2009-09-18 10:34:32 | |
| ** FAILED REVIEW ** |
| |
| 1) NOTE: PERMIT HAS NOT BEEN APPLIED FOR UNDER A |
| LICENSED CONTRACTOR. |
| |
| 2) NOTE: PLANS INDICATE TWO LIGHTING CIRCUITS. 16MA-27 |
| AND 16MA-29, HOWEVER PANEL SCHEDULE DOES NOT LIST |
| CIRCUIT 27 FOR THIS TENANT. IT DOES LIST CIRCUIT #31, |
| WHICH IS NOT ON THE PLANS. |
| IF THIS HAD BEEN THE ONLY COMMENT PLANS WOULD HAVE BEEN |
| REDLINED. |
| |
| 3) NOTE: PLEASE CORRELATE RISER AND PANELS. PLEASE SEE |
| 16MA PANEL ON RISER. THIS IS THE 277/480V 225AMP PANEL |
| WHICH IS SHOWN FEEDING TRANSFORMER AND OTHER PANELS. |
| HOWEVER THE PANEL SCHEDULE FOR 16MA STATES THE SUB FEED |
| TO THE SAME PANEL 16MA. ( MISPRINT?) |
| PLEASE SEE THE RISER WHICH INDICATES TWO SECONDARY TAPS |
| FROM THE 75KVA TRANSFORMER. ONE TAP TO 16LA AND ONE TO |
| 16LB. PER THE TRANSFORMER SCHEDULE THE SECONDARY |
| CONDUCTORS ARE ONLY ONE SET OF 250MCM. |
| THERE ARE TWO COMMENTS HERE. |
| A) THERE IS ONLY ONE SET INDICATED, WHERE IS THE OTHER |
| ONE? |
| B) PANEL 16LA IS SHOWN AS A 100AMP MCB. 250 MCM WILL |
| NOT FIT UNDER LUGS OF A 100AMP BREAKER. THIS IS |
| BASICALLY THE SAME COMMENT FOR 16LB WHICH IS A 150AMP |
| MCB PANEL WITH 250MCM. |
| |
| PLEASE MAKE ADJUSTMENTS AND CORRECTIONS. |
| 310.16,240.4,240.21C, 408.36 ETC SHOW TAPPED CONDUCTORS |
| TO EACH. |
| |
| 4) NOTE: PLEASE SEE KEY PLAN ON SHEET E-0.1. IN THE |
| LOWER LEFT HAND SIDE IN THE STORAGE ROOM OF THIS NEW |
| TENANT SPACE THERE APPEARS TO BE NEW PANELS. THERE ARE |
| DARK SQUARE SHAPES WHICH APPEAR TO BE PANELS. BASED ON |
| THE REST OF THE PLANS THERE ARE NO PANELS IN THE |
| STORAGE ROOM. PLEASE SEE 110.26 AND 240.24D AS THESE |
| WOULD NOT BE PERMITTED IN STORAGE CLOSETS. |
| |
| 5) NOTE: PANEL 16LA AS SHOWN ON E0.1 DOES NOT MEET |
| 110.26 AS SHOWN. PLEASE VERIFY AND RELOCATE AS THIS IS |
| A SAFETY CODE COMMENT. |
| |
| 6) NOTE: THE AMOUNT OF FIXTURES INDICATED FOR THE |
| CORRIDOR PERFORMANCE CALCULATIONS ARE SHORT BY A |
| RECESSED LIGHTING FIXTURE. STATES 5 WHEN THERE ARE |
| 6.THIS WOULD NOT BE CONSIDERED A GROSS ERROR PER |
| 13-103.1 |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |