Plan Review Details - Permit 09080328
Plan Review Stops For Permit 09080328
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-08-19 Cont ID  
Sent By rmcdouga Date 2009-08-19 Time 08:59 Rev Time 0.00
Received By rmcdouga Date 2009-08-19 Time 08:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-08-25 Cont ID  
Sent By btrobaug Date 2009-08-25 Time 12:13 Rev Time 0.00
Received By btrobaug Date 2009-08-25 Time 12:00 Sent To I
Notes
2009-08-25 12:12:25 
  
 PROVISO
  
 1} SMALL APPLIANCE CIRCUITS MISSING FROM PANEL
 SCHEDULE. MINIMUM 2@20 AMPS. 210.11(C)(1).
  
 2} BATH CIRCUITS ON SCHEDULE @ 15 AMPS. SEE
 210.11(C)(3).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-25 Cont ID  
Sent By btrobaug Date 2009-08-25 Time 12:13 Rev Time 0.00
Received By btrobaug Date 2009-08-14 Time 08:36 Sent To PC
Notes
2009-08-14 08:46:13R-9

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-08-18 Cont ID  
Sent By kstevens Date 2009-08-18 Time 14:55 Rev Time 0.00
Received By kstevens Date 2009-08-18 Time 14:55 Sent To  
Notes
2009-08-18 14:56:08FIXTURE REMOVAL & RESET. SHOWER EXPANDED BATH 2.