2009-09-18 12:17:36 | |
| |
| ** FAILED REVIEW ** |
| |
| 1) NOTE: PERMIT HAS NOT BEEN APPLIED FOR UNDER A |
| LICENSED CONTRACTOR. |
| |
| 2) NOTE: THE SUBMITTED RISER AS SHOWN ON E5.1 CONTAINS |
| A SUBSTANTIAL AMOUNT OF CODE VIOLATIONS. THE RISER |
| SHOWN FOR FEEDS TO FIRE PUMP AND SEVERAL OTHER ASPECTS |
| OF SERVICE AS SHOWN IN VIOLATION OF TOO MANY CODES TO |
| NOTE. THE APPLIED SCOPE OF WORK IS FOR THE SECOND FLOOR |
| TENANT. PLEASE ONLY INCLUDE ELECTRICAL FOR THIS |
| RELEVANT SPACE AND EQUIPMENT ONLY. |
| ** IT SHOULD BE NOTED IF THE ELECTRICAL AS SHOWN ON |
| RISER IS THE ACTUAL INSTALLATION THERE SHOULD BE |
| CONCERNS OVER THE INSTALLATION AS SHOWN. |
| THERE ARE SEVERAL ITEMS SHOWN ON RISER WHICH ARE LIFE |
| SAFETY AND FIRE HAZARDS CONCERNS. IF RISER IS ACCURATE |
| THEN THESE ITEMS SHOULD BE ADDRESSED BY THE APPROPRIATE |
| PARTIES RESPONSIBLE FOR THE BUILDING. |
| PLEASE SEE NFPA-110, NFPA-20 AND NFPA-70 FOR LIFE |
| SAFETY, LEGALLY REQUIRED SYSTEMS ALONG WITH FIRE PUMP |
| INSTALLATION MINIMUMS. |
| |
| ** THIS WAS NOTED ON A PREVIOUS PLAN REVIEW SEVERAL |
| YEARS AGO. |
| |
| 2) NOTE: THE LOAD SHOWN ON PANEL 2MA APPEARS TO INCLUDE |
| ONLY LOADS FOR PANELS 2LA, 2A AND 2B. WHERE IS THE LOAD |
| FOR 1LA? |
| ALL OF THESE PANELS ARE SHOWN FROM THE SAME 75KVA |
| TRANSFORMER. THE TOTAL LOADS AS SHOWN ARE EXCEEDING THE |
| RATING OF THE 75 KVA TRANSFORMER. |
| PLEASE SEE 450 FOR MAXIMUM ALLOWABLE LOADS. PLEASE SEE |
| NEC 220.12,220.14,220.42,220.44 ETC ALONG WITH |
| 215.3,230.42. |
| LOAD CALCULATIONS SHOULD BE DONE TO ACCURATELY DEPICT |
| ACTUAL LOAD ON SERVICE EQUIPMENT, TRANSFORMER. |
| THE CONDUCTORS ON THE SECONDARY SIDE OF THE TRANSFORMER |
| ARE NOTED AS ONE RUN OF 250MCM. ALL PANELS AS SHOWN ARE |
| 100AMP MCB. |
| THIS IS NOT POSSIBLE AS SHOWN/NOTED. |
| PLEASE PROVIDE CONDUCTORS ON THE SECONDARY SIDE. |
| 240.4,240.21C, 310.16, 110.3, 110.14 ETC. |
| |
| 3) NOTE: PANELS 2A AND 2B ARE SHOWN BEING FED FROM 2LA, |
| HOWEVER NO BREAKERS ARE INDICATED IN PANEL SCHEDULE. IS |
| PANEL 2LA A FEED-THRU LUG PANEL WITH DOUBLE TAPPED |
| LUGS? |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |