Plan Review Details - Permit 09080427
Plan Review Stops For Permit 09080427
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-11-18 Cont ID  
Sent By jwitmer Date 2009-11-18 Time 07:43 Rev Time 0.22
Received By jwitmer Date 2009-11-18 Time 07:42 Sent To  
Notes
2009-11-18 07:43:22PLANS ARE OK, PROVISO
 BEFORE INSPCTION WILL NEED FIRE SPRNKLER PLANS
  
 PLANS ARE IN FAILED STATUS UNTIL LICENSED CONTRACTORS
 ARE SIGNED ON WITHIN THE SCOPE OF THEIR LICENSURE. FL S
 S 489.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-08-24 Cont ID  
Sent By jwitmer Date 2009-08-24 Time 14:48 Rev Time 0.50
Received By jwitmer Date 2009-08-24 Time 14:48 Sent To  
Notes
2009-08-24 14:48:41PLANS ARE OK, PROVISO
 BEFORE INSPCTION WILL NEED FIRE SPRNKLER PLANS
  
 PLANS ARE IN FAILED STATUS UNTIL LICENSED CONTRACTORS
 ARE SIGNED ON WITHIN THE SCOPE OF THEIR LICENSURE. FL S
 S 489.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2010-01-07 Cont ID  
Sent By dpalmer Date 2010-01-07 Time 16:02 Rev Time 0.00
Received By dpalmer Date 2010-01-07 Time 16:02 Sent To  
Notes
2010-01-07 16:03:02** NEW SETS WITH NEW SHEETS DONE ON 12/28, PLANS WERE
 PLACED ON HOLD ON NOV 24TH WAITING FOR NEW SETS.
  
 TEMP FAILED UNTIL LICENSED CONTRACTOR HAS APPLIED.
 PLANS STAMPED FOR ELECTRICAL. FIRE SHEETS STILL NEED
 STAMPING AS NO STAMPS ARE ON SETS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-09-18 Cont ID  
Sent By dpalmer Date 2009-09-18 Time 11:24 Rev Time 0.00
Received By dpalmer Date 2009-09-18 Time 11:24 Sent To  
Notes
2009-09-18 11:24:35 
 ** FAILED REVIEW **
  
 1) NOTE: PERMIT HAS NOT BEEN APPLIED FOR UNDER A
 LICENSED CONTRACTOR.
  
 2) NOTE: ROOM 1503 IS SHOWN AS A UTILITY/STORAGE ROOM.
 THE ELECTRICAL PANEL AND TRANSFORMER ARE NOT PERMITTED
 IN THIS LOCATION.
 240.24D.
 PLEASE KNOW THIS MAY ONLY BE A DEDICATED ELECTRICAL
 ROOM WITH SIGNAGE AS REQUIRED.
  
 2) NOTE: THE RISER ON SHEET E 5.1 IS NOT ACCURATE. THE
 PLANS INDICATE PANELS AND EQUIPMENT 15TH FLOOR YET THE
 RISER INDICATE THAT THERE IS A PANEL 16LA FED FROM THE
 SAME TRANSFORMER AS SHOWN FOR OTHER 15TH FLOOR PANELS.
 BASED ON THE EQUIPMENT ON E0.1 FOR THE ELECTRICAL ROOM
 THIS APPEARS IT SHOULD HAVE BEEN LABELED AS PANEL 15LA?
 THE TAPPED CONDUCTORS AS SHOWN ON TRANSFORMER SCHEDULE
 WOULD ALSO NOT BE ACCURATE.
 IF THIS EQUIPMENT DOES NOT APPLY TO THE SCOPE OF WORK
 OR TO THIS TENANT THEN IT MAY BE REMOVED FROM PLANS.
  
  
 ** AS THESE ARE THE ONLY COMMENTS, THEY COULD BE
 REDLINED ON AND FROM PLANS ONCE LICENSED CONTRACTOR IS
 ON APPLICATION. PLANS WILL BE REQUIRED TO BE REVISED AT
 SOME POINT TO ACCURATELY ADDRESS COMMENTS ABOVE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-02-10 Cont ID  
Sent By mawillia Date 2010-02-10 Time 11:45 Rev Time 0.00
Received By mawillia Date 2010-02-10 Time 11:12 Sent To  
Notes
2010-02-10 11:28:42*****PARTIAL APPROVAL*****
  
  
 TEMPORARY FAILED UNTIL LICENSED CONTRACTOR HAS APPLIED;
 PLAN SHEETS CS, A-1, A-3, E2.1, AND FA0.1 & FA2.1WERE
 STAMPED, INITIALED, AND DATED.
  
 SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM AND
 FIRE SPRINKLER REMODEL
  
 CAPT MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-08-27 Cont ID  
Sent By mcarsill Date 2009-08-27 Time 07:13 Rev Time 0.00
Received By mcarsill Date 2009-08-27 Time 07:11 Sent To  
Notes
2009-08-27 07:13:20250 SOUTH AUSTRALIAN AVENUE
 PERMIT # 09080427
  
 1. EXISTING FIRE DAMPERS ARE TO BE DROP TESTED TO
 ENSURE PROPER OPERATION.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 ALARM SYSTEM REMODEL.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 SPRINKLER SYSTEM REMODEL.
  
  
 APPROVED
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-11-10 Cont ID  
Sent By shill Date 2009-11-10 Time 09:12 Rev Time 0.00
Received By shill Date 2009-11-10 Time 09:12 Sent To  
Notes
2009-11-10 09:12:36B 18
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-09-18 Time   Rev Time 0.00
Received By shill Date 2009-08-19 Time 16:15 Sent To  
Notes
2009-08-19 16:15:58B12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2009-09-18 Cont ID  
Sent By dpalmer Date 2009-09-18 Time 11:20 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-09-01 Cont ID  
Sent By rregueir Date 2009-09-01 Time 15:26 Rev Time 0.00
Received By rregueir Date 2009-08-31 Time 16:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-09-18 Cont ID  
Sent By dpalmer Date 2009-09-18 Time 11:20 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2009-09-18 11:21:25NO PLUMBING WORK SHOWN OR APPLIED FOR. NO SINK IN
 KITCHEN, WATER OR SANITARY ON PLANS.

Review Stop Z ZONING
Rev No 1 Status N Date 2009-09-08 Cont ID  
Sent By aaponte Date 2009-09-08 Time 07:52 Rev Time 0.00
Received By aaponte Date 2009-09-08 Time 07:52 Sent To  
Notes
***NONE***