Plan Review Details - Permit 09080428
Plan Review Stops For Permit 09080428
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-11-18 Cont ID  
Sent By jwitmer Date 2009-11-18 Time 07:46 Rev Time 0.22
Received By jwitmer Date 2009-11-18 Time 07:46 Sent To  
Notes
2009-11-18 07:47:38PLANS ARE OK, NO NEW BLDG PLANS, PROVISO
 BEFORE INSPCTION WILL NEED FIRE SPRNKLER PLANS
  
 PLANS ARE IN FAILED STATUS UNTIL LICENSED CONTRACTORS
 ARE SIGNED ON WITHIN THE SCOPE OF THEIR LICENSURE. FL S
 S 489.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-08-24 Cont ID  
Sent By jwitmer Date 2009-08-24 Time 15:40 Rev Time 0.66
Received By jwitmer Date 2009-08-24 Time 15:00 Sent To  
Notes
2009-08-24 15:34:36PLANS ARE OK, PROVISO
 BEFORE INSPCTION WILL NEED FIRE SPRNKLER PLANS
 106.3.5.1.1(5)
 EXISTING BUILDING CODE 704.2.1
  
 CONTRACTOR TO SUBMIT FOR PERMIT APPLICATION PLEASE
 IDENTIFY WORK AT BOTH SUITES 200 & 202 AS INDICATED ON
 PLANS.
  
 PLANS ARE IN FAILED STATUS UNTIL LICENSED CONTRACTORS
 ARE SIGNED ON WITHIN THE SCOPE OF THEIR LICENSURE. FL S
 S 489.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2010-01-07 Cont ID  
Sent By dpalmer Date 2010-01-07 Time 15:22 Rev Time 0.00
Received By dpalmer Date 2010-01-07 Time 15:22 Sent To  
Notes
2010-01-07 15:22:54** NEW SETS WITH NEW SHEETS DONE ON 12/28, PLANS WERE
 PLACED ON HOLD ON NOV 24TH WAITING FOR NEW SETS.
  
 TEMP FAILED UNTIL LICENSED CONTRACTOR HAS APPLIED.
 PLANS STAMPED FOR ELECTRICAL. FIRE SHEETS STILL NEED
 STAMPING AS NO STAMPS ARE ON SETS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-09-18 Cont ID  
Sent By dpalmer Date 2009-09-18 Time 12:17 Rev Time 0.00
Received By dpalmer Date 2009-09-18 Time 12:17 Sent To  
Notes
2009-09-18 12:17:36 
  
 ** FAILED REVIEW **
  
 1) NOTE: PERMIT HAS NOT BEEN APPLIED FOR UNDER A
 LICENSED CONTRACTOR.
  
 2) NOTE: THE SUBMITTED RISER AS SHOWN ON E5.1 CONTAINS
 A SUBSTANTIAL AMOUNT OF CODE VIOLATIONS. THE RISER
 SHOWN FOR FEEDS TO FIRE PUMP AND SEVERAL OTHER ASPECTS
 OF SERVICE AS SHOWN IN VIOLATION OF TOO MANY CODES TO
 NOTE. THE APPLIED SCOPE OF WORK IS FOR THE SECOND FLOOR
 TENANT. PLEASE ONLY INCLUDE ELECTRICAL FOR THIS
 RELEVANT SPACE AND EQUIPMENT ONLY.
 ** IT SHOULD BE NOTED IF THE ELECTRICAL AS SHOWN ON
 RISER IS THE ACTUAL INSTALLATION THERE SHOULD BE
 CONCERNS OVER THE INSTALLATION AS SHOWN.
 THERE ARE SEVERAL ITEMS SHOWN ON RISER WHICH ARE LIFE
 SAFETY AND FIRE HAZARDS CONCERNS. IF RISER IS ACCURATE
 THEN THESE ITEMS SHOULD BE ADDRESSED BY THE APPROPRIATE
 PARTIES RESPONSIBLE FOR THE BUILDING.
 PLEASE SEE NFPA-110, NFPA-20 AND NFPA-70 FOR LIFE
 SAFETY, LEGALLY REQUIRED SYSTEMS ALONG WITH FIRE PUMP
 INSTALLATION MINIMUMS.
  
 ** THIS WAS NOTED ON A PREVIOUS PLAN REVIEW SEVERAL
 YEARS AGO.
  
 2) NOTE: THE LOAD SHOWN ON PANEL 2MA APPEARS TO INCLUDE
 ONLY LOADS FOR PANELS 2LA, 2A AND 2B. WHERE IS THE LOAD
 FOR 1LA?
 ALL OF THESE PANELS ARE SHOWN FROM THE SAME 75KVA
 TRANSFORMER. THE TOTAL LOADS AS SHOWN ARE EXCEEDING THE
 RATING OF THE 75 KVA TRANSFORMER.
 PLEASE SEE 450 FOR MAXIMUM ALLOWABLE LOADS. PLEASE SEE
 NEC 220.12,220.14,220.42,220.44 ETC ALONG WITH
 215.3,230.42.
 LOAD CALCULATIONS SHOULD BE DONE TO ACCURATELY DEPICT
 ACTUAL LOAD ON SERVICE EQUIPMENT, TRANSFORMER.
 THE CONDUCTORS ON THE SECONDARY SIDE OF THE TRANSFORMER
 ARE NOTED AS ONE RUN OF 250MCM. ALL PANELS AS SHOWN ARE
 100AMP MCB.
 THIS IS NOT POSSIBLE AS SHOWN/NOTED.
 PLEASE PROVIDE CONDUCTORS ON THE SECONDARY SIDE.
 240.4,240.21C, 310.16, 110.3, 110.14 ETC.
  
 3) NOTE: PANELS 2A AND 2B ARE SHOWN BEING FED FROM 2LA,
 HOWEVER NO BREAKERS ARE INDICATED IN PANEL SCHEDULE. IS
 PANEL 2LA A FEED-THRU LUG PANEL WITH DOUBLE TAPPED
 LUGS?
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-02-10 Cont ID  
Sent By mawillia Date 2010-02-10 Time 11:56 Rev Time 0.00
Received By mawillia Date 2010-02-10 Time 11:46 Sent To  
Notes
2010-02-10 11:56:19*****PARTIAL APPROVAL*****
  
  
 TEMPORARY FAILED UNTIL LICENSED CONTRACTOR HAS APPLIED;
 PLAN SHEETS CS, A-1, A-3, E2.1, AND FA0.1 & FA2.1WERE
 STAMPED, INITIALED, AND DATED.
  
 SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM AND
 FIRE SPRINKLER REMODEL
  
 CAPT MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-08-27 Cont ID  
Sent By mcarsill Date 2009-08-27 Time 07:03 Rev Time 0.00
Received By mcarsill Date 2009-08-27 Time 06:59 Sent To  
Notes
2009-08-27 07:02:25250 SOUTH AUSTRALIAN AVENUE
 PERMIT # 09080428
  
 1. NEW OR EXISTING FIRE DAMPERS WITHIN SUITES SHALL BE
 DROP TESTED TO ENSURE PROPER FUNCTION.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 ALARM SYSTEM REMODEL.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR FOR FIRE
 SPRINKLER SYSTEM REMODEL.
  
 4. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 5. EXITS ARE TO REMAIN CLEAR AND ACCESSIBLE.
  
 APPROVED
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-11-10 Cont ID  
Sent By shill Date 2009-11-10 Time 07:52 Rev Time 0.00
Received By shill Date 2009-11-10 Time 07:52 Sent To  
Notes
2009-11-10 07:52:19B 18
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-09-18 Time   Rev Time 0.00
Received By shill Date 2009-08-19 Time 16:17 Sent To  
Notes
2009-08-19 16:17:11B12
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2009-09-18 Cont ID  
Sent By dpalmer Date 2009-09-18 Time 11:31 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-09-01 Cont ID  
Sent By rregueir Date 2009-09-01 Time 15:48 Rev Time 0.00
Received By rregueir Date 2009-09-01 Time 15:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-09-18 Cont ID  
Sent By dpalmer Date 2009-09-18 Time 11:31 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2009-09-18 11:31:57NO PLUMBING WORK SHOWN OR APPLIED FOR. NO SINK IN
 KITCHEN, WATER OR SANITARY ON PLANS.

Review Stop Z ZONING
Rev No 1 Status N Date 2009-09-08 Cont ID  
Sent By aaponte Date 2009-09-08 Time 07:54 Rev Time 0.00
Received By aaponte Date 2009-09-08 Time 07:54 Sent To  
Notes
***NONE***