTED, PRIOR TO INSTALLATION
 IN THE FIELD. PLEASE INCLUDE FIRE DAMPER SPECIFICATIONS
 AND INSTALLATION DETAILS WHICH HAVE BEEN STAMPED
 "APPROVED AS NOTED" BY THE DESIGN PROFESSIONAL.