Plan Review Details - Permit 09080353
Plan Review Stops For Permit 09080353
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-09-03 Cont ID  
Sent By rmcdouga Date 2009-09-03 Time 09:46 Rev Time 0.00
Received By rmcdouga Date 2009-09-03 Time 09:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-08-18 Cont ID  
Sent By rmcdouga Date 2009-08-18 Time 15:06 Rev Time 0.00
Received By rmcdouga Date 2009-08-18 Time 15:06 Sent To E
Notes
2009-08-18 15:21:142007 FBC W/2009 REVISIONS
 LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF A KEY PLAN AND CORRESPONDING
 INSTALLATION SCHEDULE FOR THE STORM PANELS. SPECIFY THE
 OPENING SIZES, WIND PRESSURES, MOUNT TYPE, CONNECTION
 TYPE, FASTENER OR ANCHOR TYPE AND SPACING, ETC. FBC
 R301.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-09-01 Cont ID  
Sent By btrobaug Date 2009-09-01 Time 15:02 Rev Time 0.00
Received By btrobaug Date 2009-09-01 Time 14:53 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-19 Cont ID  
Sent By btrobaug Date 2009-08-19 Time 12:35 Rev Time 0.00
Received By btrobaug Date 2009-08-19 Time 12:23 Sent To I
Notes
2009-08-19 12:35:29 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} THE DESCRIPTION ON THE APPLICATION INDICATES
 ELECTRICAL WORK TO BE DONE UNDER THIS PERMIT BUT NO
 ELECTRICAL PLANS WERE SUBMITTED. SUBMIT PLANS
 INDICATING THE SCOPE OF WORK, OR REMOVE THE ELECTRICAL
 WORK FROM THE APPLICATION. 106.1 FBC AS AMENDED.
  
 2} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3).
 IF APPLICABLE.
  
 3} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2
 RESIDENTIAL FLORIDA BUILDING CODE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-01 Cont ID  
Sent By kstevens Date 2009-09-01 Time 10:33 Rev Time 0.00
Received By kstevens Date 2009-09-01 Time 10:33 Sent To  
Notes
2009-09-01 10:34:45SENT TO BTROBAUGH.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-19 Cont ID  
Sent By btrobaug Date 2009-08-19 Time 12:36 Rev Time 0.00
Received By btrobaug Date 2009-08-17 Time 15:55 Sent To  
Notes
2009-08-19 12:37:01 
  
 TO HOLDING BIN./WRT.
2009-08-17 15:55:36R-10

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-08-18 Cont ID  
Sent By rmcdouga Date 2009-08-18 Time 15:04 Rev Time 0.00
Received By rmcdouga Date 2009-08-18 Time 15:04 Sent To  
Notes
2009-08-18 15:05:47NO MECHANICAL CONTRACTOR SIGNED ON APPLICATION AND NO
 MECHANICAL INFORMATION OR PLANS SUBMITTED.